background image

154

Location No.

Part No.

Description

MMU-

AP0154SH-TR

AP0184SH-TR

AP0244SH-TR

201

43121736 PUMP, DRAIN, ADP-1409

1

1

1

202

43172195 PAN ASSY, DRAIN

1

1

1

203

4314J370 REFRIGERATION CYCLE ASSY

1

1

204

4314J371 REFRIGERATION CYCLE ASSY

1

205

43121742 MOTOR, FAN

1

1

1

206

43146707 MOTOR, PMV

1

1

1

207

43146714 VALVE, PMV

1

1

1

208

43120227 FAN, MULTI BLADE

2

2

2

209

43170244 HOSE, DRAIN

1

1

1

210

43122084 CASE, FAN, LOWER

2

2

2

211

43122085 CASE, FAN, UPPER

2

2

2

212

43079249 BAND, HOSE

1

1

1

213

43047685 NUT, FLARE, 1/4 IN

1

1

214

43049776 SOCKET

1

215

43149351 SOCKET

1

1

216

43047688 NUT, FLARE, 1/2, IN

1

1

217

43149352 NUT, FLARE, 5/8, IN

1

218

43149353 SOCKET

1

1

219

43149354 SOCKET

1

220

43151284 SWITCH, FLOAT

1

1

1

221

43139152 BAND, MOTOR

2

2

2

222

43179129 CAP DRAIN

1

1

1

223

43119481 NUT, PLATE

2

2

2

224

43170240 HOSE, DRAIN

1

1

1

225

43107215 HOLDER, SENSOR

1

1

1

226

43047609 BONNET

1

227

43147195 BONNET, 1/2 IN

1

1

228

43194029 BONNET

1

229

43149355 NUT, FLARE, 3/8, IN

1

230

43049697 BONNET

1

1

231

43019904 HOLDER, SENSOR (TS)

2

2

2

232

43149314 SHEET, PMV

1

1

1

233

43179126 RUBBER, PUMP DRAIN

3

3

3

234

43162051 BUSHING

1

1

1

235

43179149 BAND, HOSE

1

1

1

236

43166011 REMOTE CONTROLLER, SX-A4EE

1

1

1

237

43166012 REMOTE CONTROLLER, SX-A5EE

1

1

1

238

43166004 REMOTE CONTROLLER, SX-A11JE2

1

1

1

239

43166006 REMOTE CONTROLLER, WH-H1JE2

1

1

1

241

431S8206 OWNER'S MANUAL, MMY-MAP0804HT8-TR

1

1

1

Summary of Contents for A03-009

Page 1: ...4H E TR MMC AP0484H E TR Floor Standing Cabinet Type MML AP0074H E TR MML AP0094H E TR MML AP0124H E TR MML AP0154H E TR MML AP0184H E TR MML AP0244H E TR Slim Duct Type MMD AP0074SPH E TR MMD AP0094SPH E TR MMD AP0124SPH E TR MMD AP0154SPH E TR MMD AP0184SPH E TR Floor Standing Type MMF AP0154H E TR MMF AP0184H E TR MMF AP0244H E TR MMF AP0274H E TR MMF AP0364H E TR MMF AP0484H E TR MMF AP0564H E...

Page 2: ...37 5 1 Indoor controller block diagram 37 5 1 1 When main sub remote controller connected 37 5 1 2 When wireless remote controller kit connected 39 5 1 3 When both main sub remote controller and wireless remote controller kit connected 41 5 2 Indoor printed circuit board 43 5 3 Optional connector specifications of indoor P C board 45 5 4 Test operation of indoor unit 46 5 5 Method to set indoor un...

Page 3: ...32 8 6 Ceiling 133 8 7 Floor standing 141 8 8 Floor standing cabinet 144 9 Exploded Diagram Service Parts List 147 9 1 1 way cassette type YH 147 9 2 1 Way cassette type SH 152 9 3 Compact 4 way cassette type 156 9 4 Slim duct type 160 9 5 Concealed duct standard type 164 9 6 Concealed duct high static pressure type 178 9 7 Ceiling type 186 9 8 Floor standing type 193 9 9 Floor standing concealed ...

Page 4: ... is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted...

Page 5: ...lectric shock Work done at heights 50 cm or more Helmets for use in industry Transportation of heavy objects Shoes with additional protective toe cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Indication Explanation DANGER Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when a...

Page 6: ... Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminium fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there...

Page 7: ...n Take steps to ensure that the power will not be turned on by marking out of service near the circuit breaker for instance until qualified service person arrives Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure Electric shock hazard When you access inside of the service panel to repair electric part...

Page 8: ... that no one will approach the work location before proceeding with the work Parts and other objects may fall from above possibly injuring a person below When executing address setting test run or troubleshooting through the checking window on the electric parts box put on insulated gloves to provide protection from electric shock Otherwise you may receive an electric shock Do not touch the alumin...

Page 9: ... cycle Failure to purge the air completely may cause the air conditioner to malfunction Do not charge refrigerant additionally If charging refrigerant additionally when refrigerant gas leaks the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure i...

Page 10: ...here is leak of refrigerant at connecting section of pipes the air is sucked and causes further abnormal high pressure resulted in burst or injury Check after reinstallation Only a qualified installer 1 or qualified service person 1 is allowed to relocate the air conditioner It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury wat...

Page 11: ...s instructions to install the air conditioner Be sure to use the company specified products for the separately purchased parts Use of non specified products may result in fire electric shock water leakage or other failure Have the installation performed by a qualified installer Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit Capacity overflow ...

Page 12: ...H E TR MMD AP0184BH E TR MMD AP0244BH E TR MMD AP0274BH E TR MMD AP0304BH E TR MMD AP0364BH E TR MMD AP0484BH E TR MMD AP0564BH E TR Concealed Duct High Static Pressure Type MMD AP0184H E TR MMD AP0244H E TR MMD AP0274H E TR MMD AP0364H E TR MMD AP0484H E TR MMD AP0724H E TR MMD AP0964H E TR Ceiling Type MMC AP0154H E TR MMC AP0184H E TR MMC AP0244H E TR MMC AP0274H E TR MMC AP0364H E TR MMC AP048...

Page 13: ...AP0484BH E 55 MMD AP0564BH E 55 MMD AP0184H E 50 MMD AP0244H E 52 MMD AP0274H E 52 MMD AP0364H E 56 MMD AP0484H E 67 MMD AP0724H E 160 MMD AP0964H E 70 70 160 MMD AP0074SPH E 22 MMD AP0094SPH E 22 MMD AP0124SPH E 22 MMD AP0154SPH E 23 MMD AP0184SPH E 23 MMC AP0154H E 22 MMC AP0184H E 22 MMC AP0244H E 26 MMC AP0274H E 26 MMC AP0364H E 34 MMC AP0484H E 34 MML AP0074H E 37 MML AP0094H E 37 MML AP0124...

Page 14: ...D AP0564BH TR 55 MMD AP0184H TR 50 MMD AP0244H TR 52 MMD AP0274H TR 52 MMD AP0364H TR 56 MMD AP0484H TR 67 MMD AP0724H TR 160 MMD AP0964H TR 70 70 160 MMD AP0074SPH TR 22 MMD AP0094SPH TR 22 MMD AP0124SPH TR 22 MMD AP0154SPH TR 23 MMD AP0184SPH TR 23 MMC AP0154H TR 22 MMC AP0184H TR 22 MMC AP0244H TR 26 MMC AP0274H TR 26 MMC AP0364H TR 34 MMC AP0484H TR 34 MML AP0074H TR 37 MML AP0094H TR 37 MML A...

Page 15: ...rminal block indicates the connection terminal indicates the connector on the control P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN Symbol Parts Name CN Connector DM Drain Pump Motor F301 302 Fuse FM Fan Motor FS Float Switch LM1 2 Louver Motor PMV Pulse Motor Valve RY30...

Page 16: ...ol P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN Remote Controller Sub P C Board Outdoor unit Power supply circuit COLOR IDENTIFICATION Symbol Parts Name CN Connector DM Drain Pump Motor F301 302 Fuse FM Fan Motor FS Float Switch LM Louver Motor PMV Pulse Motor Valve RY0...

Page 17: ... the control P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN Outdoor unit Power supply circuit COLOR IDENTIFICATION Symbol Parts Name CN Connector DM Drain Pump Motor F301 302 Fuse FM Fan Motor FS Float Switch LM Louver Motor PMV Pulse Motor Valve RY302 Drain Control Relay...

Page 18: ...ck indicates the connection terminal indicates the connector on the control P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN Outdoor unit Power supply circuit COLOR IDENTIFICATION Symbol Parts Name CN Connector DM Drain Pump Motor F301 302 Fuse FM Fan Motor FS Float Switch ...

Page 19: ... motor Control Relay CN Connector F Fuse F301 Fuse FM Fan Motor PMV Pulse Motor Valve RC Running Capacitor RY002 Drain Control Relay RY005 006 007 Fan Motor Control Relay TA Indoor temp sensor TB01 02 03 Terminal Block TC1 2 TCJ Temp sensor TR Transformer Sold Separately DM Drain Pump Motor FS Float Switch 1 Broken line indicate the wiring at site Long dashed short dashed line indicate the accesso...

Page 20: ...e drain pump connect the froat switch connector to CN30 connector 6 position is connected to terminal block when change to static pressure Exchange the lead wire of arrow position after check the terminal number as figure and lead wire s color of fan motor 7 Be careful when modify the static pressure the static pressure of high tap is different by 50Hz or 60Hz Terminal No Fan motor wiring Static p...

