118
6
Electrical
control box
1. Detachment
1) Perform works of procedure
1
-1- and
2
-1.
2) Remove connectors of the lead wire connected to the following connectors of the control P.C. board.
CN33:
Louver motor (5P, White)
CN34:
Float switch (3P, Red)
CN68:
Drain pump (3P, Blue)
CN100: TC1 sensor (3P, Brown)
CN101: TC2 sensor (2P, Black)
CN102: TCJ sensor (2P, Red)
CN82:
PMV (6P, Blue)
CN333: Fan motor power supply (5P, White)
CN334: Fan motor position detection (5P, White)
NOTE
Remove the connectors after unlocking the
lock of the housing.
3) Remove each lead wire from cord
clamps in the electrical control box.
4) Remove the power supply wiring,
remote controller wiring, and
crossover wiring.
5) Take off screws (Ø4 × 10, 2 pcs.)
2. Attachment
1) Tighten screws (Ø4 × 10, 2 pcs.) fixing the electrical control box.
2) Connect the connectors as original before being removed in item 1.
3) Perform power supply wiring, remote controller wiring, and crossover wiring between inside and outside.
NOTE
For drawing of each wire and position of ferrite core, perform wiring same as those before removing. If there is
incomplete drawing of wire, short or water leakage of the parts may be caused.
No.
Part name
Procedure
Remarks
Ferrite core for sensor lead
Ferrite core for fan motor
Drawing-out port of lead wire
Card edge spacer
Enlarged drawing
Fix the lead wires with cord clamp
so that the lead wires do not slacken
at P.C board side. (2 positions)
Cord clamp
As shown in the figure, store PMV
lead wire connected with connector
assembly so that the connector
positions under wire of the terminal.
Details of PMV lead wire drawing
Fix the sensor lead wires firmly with the cord clamp
so that they do not touch with the caution plate of
the terminal block and they do not slacken at P.C.
board side. (3 positions)
Arrange the clamp at the position as shown in the
figure.
Cord clamp
Fold back the sensor lead wire and
fix it surely with the cord clamp.
Adhere on the transformer.
Arrow view
Details of sensor lead wire drawing
Be sure that the float switch
lead wire positions at inner side
of the fan motor lead wire.
Cord clamp
Fold back the float switch lead
wire and fix surely with cord
clamp. (There is no catching-
in of P.C. board and lead wire.)
Arrange at position as
shown in the figure.
Details of fan motor lead wire drawing
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...