Page 21: ...Indoor temp sensor TB01 02 Terminal Block TC1 2 TCJ Temp sensor 1 Broken line indicate the wiring at site Long dashed short dashed line indicate the accessories 2 indicates the terminal block indicates the connection terminal indicates the connector on the control P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY ...

Page 22: ...tes the protection ground 4 indicates the control P C board 5 When installing the drain pump connect the froat switch connector to CN34 connector RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN COLOR IDENTIFICATION Symbol Parts Name CN Connector F301 302 Fuse FM Fan Motor LM Louver Motor PMV Pulse Motor Valve RY302 Drain Control Relay TA Indoor temp...

Page 23: ...ndicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN COLOR IDENTIFICATION Remote Controller Outdoor unit Power supply 1 50Hz 220 240V 1 60Hz 220V Indoor unit Earth screw Flow selector unit Earth screw Control P C Board for Indoor Unit Power supply circuit Line Filter Sub P C Board Symbol Parts Name CN Connector F301 Fuse FM...

Page 24: ...es the terminal block indicates the connection terminal indicates the connector on the control P C board 3 indicates the protection ground 4 indicates the control P C board RED RED WHI WHITE YEL YELLOW BLU BLUE BLK BLACK GRY GRAY PNK PINK ORN ORANGE BRW BROWN GRN GREEN COLOR IDENTIFICATION Symbol Parts Name CN Connector F301 Fuse FM Fan Motor PMV Pulse Motor Valve RC Running Capacitor RY005 006 00...

Page 25: ...s Name CN Connector LM Louver Motor F301 Fuse FM Fan Motor PMV Pulse Motor Valve RC Running Capacitor RY001 Louver Control Relay RY005 006 007 Fan Motor Control Relay TA Indoor temp sensor TB01 02 03 Terminal Block TC1 2 TCJ Temp sensor TR Transformer 1 Broken line indicate the wiring at site Long dashed short dashed line indicate the accessories 2 indicates the terminal block indicates the connec...

Page 26: ...2 4N 1 Running capacitor for fan motor AC 400 V 1 µF Drain pump motor PJD 05230TF 1 Float switch FS 0208 602 Control P C board transformer TT 13 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B25YGTF TA sensor Lead wire length 818 mm TC1 sensor Ø4 size lead wire length 1200 mm Vinyl tube Blue TCJ sensor Ø6 size lead wire length 1200 mm Vinyl tube Red Model MMU AP 0154SH 0184SH 0244SH Fan motor SWF...

Page 27: ...nyl tube Black TCJ sensor Ø6 size lead wire length 1200 mm Vinyl tube Red Model MMD AP 0184H 0244H 0274H 0364H 0484H Fan motor STF 200 160 4B STF 200 160 4A STF 200 260 4C STF 200 260 4B Running condenser for fan motor AC 500 V 4 µF AC 400 V 8 µF AC 450 V 6 µF AC 400 V 8 µF Drain pump motor ADP 1409 Float switch FS 0218 102 6 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B40YGTF EDM B60YGTF 1 TA ...

Page 28: ... wire length 1200 mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1200 mm Vinyl tube Red Model MML AP 0074H 0094H 0124H 0154H 0184H 0244H Fan motor AF 200 19 4F AF 200 45 4F AF200 70 4K Running condenser for fan motor AC450 V 1 2 µF AC400 V 1 8 µF AC450 V 2 µF Transformer TT13 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B25YGTF EDM B40YGTF TA sensor Lead wire length 818 mm Vinyl tube TC...

Page 29: ... AC500 V 3 5 µF AC500 V 4 µF Transformer TT 13 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B40YGTF EDM B60YGTF 1 Driving motor for vertical louver MT8 3 9 TA sensor Lead wire length 1200 mm Vinyl tube TC1 sensor Ø4 size lead wire length 1200 mm Vinyl tube Blue TC2 sensor Ø6 size lead wire length 2000 mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1200 mm Vinyl tube Red ...

Page 30: ... 4 Recovers refrigerant oil in heating operation Temp Sensor 1 TA Connector CN104 2P Yellow 1 Detects indoor suction temperature 2 TC1 Connector CN100 3P Brown 1 Controls PMV super heat in cooling operation 3 TC2 Connector CN101 2P Black 1 Controls PMV under cool in heating operation 4 TCJ Connector CN102 2P Red 1 Controls PMV super heat in cooling operation 2 MMU AP0074YH to AP0124YH only Control...

Page 31: ... changes in response to an operation selection command issued via the remote controller Ts Temperature setting Ta Room temperature 3 Room temp control 1 Adjustment range remote controller temperature setting C 2 In heating operation the temperature setting may be fine tuned via the DN code 06 Factory default Shift in heating suction temperature not applicable to remote controller thermo operation ...

Page 32: ...g as the temperature difference remains on a boundary line the fan speed stays the same Heating Figures inside applies to remote controller thermo operation Figures outside applies to body thermo operation Speed modes shown in apply to heating operation under AUTO air conditioner operation mode DN code 32 0000 Body thermo 0001 Remote controller thermo In AUTO fan speed mode the fan speed remains t...

Page 33: ...he indoor fan is operated in breeze mode until it moves into zone I The control is terminated under the following conditions Termination conditions 1 TC1 12 C TC2 12 C and TCJ 12 C 2 Passage of 20 minutes after stoppage 2 During cooling the air conditioner is operated in the manner described below according to the temperature readings of the TC2 and TCJ sensors If zone M operation is detected for ...

Page 34: ...is engaged in defrosting control the indoor units perform the following control tasks 1 Open the indoor PMV to a certain degree 2 Control the indoor fan according to the operation mode Indoor units operating in heating thermo ON OFF state Let the indoor fan continue operating for a while but turn it off as the temperature of the indoor heat exchanger drops Indoor units operating in FAN mode Let th...

Page 35: ...oor unit is operating in COOL DRY mode under priority cooling setting bit 1 of SW11 on outdoor I F P C board ON 3 All indoor units not able to engage in any of the above operations stand by in thermo OFF state 4 The indoor fan has been turned off because the system is engaged in a heat refrigerant oil recovery operation OPERATION STANDBY displayed No display provided on wireless remote controller ...

Page 36: ...e performed individually or collectively 3 Set louver positions 18 DC motor 1 When the fan is turned on the positions of the stator and rotor are determined The motor turns in incremental steps 2 The fan operates in accordance with commands issued by the indoor controller Note If the fan is rotating while the air conditioner is turned off due to an inflow of outside air or some other reason the in...

Page 37: ... 75 4 If the power saving operation is enabled the settings are retained when the operation is stopped when the mode is changed or when the power is reset The power saving operation will be enabled the next time the operation starts The power saving operation cannot be set by the wireless remote controller or wired remote controller of AMT31E or older NO Item Specification outline Remarks ...

Page 38: ...roller communication circuit AI NET communication circuit Power supply circuit Switch setting Transformer Louver motor Indoor fan motor Not applicable to concealed duct standard type Slim Duct Type Drain pump Power supply circuit Fan motor control circuit In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output D...

Page 39: ...motor Not applicable to concealed duct high static pressure type Drain pump Power supply circuit Fan motor relay circuit In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output Driver TA sensor TCI sensor TC2 sensor TCJ sensor Float input Remote controller communication circuit EEPROM Network adaptor 1 1 model c...

Page 40: ...r TCJ sensor Float input Remote controller communication circuit EEPROM Not applicable to concealed duct high static pressure type Indoor control P C board MCC 1402 Power supply circuit Fan motor relay circuit Transformer Network adaptor 1 1 model connection interface TCB PCNT30TLE2 Indoor outdoor communication Power source 1Ø 220 240 V 50 Hz 1Ø 220 V 60 Hz Outdoor unit Louver motor Indoor fan mot...

Page 41: ...cuit BUS communication circuit External output Driver TA sensor TCI sensor TC2 sensor TCJ sensor Float input Remote controller communication circuit EEPROM Not applicable to concealed duct high static pressure type Indoor control P C board MCC 1403 Fan motor relay circuit Transformer Transformer Power supply circuit Network adaptor 1 1 model connection interface TCB PCNT30TLE2 Indoor outdoor commu...

Page 42: ...tor Not applicable to concealed duct standard type Slim Duct Type Drain pump Power supply circuit Fan motor control circuit In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output Driver TA sensor TCI sensor TC2 sensor TCJ sensor Float input Remote controller communication circuit EEPROM Network adaptor 1 1 mode...

Page 43: ... motor Not applicable to concealed duct high static pressure type Drain pump Power supply circuit Fan motor control circuit In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output Driver TA sensor TCI sensor TC2 sensor TCJ sensor Float input Remote controller communication circuit EEPROM Network adaptor 1 1 mode...

Page 44: ...tment input Power supply Optional power supply Remote controller power source LED Drain pump output Remote controller jumper Indoor outdoor communication doubling as central control communication Indoor outdoor communication backup TCI sensor TC2 sensor External error input TCJ sensor EXCT DISP Used for servicing CHK Used for servicing TA sensor HA T10 Optional output Fan output Louver Float SW DC...

Page 45: ...l communication Remote controller power source LED HA T10 Optional output Remote controller jumper Used for servicing DISP CHK TCI sensor TC2 sensor TCJ sensor External error input Float SW Short plug inserted in concealed duct TA sensor Filter optional error input EXCT AC fan output Optional power supply Louver Power supply transformer primary side Power supply Power supply transformer secondary ...

Page 46: ...essor ON 4 Cooling output ON while air conditioner in cooling or related operation COOL DRY or cooling under AUTO mode 5 Heating output ON while air conditioner in heating operation HEAT or heating under AUTO mode 6 Fan output ON while indoor fan ON air cleaner in use or via interlock wiring External error input CN80 1 DC12 V COM Generates test code L30 and automatically shuts down air conditioner...

Page 47: ...hort circuiting DISP pin CN72 on the indoor P C board in addition to short circuit of CHK pin CN71 on the indoor P C board the minimum opening degree 30 pls can be set to the indoor PMV only When open DISP pin the maximum opening degree 1500 pls can be obtained again How to clear Open CHK pin While the system is operating it stops once but automatically returns to operation after several minutes T...

Page 48: ...ove 2 Each time the Select unit side of the button is pressed one of the indoor unit Nos under group control is displayed in turn Then the fan and louver of the selected indoor unit move 3 Use the button to select the CODE No DN code of the desired function 4 Use the button to select the desired SET DATA associated with the selected function 5 Push the button The display changes from flashing to s...

Page 49: ... 0001 to 0034 According to capacity type 12 Line address 0001 No 1 unit to 0030 No 30 unit 0099 Unfixed 13 Indoor unit address 0001 No 1 unit to 0064 No 64 unit 0099 Unfixed 14 Group address 0000 Individual 0002 Follower unit of group 0001 Header unit of group 0099 Unfixed 19 Louver type Air direction adjustment 0000 No louver 0001 Swing only According to type 0002 1 way Cassette type Ceiling type...

Page 50: ...ntroller 0000 Available can be performed 0001 Unavailable cannot be performed 0000 Available 92 External interlock release condition 0000 Operation stopped 0001 Release signal received 0000 Operation stopped D0 Whether the power saving mode can be set by the remote controller 0000 Invalid 0001 Valid 0001 Valid DN Item Description At shipment Value Type AP015 AP018 AP024 0000 Standard factory defau...

Page 51: ...ard MMD AP BH 0005 Slim Duct MMD AP SPH SH 0006 Concealed Duct High Static Pressure MMD AP H 0007 Ceiling MMC AP H 0008 High Wall MMK AP H 0010 Floor Standing Cabinet MML AP H 0011 Floor Standing Concealed MML AP BH 0013 Floor Standing MMF AP H 0014 Compact 4 way Cassette MMU AP MH 0016 Fresh Air Intake indoor unit Duct type MMD AP HFE Value Capacity 0000 Invalid 0001 007 type 0003 009 type 0005 0...

Page 52: ...ut present while unit in normal operation 3 Error signal Output present while alarm e g serial communication error or operation of protective device for indoor outdoor unit being activated Wiring diagram of control system using remote controller interface TCB IFCB4E2 Input IFCB4E2 No voltage ON OFF serial signal Output No voltage contact in operation and error indication Contact capacity Max AC 24...

Page 53: ...t numbers in group control are displayed successively In this time the fan of the selected indoor unit only turns on 3 Using the setup temp or button specify the CODE No 31 4 Using the timer time or button select the SET DATA At shipment The setup data are as follows 5 Push button OK if display goes on To change the selected indoor unit go to the procedure 2 To change the item to be set up go to t...

Page 54: ...rohibited to remote controller Status that card is taken out from the card switch box When the card switch box does not perform the above contact operation convert it using a relay with b contact 2 Operation Handle the wired remote controller switch in the following procedure Use the wired remote controller switch during stop of the system 1 Push concurrently buttons for 4 seconds or more 2 Using ...

Page 55: ...connect a wired remote controller to the target unit directly before address setting Pair the indoor unit to set and the remote controller one to one Turn on the power 1 Push and hold the and buttons at the same time for more than 4 seconds LCD starts flashing Line system address 1 1 1 2 2 Indoor unit address 1 2 3 1 2 Group address 1 Header unit 2 Follower unit 2 Follower unit 2 Follower unit 2 F...

Page 56: ...using the remote controller These 2 address numbers cannot be used on outdoor units and the CODE No E04 Indoor outdoor communication error will appear if they are mistakenly used 2 If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally set the header outdoor unit of each line as below Set a system address for the hea...

Page 57: ...r one to one or it is a group controlled one Execute it while the units are running 1 Push the button if the units stop 2 Push the button left side of the button A unit numbers is indicated on the LCD it will disappear after a few seconds The indicated number shows the system address and indoor unit address of the unit When 2 or more indoor units are connected to the remote controller group contro...

Page 58: ... at the same time for more than 4 seconds appears on UNIT No on the LCD display The fans and louvers of all the indoor units in the group are activated 2 Push the button left side of the button Each time you push the button the indoor unit numbers are indicated one after another The first indicated unit number is the address of the header unit Only the fan and louvers of the indicated indoor unit ...

Page 59: ...1 and CODE No Address Change are indicated on the LCD display Select an outdoor unit 2 Push the left side of the button and buttons repeatedly to select a system address 3 Push the button to confirm the system address selection The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated 4 Push the button left side o...

Page 60: ...2 Push the button left side of the button repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group The fan and louvers of the selected indoor unit are activated The fan of the selected indoor unit is turned on 3 Push the TEMP buttons repeatedly to select for CODE No 4 Push the TIME buttons repeatedly to change the value indicated in the SET DATA section to ...

Page 61: ...nit exists on the line Push button and select another line following step 2 Execute it while the units are stopped 1 Push and hold the TIME buttons at the same time for more than 4 seconds At first the line 1 and CODE No Address Change are indicated on the LCD display 2 Push left side of the button and buttons repeatedly to select a system address 3 Push the button The address of one of the indoor...

Page 62: ...ide of the button repeatedly to select another address to change Each time you push the button the indoor unit numbers in a refrigerant line are indicated one after another Only the fan and louvers of the selected indoor unit are activated Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique 7 Push the button All the segments on the LCD display light up 8 Push ...

Page 63: ...ction of the remote controller 1 Push and hold the and for 4 seconds or longer to enter the service monitoring mode 2 Push the button to set CODE No to 3 The display in A of the following figure counts down as follows at 5 second intervals Æ Æ Æ Æ Æ The error is cleared when appears However the display counts down from again 4 Push the to return the display to normal Clearing an error of the indoo...

Page 64: ...t and outdoor unit 1 Push and hold the and for 4 seconds or longer to enter the service monitoring mode The service monitor lights up The temperature of CODE No appears at first 2 Push the button to change to CODE No of the item to monitor Refer to the following table for CODE No 3 Push the left part of the button to change to the item to monitor Monitor the sensor temperature or operation status ...

Page 65: ... 1 HP 0415 41 5 HP 0C Number of connected outdoor units 1 0004 4 0D Total horse power of outdoor units 1 HP 0420 42 HP CODE No Data Format Unit Remote controller display example U1 U2 U3 U4 Individual data 1 of outdoor unit 3 10 20 30 40 Discharge temperature of compressor 1 Td1 1 C 0024 24 C 11 21 31 41 Discharge temperature of compressor 2 Td2 1 C 12 22 32 42 Detection pressure of high pressure ...

Page 66: ...coil TSA 1 1 C 0024 24 C FA Outdoor Air Temperature TOA 1 1 C System data 0A Number of connected indoor units 1 0048 48 0B Total horse power of connected indoor units 10 HP 0415 41 5HP 0C Number of connected outdoor units 1 0004 4 0D Total horse power of outdoor units 10 HP 0420 42HP CODE No Data Format Unit Remote controller display example U1 U2 U3 U4 Individual data 1 of outdoorunit 3 10 20 30 ...

Page 67: ...4 D504 Green Remote controller communication The group header unit lights up for the first half 5 seconds while communicating with the remote controller Blinks for the second half 5 seconds at 0 2 second intervals 0 1 second during communication between group indoor header and follower CODE No Data Format Unit Remote controller display example U1 U2 U3 U4 Individual data 2 of outdoorunit 4 50 60 7...

Page 68: ...ot start Could it just be the 3 minute delay period 3 minutes after compressor shutdown Could it just be the air conditioner having gone thermo OFF Could it just be the air conditioner operating in fan mode or put on the timer Could it just be the system going through initial communication 2 An indoor fan would not start Could it just be cold air discharge prevention control which is part of heati...

Page 69: ...unit L20 SIM SIM Duplicated central control address There is duplication in central control address setting L30 L30 Detected indoor unit No Indoor external error input interlock Unit shutdown has been caused by external error input CN80 P01 ALT Indoor AC fan error Indoor AC fan error is detected activation of fan motor thermal relay P10 P10 Detected indoor unit No ALT Indoor overflow error Float s...

Page 70: ...dy Operation C05 C06 C12 P30 Error detected by central control device TCC LINK central control No indication when main remote controller also in use Faulty central control communication transmission Faulty central control communication reception Multiple network adapters Central control device is unable to transmit signal due to duplication of central control device AI NET Central control device i...

Page 71: ...oor unit from other refrigerant line is detected while indoor automatic address setting is in progress E23 E23 Outdoor outdoor communication transmission error Signal cannot be transmitted to other outdoor units E25 E25 Duplicated follower outdoor address There is duplication in outdoor addresses set manually E26 Address of outdoor unit from which signal is not received normally E26 Dropping out o...

Page 72: ... circuit error 04 TK4 oil circuit error 05 TK5 oil circuit error H16 Oil level detection circuit error No temperature change is detected by temperature sensor for oil level detection TK1 5 despite compressor having been started H25 H25 Outdoor discharge temperature sensor TD3 wiring error Wiring installation error or detachment of outdoor discharge temperature sensor TD3 has been detected L04 L04 ...

Page 73: ...06 A3 IPDU2 Fan IPDU error 07 All IPDU error SMMS i Series 4 There are insufficient number of IPDUs P C boards in inverter box Error in number of IPDUs Indoor unit has been shut down for external error input in one refrigerant line detected by indoor unit Outdoor discharge temperature sensor TD1 has detected abnormally high temperature Outdoor discharge TD1 temperature error P04 P04 High pressure ...

Page 74: ...activated Heat sink overheating error Temperature sensor built into IGBT TH detects overheating P20 P20 ALT High pressure protection activation High pressure Pd sensor detected a value over the criteria SMMS Series 1 04 Rotation difference error 06 Maximum rotation exceeded 08 Out of step 0A Idc activation 0C Fan lock 0d Lock 0E Sync error 0F Control error SMMS i Series 4 0 IGBT circuit 1 Position...

Page 75: ...Procedure To be performed when system at rest 1 Invoke the SERVICE CHECK mode by pressing the buttons simultaneously and holding for at least 4 seconds The letters SERVICE CHECK light up and the check code 01 is displayed indicating the error history This is accompanied by the indoor unit No to which the error history is related and a check code 2 To check other error history items press the butto...

Page 76: ... down 1 Push the buttons simultaneously and hold for at least 4 seconds 2 The letters SERVICE CHECK light up and the check code 01 is displayed 3 When a group No is selected blinking if there is an error history the UNIT No and the latest error history information are displayed alternately During this procedure the temperature setting feature is unavailable 4 To check other error history items pus...

Page 77: ...rloading E19 Error in number of outdoor header units E20 Detection of refrigerant piping communication error during automatic address setting E23 Faulty transmission in outdoor outdoor communication E25 Duplicated follower outdoor address E26 Faulty reception in outdoor outdoor communication dropping out of outdoor unit E28 Outdoor follower unit error E31 IPDU communication error P01 Indoor AC fan...

Page 78: ...discharge temperature sensor TD1 H06 Abnormal drop in low pressure sensor Ps reading Protective shutdown of outdoor unit H07 Abnormal drop in oil level H08 Error in temperature sensor for oil level detection circuit TK1 TK2 TK3 TK4 or TK5 H15 Wiring installation error or detachment of outdoor discharge temperature sensor TD2 H16 Oil level detection circuit error Error in outdoor unit TK1 TK2 TK3 T...

Page 79: ...st run in progress Setting incompatibility automatic cooling heating setting for model incapable of it and heating setting for cooling only model Light block Check code Cause of fault Operation Timer Ready Synchronized blinking Operation Timer Ready Synchronized blinking Operation Timer Ready Alternate blinking ...

Page 80: ...ontroller communication error detected at indoor end Stop of corresponding unit There is no communication from remote controller including wireless or network adaptor Check remote controller and network adaptor wiring E04 04 Indoor unit Indoor outdoor communication circuit error detected at indoor end Stop of corresponding unit Indoor unit is not receiving signal from outdoor unit Check order in w...

Page 81: ...ll stop Indoor automatic address setting is started while automatic address setting for equipment in other refrigerant line is in progress Outdoor automatic address setting is started while automatic address setting for indoor units is in progress Perform automatic address setting again after disconnecting communication cable to that refrigerant line E15 E15 42 I F Indoor unit not found during aut...

Page 82: ...gnal cannot be transmitted to other outdoor units for at least 30 seconds continuously Check power supply to outdoor units Is power turned on Check connection of tie cables between outdoor units for bad contact or broken wire Check communication connectors on outdoor P C boards Check for defect in outdoor P C board I F Check termination resistance setting for communication between outdoor units E2...

Page 83: ...fect in indoor P C board F02 0d Indoor unit Indoor TC2 sensor error Stop of corresponding unit Sensor resistance is infinity or zero open short circuit Check connection of TC2 sensor connector and wiring Check resistance characteristics of TC2 sensor Check for defect in indoor P C board F03 93 Indoor unit Indoor TC1 sensor error Stop of corresponding unit Sensor resistance is infinity or zero open...

Page 84: ...ompressor 1 side 02 Compressor 2 side 03 Compressor 3 side 43 IPDU TH sensor error All stop Sensor resistance is infinity or zero open short circuit Defect in IGBT built in temperature sensor Replace A3 IPDU P C board F15 F15 18 I F Outdoor temperature sensor wiring error TE1 TL All stop During compressor operation in HEAT mode TE1 continuously provides temperature reading higher than indicated by...

Page 85: ...p Overcurrent is detected several seconds after startup of inverter compressor Check for defect in compressor Check power supply voltage AC200 V 10 Check compressor system wiring particularly for open phase Check connection of connectors terminals on A3 IPDU P C board Check conductivity of case heater Check for refrigerant entrapment inside compressor Check for defect in outdoor P C board A3 IPDU ...

Page 86: ... 03 TK3 sensor error 04 TK4 sensor error 05 TK5 sensor error d4 I F Error in temperature sensor for oil level detection All stop Sensor resistance is infinity or zero open short circuit Check connection of TK1 sensor connector Check resistance characteristics of TK1 sensor Check for defect in outdoor P C board I F All stop Sensor resistance is infinity or zero open short circuit Check connection o...

Page 87: ...rd Open and check the service valve Gas side Liquid side Check the outdoor PMV clogging PMV1 2 Check the SV42 circuit Check the SV4 circuit SV41 42 miswiring Check the opening status of indoor PMV Check the four way valve error Check the refrigerant shortage H15 H15 I F TD2 sensor miswiring incomplete insertion All stop Air discharge temperature of TD2 does not increase despite compressor 2 being ...

Page 88: ...or 4 starts operating or the temperature difference from that of the other TK sensor changes only in the specified range for a given time or longer Check the TK4 sensor installation Check the TK4 sensor resistant characteristics Check the misconnection of TK1 TK2 TK3 or TK4 Check the SV3E valve error Check the oil circuit capillary clogging and non return valve error Check the hibernating refriger...

Page 89: ... P C board I F L02 L02 Indoor unit Outdoor unit model mismatch error Only the target unit stopped An error was found on the outdoor unit model Check the model name of the outdoor unit Check the miswiring of the communication line between indoor and outdoor L03 96 Indoor unit Duplicated indoor header unit Stop of corresponding unit There is more than one header unit in group Check indoor addresses ...

Page 90: ...g unit Miswiring of discharge gas suction gas Check the SVS SVD valve miswiring misinstallation L20 98 AI NET Indoor unit Duplicated central control address All stop There is duplication in central control address setting Check central control addresses Check network adaptor P C board applicable to AI NET L28 L28 46 I F Too many outdoor units connected All stop There are more than four outdoor uni...

Page 91: ...ng Check outdoor PMVs PMV1 2 4 for clogging Check resistance characteristics of TD1 sensor Check for insufficiency in refrigerant quantity Check for defect in 4 way valve Check for leakage of SV4 circuit Check SV4 circuit wiring or installation error in SV41 SV42 or SV43 P04 P04 01 Compressor 1 side 02 Compressor 2 side 03 Compressor 3 side 21 IPDU Activation of high pressure SW All stop High pres...

Page 92: ... CTT error P07 P07 01 Compressor 1 side 02 Compressor 2 side 03 Compressor 3 side 1C IPDU I F Heat sink overheating error All stop Temperature sensor built into IGBT TH is overheated Check power supply voltage Check outdoor fan system error Check heat sink cooling duct for clogging Check IGBT and heat sink for thermal performance for faulty installation e g mounting screws and thermal conductivity...

Page 93: ...tdoor service valves gas side liquid side to confirm full opening Check PMVs PMV1 2 for clogging Check resistance characteristics of TS1 sensor Check for defect in 4 way valve Check SV4 circuit for leakage 02 TD condition AE I F Gas leak detection TD condition All stop Protective shutdown due to sustained discharge temperature TD1 TD2 or TD3 at or above 108 C for at least 10 minutes is repeated fo...

Page 94: ...0 P20 22 I F Activation of high pressure protection All stop Pd sensor detects pressure equal to or greater than 3 6 MPa Check for defect in Pd pressure sensor Check service valves gas side liquid side to confirm full opening Check for defect in outdoor fan Check for defect in outdoor fan motor Check outdoor PMVs PMV1 2 4 for clogging Check indoor outdoor heat exchangers for clogging Check for sho...

Page 95: ... properly Check the fan motor Check the connector connection for fan motor Check the error of IPDU board for fan All stop Sub code 0F FAN IPDU position detection circuit Position detection is not performed properly Check the fan motor Check the connector connection for fan motor Check the error of IPDU board for fan All stop Sub code 06 External factors such as blast Position detection is not perf...

Page 96: ...fan Check fan motor Check connection of fan motor connector Check for defect in fan IPDU P C board All stop Sub code C Higher temperature than the specified value is detected during operation of the fan Check fan motor Check for defect in fan IPDU P C board All stop Sub code D The resistance value of the sensor is infinite or zero open or short circuit Check for defect in fan IPDU P C board All st...

Page 97: ...trol device Check for defect in central control communication line Check termination resistance setting Check power supply for devices at other end of central control communication line Check defect in P C boards of devices at other end of central control communication line C12 General purpose device I F Blanket alarm for general purpose device control interface Continued operation Error signal is...

Page 98: ...sor Resistance k Temperature C Temperature C Resistance k Temperature C Resistance k Resistance k 10 C or below Temperature C Resistance k 10 C or above Indoor TC1 sensor Resistance k 10 C or below Temperature C Resistance k 10 C or above Indoor TC2 and TCJ sensors Temperature C Resistance k ...

Page 99: ...gain including the indoor unit No and group header follower designation and confirm the integrity of the refrigerating cycle by conducting a test operation etc Replacement procedure Method 1 If it is possible to turn on the indoor unit and read the setting data from the P C board to be replaced via a wired remote controller Reading EEPROM data Procedure 1 Replacing P C board and turning on power P...

Page 100: ...ethod to replace it see the EEPROM location diagram section The old EEPROM supplied with the P C board to be replaced and now mounted on the service P C board needs to be replaced with the new EEPROM supplied with the service P C board Replacing P C board and turning on power Procedure 2 Writing EEPROM data in new EEPROM Procedure 3 Resetting power supply applicable to all indoor units connected t...

Page 101: ... unit comes on with the louvers swinging depending on the model 3 The button allows you to move the CODE No DN code up down by one place 4 First change the CODE No DN code from 10 to 01 To set filter sign lighting time Jot down the setting data displayed 5 Change the CODE No DN code using the button Again jot down the setting data displayed 6 Repeat step 5 until all the setting data has been jotte...

Page 102: ...n on the indoor unit and proceed to Procedure 3 If this method cannot be used proceed to the alternative method described below Case 2 C If it is not possible to selectively turn on the indoor unit being serviced Case 2 a Remove the CN41 connectors of all other indoor units in the same group b Turn on the indoor unit and proceed to Procedure 3 Be sure to restore the temporarily removed group contr...

Page 103: ...ype See the CODE No list 6 Push the button The display should change from flashing to steady 7 Push the button to bring the system back to normal off state 5 Next write any setting changes made on site after installation such as address settings in the EEPROM Perform the tasks specified in step 1 again 6 Use the button to set the CODE No DN code to 01 To set filter sign lighting time 7 Check the v...

Page 104: ...ove it When installing it adjust its orientation as shown in the diagram below During EEPROM removal installation take care not to bend IC leads P C board MCC 1402 P C board MCC 1403 EEPROM IC10 When installing the EEPROM align its notch with that of the IC socket EEPROM IC10 IC socket Notch EEPROM Notch ...

Page 105: ...overy 0000 None 31 Vent Fan Single operation 0000 Not possible 32 Sensor SW Selection of static pressure 0000 Body sensor 5d High ceiling select 0000 Standard 60 Timer setting wired remote controller 0000 Available F0 Swing mode 0001 Standard D0 Power save operation 0001 Standard Type Code No 10 Setup data Type Model abb name 0000 1 way Cassette MMU AP SH 0001 1 2 4 way Cassette MMU AP 2H 0002 2 w...

Page 106: ...grilles by sliding knobs toward suction side Both 2 pieces at left and right sides 4 Pull out the grille by pushing claws at rear hinge 2 positions with screwdriver 2 Attachment 1 Insert the rear hinge 2 positions into square holes of the panel Insert it surely up to the end NOTE After inserting the hinge check the grille does not fall out even if pulling the grilles 2 Close the grilles and slide ...

Page 107: ...inside of the fixing screw with hole of the cover 2 Tighten the fixing screws Ø4 8 2 pcs 3 Adjust cap 1 Detachment 1 Perform work of procedure 1 of 1 2 Take off fixing screws Ø4 12 2 pcs 3 Hold handle of the cap and then slide it toward suction side to remove cap 2 Attachment 1 Catch on the top claw and slide it toward discharge side for attachment 2 Fit the fixing screws Ø4 12 2 pcs No Part name ...

Page 108: ...knob of hook movable at right side of the panel toward inner side remove the hook movable and also the hook movable at left side to pull down the ceiling panel by lifting the left side of the panel and sliding toward outside 2 Attachment 1 Hook the hooks at both sides of the ceiling panel to the indoor unit 2 Fit the fixing screws M5 4 pcs M4 2 pcs NOTE Be sure to close the screw cap after screwin...

Page 109: ...law at the rear side to square hole of the panel 2 Attachment 1 Take off the hook at the rear side of the electrical control box 2 Return the electrical control box at the original position ant then fit the fixing screws Ø4 8 4 pcs 3 Using cord clamp at the ceiling surface fix the lead wires as before No Part name Procedure Remarks Square hole for hooking electrical control box Hooking section Fix...

Page 110: ...pump 2P Blue CN82 PMV 6P Blue CN100 TC1 sensor 3P Brown CN101 TC2 sensor 2P Black CN102 TCJ sensor 2P Red CN104 Room temp Sensor 2P Orange CN333 Fan motor power supply 5P White CN334 Fan motor position detection 5P White 3 Unlock the locks of the card edge spacers 7 positions and then remove the control P C board 2 Attachment 1 Fix the control P C board to the card edge spacers 7 positions 2 Conne...

Page 111: ...Tighten earth lead wires of the motor together as before For the boss of the fan attach hexagon socket head screw to shaft of the motor matching the marked position of the shaft with groove of the fan NOTE Match the rotation direction of the motor with that of the fan and fix the fan motor so that the motor lead section comes to the piping side referring to the right photo 2 Determine the position...

Page 112: ...e to catch drain water using bucket etc 3 Take off screws fixing the drain pan Ø4 8 2 pcs 4 Remove the drain pan while lowering the discharge side 2 Attachment 1 Fix parts as before in order of Drain cap Drain pan Ceiling panel Electric parts cover Adjust cover Air intake grille No Part name Procedure Remarks Fixing screw Drain cap Pull down the discharge side And remove the drain pan ...

Page 113: ... 8 3 pcs 5 Pull out the drain pump assembly toward discharge side to remove it 2 Attachment 1 Fix the drain pump assembly as before 2 Connect the drain hose and attach the hose band NOTE Insert the drain hose completely up to the end of the pump connecting part and then attach band at the white mark position of the hose 3 Insert the connectors to the control P C board as before 4 Fix parts as befo...

Page 114: ... gas 2 Remove the refrigerant pipe of the indoor unit 3 Perform work of procedure 1 of 8 4 Remove the pipe cover by taking off fixing screws of the cover Ø4 8 2 pcs 5 Remove the clamp which fixes TC1 sensor TC2 sensor and TCJ sensor and then pull out the sensors from the holder 6 Remove the heat exchanger by taking off fixing screws of the partition board while holding the heat exchanger Ø4 8 4 pc...

Page 115: ...r intake grille buttons to detach the air intake grille from the ceiling panel Lower the grille slowly whilst holding 4 Slide hooks 2 positions of the air intake grille to inner side and then hang down the air intake grille 5 Take off the strap that connects the panel and the air intake grille and then lift up shaft of the air intake grille to remove the air intake grille 2 Attachment 1 Hook shaft...

Page 116: ...not use an electric screwdriver otherwise the mechanism of adjust corner cover may be damaged and not be removed 3 Pull downward the risen up part of adjust corner cover and remove it 4 Remove the strap of adjust corner cover 2 Attachment 1 Attach the strap of adjust corner cover to the panel hook claws of adjust corner cover to the panel corner and then push the opposite side into the panel 2 Tur...

Page 117: ... Attachment 1 Hook the panel to the temporary bracket of the drain pan of the main body NOTE The panel has directionality Therefore mount the panel according to the temporary bracket and the bracket mounting position 2 Tighten the fixing screws M5 4 pcs 3 Connect louver connector of the ceiling panel to the connector CN33 White 5P of the control P C board No Part name Procedure Remarks Temporary b...

Page 118: ... there is incomplete drawing of wire short or water leakage of the parts may be caused No Part name Procedure Remarks Ferrite core for sensor lead Ferrite core for fan motor Drawing out port of lead wire Card edge spacer Enlarged drawing Fix the lead wires with cord clamp so that the lead wires do not slacken at P C board side 2 positions Cord clamp As shown in the figure store PMV lead wire conne...

Page 119: ... removing If there is incomplete drawing of wire short or water leakage of the parts may be caused No Part name Procedure Remarks Ferrite core for sensor lead Ferrite core for fan motor Drawing out port of lead wire Card edge spacer Enlarged drawing Fix the lead wires with cord clamp so that the lead wires do not slacken at P C board side 2 positions Cord clamp As shown in the figure store PMV lea...

Page 120: ...ginal before being removed NOTE Pinch lead wire of the drain pump and float switch with lead wire fixing claws of the bell mouth and perform wiring along the guide 9 Turbo fan 1 Detachment 1 Perform work of procedure 8 1 2 Take off the nut M6 nut 1 pc of the turbo fan NOTE Use a box wrench for attachment and detachment of the turbo fan If using a monkey wrench etc the other parts may be damaged in...

Page 121: ...s preventing agent as paints to the nut after tightening 2 Attach the fan motor lead wire holder NOTE For the fan motor lead wire fix the lead wire holding bracket along concave part of the ceiling panel There is no catch in of lead wire and ceiling panel When fixing the lead wire bracket tighten fan motor earth together with the lead wire For this work do not use an electric screwdriver Take note...

Page 122: ...se water leakage may be caused 3 Fix the drain pan with screws Ø4 10 4 pcs 12 Drain pump assembly 1 Detachment 1 Perform work of procedure 11 1 2 Pick up the hose band and slide it from the pump connecting part to remove the drain hose 3 Take off screws Ø4 10 3 pcs fixing the drain pump assembly and then move hooking claw 1 position of the main body from the drain pump assembly to remove the drain...

Page 123: ...d then fix it with bind band Fix the head of bind band and lead wire at inner side of the position in the figure so that they do not stick out to outside Insert the sensor lead wires Red Blue Black from the positions in the figure Sensor lead Black PMV motor Details of A part Heat insulationpipe Gas pipe Sensor lead Blue Sensor lead Red Heat insulation pipe Liquid pipe Sensor lead wire Black Do no...

Page 124: ...ixing band and fixing screws Ø4 10 3 pcs and then remove the heat exchanger 2 Attachment 1 Mount parts in order heat exchanger fixing band piping cover drain pan bell mouth electrical control box as original NOTE Arrange wires as original 2 Attach the removed connectors and wires as original 3 Connect the refrigerant pipe as original and then perform vacuuming No Part name Procedure Remarks Fixing...

Page 125: ...e air filter so that hooks are aligned at discharge side 2 Plate inlet A Plate inlet B 1 Detachment 1 Take off fixing screws while holding the plate inlet A with hands to remove it Sucking system from rear side Ø4 10 8 pcs Sucking system from bottom side Ø4 10 11 pcs 2 Take off fixing screws while holding the plate inlet B with hands to remove it Ø4 10 6 pcs NOTE Be careful that sheeting metal doe...

Page 126: ... pump incorporated model 3 positions Natural drain model 2 positions 3 Take off screws fixing E box Ø4 10 2 pcs E box does not fall down under condition that screws are taken off 4 Remove the E box over sheeting metal which was fixed with screws 2 Attachment 1 Insert hooks of E box into the hooking part of the main body 2 Store E box as before and then attach it by using screws taken off in proced...

Page 127: ...r poor contact of the connectors 6 Multi blade fan case fan lower case fan upper case 1 Detachment 1 Perform work 1 of 2 2 Take off hanging hooks at both sides of the lower fan case to remove fan lower case 3 Remove the upper fan case while taking off hooks of fan upper case which are hooked to the partition board 4 Loosen hexagonal hole screw of the multi blade fan to remove multi blade fan from ...

Page 128: ...rain cap and drain the drain water accumulated in the drain pan assembly In case of natural drain model drain the drain water by taking off hose band and drain hose NOTE When taking off drain cap and drain hose be sure receive drain water in a bucket etc 2 Take off screws fixing the under panel while holding it to remove Ø4 10 8 pcs NOTE Be careful that sheeting metal does not fall when removing t...

Page 129: ...se band Arrange handle of the hose band at contrary side of heat exchanger side and at direction remote from drain pan assembly 3 Carry out wiring as before and then perform work of procedure 2 of 8 NOTE Finally check whether they correctly operate or not 10 Evaporator assembly 1 Detachment 1 Recover refrigerant and then remove refrigerant pipes at indoor unit side 2 Perform works of procedures 1 ...

Page 130: ...er 2 Remove the fan motor connector 3 Remove the hexagon screws fixing the fan assembly and main unit 4 Remove the fan assembly from the main unit The fan assembly is fixed by three hooks on the upper part of the main unit Pull it up once and then backward to remove the hooks 5 Remove the four screws fixing the fan case and cover 6 Remove the fan cover 7 Loosen the screws fixing the fan with a hex...

Page 131: ...nit 6 Pull up and remove the drain pan 5 Float switch 1 Remove the drain pan 2 Remove the screw of the float switch fixing board 3 Remove the plastic nut fixing the float switch 4 Remove the float switch No Component Procedure Remarks Fan motor attachment board Fan motor Fan motor attachment board fixing screw Bottom board fixing screws Bottom board Drain pan fixing board screws Drain pan fixing b...

Page 132: ...emove the drain pan 3 Remove the check port cover on the right 4 Remove the six screws fixing the check port cover on the left 5 Remove the two screws fixing the main unit and heat exchanger 6 Remove the screws on the front and right fixing the main unit and heat exchanger No Component Procedure Remarks Drain pump Drain pump holder Drain pump holder fixing board screws Screws for drain pump and fi...

Page 133: ... 2 screws 5 Remove the side board from the main unit M5 screws 8 pcs 6 Remove the three screws fixing the fan assembly and slide the assembly along the guide rail to pull it out 3 M5 tap tight screws 7 Loosen the screws fixing the fan M8 8 Remove the two screws fixing the motor band 9 Replace the motor TC1 TC2 TCJ sensor leads PMV coil lead TAsensor lead Electrical control box Side board Electrica...

Page 134: ...ntake grille into the hole of the main unit Make sure that the hook is hooked firmly 2 Fix the screws of air intake grille fixing knob on a side of each filter 2 Electrical control cover 1 Removing 1 Perform Step 1 of 1 2 Loosen the screws fixing the electrical control cover Ø4 X 10 2 3 The screw fixing part of the electrical control cover is a U shaped groove Slide the electrical control cover to...

Page 135: ...d and another component NOTE Unlock the housing part before removing the connector CN33 Louver motor 5P White CN41 Remote controller terminal 2P 3P Blue CN67 Power terminal 3P 3P Black CN82 PMV 6P Blue CN100 TC1 sensor 3P Brown CN101 TC2 sensor 2P Black CN102 TCJ sensor 2P Red CN104 Room temperature sensor 2P Orange CN333 Fan motor power 5P White CN334 Fan motor position detection 5P White 3 Unloc...

Page 136: ...over and base fixing the bearing Be careful not to lose them 6 Loosen the screws with square holes of the coupling and then remove the fan and shaft 7 Loosen the screws with square holes of the coupling and then remove the fan and shaft If necessary loosen the screws with square holes of the bearing and then remove the bearing from the shaft No Component Procedure Remarks Model No Attachment AP015...

Page 137: ...m 3 Insert the shaft with fan into the coupling Tighten later 4 Reattach the bearing to the main unit NOTE Insert the bearing spacer between the base and cover and tighten with a bolt Ø8 X 12 2 5 Tighten the coupling On the shaft there is a groove to fit the attaching position for the coupling Fit a single face of the coupling to the groove and then fix with the screw with square hole NOTE Tighten...

Page 138: ... drop it 2 Attaching 1 Fix the components again in the following order Fan motor Motor fixing metal fittings Electrical control box cover Reconnect the connector and earth lead removed in Step 1 7 Side cover 1 Removing 1 Perform Step 1 of 1 2 Remove the screw of the side cover One side Ø4 X 12 With washer 1 3 Slide the side cover in the discharge direction to remove it 2 Attaching 1 Insert the hoo...

Page 139: ... it horizontally from the drain pan of the discharge Applying excessive force may cause breakage 6 When removing the sensor base wrap vinyl tape on the tip of a flat head driver as shown in the following picture and then insert it into the groove of the side below the sign of the cover 2 Attaching 1 Slide along the drain pan from the discharge to attach it 2 Insert the screws strengthening metal f...

Page 140: ...n and then remove the stepped screw AP015 AP027 One stepped screw AP036 AP048 Two stepped screws The removed thermal insulator is used when attaching 5 Slide the drain pan toward the discharge to remove it 2 Attaching 1 Insert the drain cap deep into the drain pan 2 Slide from the discharge and then hook firmly on the hook part of the board metal on the fan 3 Insert the stepped screw removed in 1 ...

Page 141: ...motor with a double spanner to remove it 6 Hold the heat exchanger and remove the screws fixing the heat exchange separation board to remove it Ø4 X 8 4 7 Hold the heat exchanger and remove the screws fixing the heat exchanger on the opposite side of the heat exchange separation board to remove the heat exchanger Ø4 X 8 2 2 Attaching 1 Fix the components together with the sensors in the following ...

Page 142: ...Remove the three temperature sensors from CN101 Black CN102 Red and CN104 Yellow 8 Remove the indoor and outdoor connectors 9 Remove the two screws fixing the electrical control box to the lower cabinet slide the box to the right and pull it out toward you AP036 AP048 1 Remove the screws 3 and 4 on the front of the electrical control box to remove the electrical control box cover 2 Remove the fan ...

Page 143: ...hange assembly itself AP036 AP048 1 Remove the relay connector of the PMV lead wire 2 Remove the screws 1 3 positions fixing the upper shield and box and pull the heat exchange assembly out toward you 3 Remove the screws 2 2 positions of the heat exchange assembly pulled out and then remove the upper shield 4 Remove the screws 3 5 positions of the heat exchange assembly pulled out and then remove ...

Page 144: ... the shield to remove it 3 Remove the fan ceiling fixing screws 2 4 positions and then put out the fan assembly toward you 4 Remove the screws 3 4 positions fixing the motor fixing board and reception board 5 Remove the screws 4 per side fixing the left and right of the bell mouth on the motor and then remove the fan case 4 screws per side 6 Remove the fan with one screw per side from the fan moto...

Page 145: ...he air conditioner and turn off the main power 2 Remove the two intake grilles No fixing screw 3 Remove the front panel 2 M4 screws 4 Remove the discharge grille M4 X 20L 2 5 Remove the control assembly 3 M4 screws 6 Remove the screw fixing the electrical control assembly to the box and pull it out toward you Discharge grille Front panel Control assembly Remote controller assembly Electrical compo...

Page 146: ...ld front 3 M4 screws 7 Remove the heat exchange shield right 2 M4 screws 8 Remove the screws fixing the heat exchanger 4 M4 screws 9 Remove the shield on the side of the heat exchanger 2 M4 screws 10 Slide the heat exchanger to the right keep the connecting pipe away from the drain pan and then pull the exchanger upward Upper panel Heat exchange shield right Screws Strengthening board Vertical gri...

Page 147: ...eat exchanger to remove the heat exchanger 2 Remove the nut in the deep right corner of the fan assembly M6 nut 1 position 3 Remove the two screws in the left of the fan assembly M4 screw 4 Pull out the fan assembly toward you Pull out toward you Fan assembly ...

Page 148: ...147 9 Exploded Diagram Service Parts List 9 1 1 way cassette type YH MMU AP0074YH AP0094YH AP0124YH ...

Page 149: ...148 ...

Page 150: ...70146 HOSE DRAIN 1 1 1 217 43122082 CASING ASSY 1 1 1 218 43172143 DRAIN PAN INST ASSY 1 1 1 219 43121731 PUMP ASSY 1 1 1 220 43109369 GRILLE ASSY P 1 1 1 221 43170211 HOSE DRAIN 1 1 1 222 43107215 HOLDER SENSOR 1 1 1 223 43047609 BONNET 1 1 1 224 43049697 BONNET 1 1 1 225 43139154 BAND MOTOR LEFT 1 1 1 226 43139155 BAND MOTOR RIGHT 1 1 1 227 43139161 BAND MOTOR LEFT 1 1 1 228 43139162 BAND MOTOR ...

Page 151: ...070146 HOSE DRAIN 1 1 1 217 43122082 CASING ASSY 1 1 1 218 43172143 DRAIN PAN INST ASSY 1 1 1 219 43121731 PUMP ASSY 1 1 1 220 43109369 GRILLE ASSY P 1 1 1 221 43170211 HOSE DRAIN 1 1 1 222 43107215 HOLDER SENSOR 1 1 1 223 43047609 BONNET 1 1 1 224 43049697 BONNET 1 1 1 225 43139154 BAND MOTOR LEFT 1 1 1 226 43139155 BAND MOTOR RIGHT 1 1 1 227 43139161 BAND MOTOR LEFT 1 1 1 228 43139162 BAND MOTOR...

Page 152: ... SENSOR ASSY SERVICE TC 2 2 2 402 43050426 SENSOR SERVICE TA 1 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 1 404 43158204 TRANSFORMER TT 13 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 406 43160583 TERMINAL 6P 1 1 1 407 4316V444 P C BOARD ASSY MCC 1403 1 1 1 408 4316V345 P C BOARD ASSY MCC 1520 1 1 1 ...

Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...

Page 154: ... 1 1 217 43149352 NUT FLARE 5 8 IN 1 218 43149353 SOCKET 1 1 219 43149354 SOCKET 1 220 43151284 SWITCH FLOAT 1 1 1 221 43139152 BAND MOTOR 2 2 2 222 43179129 CAP DRAIN 1 1 1 223 43119481 NUT PLATE 2 2 2 224 43170240 HOSE DRAIN 1 1 1 225 43107215 HOLDER SENSOR 1 1 1 226 43047609 BONNET 1 227 43147195 BONNET 1 2 IN 1 1 228 43194029 BONNET 1 229 43149355 NUT FLARE 3 8 IN 1 230 43049697 BONNET 1 1 231...

Page 155: ...N 1 1 217 43149352 NUT FLARE 5 8 IN 1 218 43149353 SOCKET 1 1 219 43149354 SOCKET 1 220 43151284 SWITCH FLOAT 1 1 1 221 43139152 BAND MOTOR 2 2 2 222 43179129 CAP DRAIN 1 1 1 223 43119481 NUT PLATE 2 2 2 224 43170240 HOSE DRAIN 1 1 1 225 43107215 HOLDER SENSOR 1 1 1 226 43047609 BONNET 1 227 43147195 BONNET 1 2 IN 1 1 228 43194029 BONNET 1 229 43149355 NUT FLARE 3 8 IN 1 230 43049697 BONNET 1 1 23...

Page 156: ...AP0184SH E TR AP0244SH E TR 401 43050425 SENSOR ASSY SERVICE TC 2 2 2 402 43050426 SENSOR SERVICE TA 1 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 1 404 43160582 TERMINAL 4P 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 406 4316V437 P C BOARD ASSY MCC 1402 1 1 1 ...

Page 157: ...156 9 3 Compact 4 way cassette type MMU AP0074MH AP0094MH AP0124MH AP0154MH AP0184MH AP015 AP018 AP007 AP009 AP012 AP015 AP018 AP007 AP009 AP012 AP015 AP018 AP007 AP009 AP012 ...

Page 158: ...43170244 HOSE DRAIN 1 1 1 1 1 222 43079249 BAND HOSE 1 1 1 1 1 223 43060029 FILTER NOISE 2 2 2 2 2 224 43163052 HOLDER LEAD FAN MOTOR 1 1 1 1 1 225 43119482 COVER ASSY BODY 1 1 1 1 1 226 43170248 HOSE DRAIN 1 1 1 1 1 227 43119483 COVER PIPE 1 1 1 1 1 228 43097212 NUT 1 1 1 1 1 229 43107215 HOLDER SENSOR 1 1 1 1 1 230 43019904 HOLDER SENSOR TS 2 2 2 2 2 231 43179135 BAND HOSE 1 1 1 1 1 232 43149314...

Page 159: ...1 43170244 HOSE DRAIN 1 1 1 1 1 222 43079249 BAND HOSE 1 1 1 1 1 223 43060029 FILTER NOISE 2 2 2 2 2 224 43163052 HOLDER LEAD FAN MOTOR 1 1 1 1 1 225 43119482 COVER ASSY BODY 1 1 1 1 1 226 43170248 HOSE DRAIN 1 1 1 1 1 227 43119483 COVER PIPE 1 1 1 1 1 228 43097212 NUT 1 1 1 1 1 229 43107215 HOLDER SENSOR 1 1 1 1 1 230 43019904 HOLDER SENSOR TS 2 2 2 2 2 231 43179135 BAND HOSE 1 1 1 1 1 232 431493...

Page 160: ...R AP0154MH E TR AP0184MH E TR 401 43050425 SENSOR ASSY SERVICE TA 2 2 2 2 2 402 43050426 SENS0R SERVICE TC 1 1 1 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 1 1 1 404 43160582 TERMINAL 4P 1 1 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 406 4316V437 P C BOARD ASSY MCC 1402 1 1 1 1 1 ...

Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...

Page 162: ... BONNET 1 1 1 1 1 219 43179135 BAND HOSE 1 1 1 1 1 220 43149314 SHEET PMV 1 1 1 1 1 221 43146714 VALVE PMV 1 1 222 43196109 BUSHING 1 1 1 1 1 223 43049776 SOCKET 1 1 1 224 43149353 SOCKET 1 1 225 43047688 NUT FLARE 1 2 IN 1 1 226 43149355 NUT FLARE 3 8 IN 1 1 1 227 43047685 NUT FLARE 1 4 IN 1 1 1 1 1 228 43147662 STRAINER 1 1 1 1 1 229 43047609 BONNET 1 1 1 230 43047692 BONNET 1 1 231 43100320 PLA...

Page 163: ...97 BONNET 1 1 1 1 1 219 43179135 BAND HOSE 1 1 1 1 1 220 43149314 SHEET PMV 1 1 1 1 1 221 43146714 VALVE PMV 1 1 222 43196109 BUSHING 1 1 1 1 1 223 43049776 SOCKET 1 1 1 224 43149353 SOCKET 1 1 225 43047688 NUT FLARE 1 2 IN 1 1 226 43149355 NUT FLARE 3 8 IN 1 1 1 227 43047685 NUT FLARE 1 4 IN 1 1 1 1 1 228 43147662 STRAINER 1 1 1 1 1 229 43047609 BONNET 1 1 1 230 43047692 BONNET 1 1 231 43100320 P...

Page 164: ...401 43050425 SENSOR ASSY SERVICE TC 2 2 2 2 2 402 43050426 SENSOR SERVICE TA 1 1 1 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 1 1 1 404 43160575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 405 43163057 CLAMP DOWN 1 1 1 1 1 406 43163058 CLAMP UP 1 1 1 1 1 407 4316V437 P C BOARD ASSY MCC 1402 1 1 1 1 1 408 43160582 TERMINAL 4P 1 1 1 1 1 ...

Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...

Page 166: ...165 ...

Page 167: ...3 LEAD MOTOR FAN 1 1 1 1 1 232 43100284 PLATE ASSY A 1 1 1 233 43100285 PLATE ASSY A 1 1 236 43100288 PLATE B 1 1 1 1 1 239 43100291 FLANGE 1 1 240 43100292 FLANGE 1 1 1 244 43172168 PAN ASSY DRAIN 1 1 245 43172169 PAN ASSY DRAIN 1 1 1 246 4314Q039 DISTRIBUTOR ASSY 1 1 1 247 4314Q040 DISTRIBUTOR ASSY 1 1 250 43107215 HOLDER SENSOR 1 1 1 1 1 251 43047609 BONNET 1 1 1 252 43047692 BONNET 1 1 254 430...

Page 168: ...553 LEAD MOTOR FAN 1 1 1 1 1 232 43100284 PLATE ASSY A 1 1 1 233 43100285 PLATE ASSY A 1 1 236 43100288 PLATE B 1 1 1 1 1 239 43100291 FLANGE 1 1 240 43100292 FLANGE 1 1 1 244 43172168 PAN ASSY DRAIN 1 1 245 43172169 PAN ASSY DRAIN 1 1 1 246 4314Q039 DISTRIBUTOR ASSY 1 1 1 247 4314Q040 DISTRIBUTOR ASSY 1 1 250 43107215 HOLDER SENSOR 1 1 1 1 1 251 43047609 BONNET 1 1 1 252 43047692 BONNET 1 1 254 4...

Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...

Page 170: ...169 ...

Page 171: ...231 43160553 LEAD MOTOR FAN 1 1 1 1 1 234 43100286 PLATE ASSY A 1 1 1 235 43100287 PLATE ASSY A 1 1 236 43100288 PLATE B 1 1 1 1 1 237 43100289 FLANGE 1 1 238 43100290 FLANGE 1 1 1 241 43125163 SHAFT 1 1 242 43172166 PAN ASSY DRAIN 1 1 243 43172167 PAN ASSY DRAIN 1 1 1 248 4314Q041 DISTRIBUTOR ASSY 1 1 1 249 4314Q042 DISTRIBUTOR ASSY 1 1 250 43107215 HOLDER SENSOR 1 1 1 1 1 251 43047609 BONNET 1 1...

Page 172: ...1 231 43160553 LEAD MOTOR FAN 1 1 1 1 1 234 43100286 PLATE ASSY A 1 1 1 235 43100287 PLATE ASSY A 1 1 236 43100288 PLATE B 1 1 1 1 1 237 43100289 FLANGE 1 1 238 43100290 FLANGE 1 1 1 241 43125163 SHAFT 1 1 242 43172166 PAN ASSY DRAIN 1 1 243 43172167 PAN ASSY DRAIN 1 1 1 248 4314Q041 DISTRIBUTOR ASSY 1 1 1 249 4314Q042 DISTRIBUTOR ASSY 1 1 250 43107215 HOLDER SENSOR 1 1 1 1 1 251 43047609 BONNET 1...

Page 173: ...172 MMD AP0564BH ...

Page 174: ...173 ...

Page 175: ...94 SWITCH FLOAT 1 231 43160553 LEAD MOTOR FAN 1 235 43100287 PLATE ASSY A 1 236 43100288 PLATE B 1 237 43100289 FLANGE 1 241 43125163 SHAFT 1 242 43172166 PAN ASSY DRAIN 1 249 4314Q042 DISTRIBUTOR ASSY 1 250 43107215 HOLDER SENSOR 1 251 43047609 BONNET 1 253 43194029 BONNET 1 254 43047686 NUT FLARE 3 8 IN 1 256 43019904 HOLDER SENSOR TS 2 257 43179110 PLUG 1 259 43179126 RUBBER PUMP DRAIN 3 260 43...

Page 176: ...94 SWITCH FLOAT 1 231 43160553 LEAD MOTOR FAN 1 235 43100287 PLATE ASSY A 1 236 43100288 PLATE B 1 237 43100289 FLANGE 1 241 43125163 SHAFT 1 242 43172166 PAN ASSY DRAIN 1 249 4314Q042 DISTRIBUTOR ASSY 1 250 43107215 HOLDER SENSOR 1 251 43047609 BONNET 1 253 43194029 BONNET 1 254 43047686 NUT FLARE 3 8 IN 1 256 43019904 HOLDER SENSOR TS 2 257 43179110 PLUG 1 259 43179126 RUBBER PUMP DRAIN 3 260 43...

Page 177: ...176 E Parts ...

Page 178: ...E TR AP0274BH E TR AP0304BH E TR AP0364BH E TR AP0484BH E TR 401 43050425 SENSOR ASSY SERVICE TC 2 2 2 2 2 402 43050426 SENSOR SERVICE TA 1 1 1 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 1 1 1 404 43158193 REACTOR CH 43 2Z T 1 1 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 406 4316V438 P C BOARD ASSY MCC 1402 1 1 1 1 1 407 43160582 TERMINAL 4P 1 1 1 1 1 Location No Part No Description MMD A...

Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...

Page 180: ... FLARE 1 4 IN 1 218 43149355 NUT FLARE 3 8 IN 1 1 1 1 219 43049776 SOCKET 1 1 1 1 220 43149351 SOCKET 1 221 43047688 NUT FLARE 1 2 IN 1 222 43149352 NUT FLARE 5 8 IN 1 1 1 1 223 43149353 SOCKET 1 224 43149354 SOCKET 1 1 1 1 228 43107215 HOLDER SENSOR 1 1 1 1 1 229 43047609 BONNET 1 1 1 1 230 43147195 BONNET 1 2 IN 1 231 43194029 BONNET 1 1 1 1 232 43049697 BONNET 1 233 43139154 BAND MOTOR LEFT 2 2...

Page 181: ...UT FLARE 1 4 IN 1 218 43149355 NUT FLARE 3 8 IN 1 1 1 1 219 43049776 SOCKET 1 1 1 1 220 43149351 SOCKET 1 221 43047688 NUT FLARE 1 2 IN 1 222 43149352 NUT FLARE 5 8 IN 1 1 1 1 223 43149353 SOCKET 1 224 43149354 SOCKET 1 1 1 1 228 43107215 HOLDER SENSOR 1 1 1 1 1 229 43047609 BONNET 1 1 1 1 230 43147195 BONNET 1 2 IN 1 231 43194029 BONNET 1 1 1 1 232 43049697 BONNET 1 233 43139154 BAND MOTOR LEFT 2...

Page 182: ...1 1 1 404 43150320 SENSOR ASSY SERVICE 1 1 1 1 1 405 43154173 RELAY LY2F L AC230V 1 1 1 1 1 406 43155206 CAPACITOR 1 1 1 1 407 43155208 CAPACITOR 1 409 43158204 TRANSFORMER 1 1 1 1 1 410 43160575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 411 43160576 TERMINAL BLOCK 4P 20A 1 1 1 1 1 412 43160577 FUSE 10A 1 1 1 1 1 413 43160582 TERMINAL 4P 1 1 1 1 1 414 4316V444 P C BOARD ASSY MCC 1403 1 1 1 1 1 415 4316V345 ...

Page 183: ...182 MMD AP0724H AP0964H ...

Page 184: ...183 ...

Page 185: ...5EE 1 1 220 43166004 REMOTE CONTROLLER SX A11JE2 1 1 221 431S8205 OWNER S MANUAL MMY MAP0804HT8 E 1 1 Location No Part No Description MMD AP0724H TR MMD AP0964H TR 201 4312C023 MOTOR FAN 3 3 202 43146707 MOTOR PMV 1 1 203 43146729 BODY PMV 1 1 204 4314J340 EVAPORATOR ASSY 1 1 205 4314Q091 DISTRIBUTOR ASSY 1 1 206 43122106 CASE FAN 3 3 207 43120237 FAN 3 3 208 43047688 NUT FLARE 1 2 IN 1 1 209 4314...

Page 186: ... 3 404 43150320 SENSOR ASSY SERVICE 1 1 405 43154173 RELAY LY2F L AC230V 2 2 406 43155219 CAPACITOR 3 3 407 43158204 TRANSFORMER 1 1 408 43160575 TERMINAL BLOCK 2P 20A 1 1 409 43160576 TERMINAL BLOCK 4P 20A 3 3 410 43160577 FUSE 10A 3 3 411 43160582 TERMINAL 4P 1 1 412 4316V444 P C BOARD ASSY MCC 1403 1 1 413 4316V345 P C BOARD ASSY MCC 1520 1 1 414 43060157 TERMINAL BLOCK 4P 1 1 ...

Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...

Page 188: ...0556 LEAD LOUVER HORIZONTAL 1 1 1 1 240 43109409 GRILLE A SSY HORIZONTAL 1 1 241 43109410 GRILLE A SSY HORIZONTAL 1 1 243 43107252 SHAFT HOLIZONTAL LOUVER 1 1 1 1 244 43107260 SUPPORT GRILLE HORIZONTAL 1 1 1 1 245 43122086 GRILLE A SSY VERTICAL 2 2 2 2 246 43179129 CAP DRAIN 1 1 1 1 247 43107254 H1NGE GRILLE INLET 4 4 4 4 248 43107255 HOOK GRILLE INLET 2 2 2 2 249 43108016 MARK TOSHIBA 1 1 1 1 250...

Page 189: ...60556 LEAD LOUVER HORIZONTAL 1 1 1 1 240 43109409 GRILLE A SSY HORIZONTAL 1 1 241 43109410 GRILLE A SSY HORIZONTAL 1 1 243 43107252 SHAFT HOLIZONTAL LOUVER 1 1 1 1 244 43107260 SUPPORT GRILLE HORIZONTAL 1 1 1 1 245 43122086 GRILLE A SSY VERTICAL 2 2 2 2 246 43179129 CAP DRAIN 1 1 1 1 247 43107254 H1NGE GRILLE INLET 4 4 4 4 248 43107255 HOOK GRILLE INLET 2 2 2 2 249 43108016 MARK TOSHIBA 1 1 1 1 25...

Page 190: ...189 MMC AP0364H AP0484H ...

Page 191: ...242 43109411 GRILLE A SSY HORIZONTAL 1 1 243 43107252 SHAFT HOLIZONTAL LOUVER 1 1 244 43107260 SUPPORT GRILLE HORIZONTAL 2 2 245 43122086 GRILLE A SSY VERTICAL 3 3 246 43179129 CAP DRAIN 1 1 247 43107254 HINGE GRILLE INLET 6 6 248 43107255 HOOK GRILLE INLET 3 3 249 43108016 MARK TOSHIBA 1 1 250 43170234 HOSE DRAIN 1 1 251 43102647 COVER SIDE RIGHT 1 1 252 43102648 COVER SIDE LEFT 1 1 258 43191665 ...

Page 192: ...242 43109411 GRILLE A SSY HORIZONTAL 1 1 243 43107252 SHAFT HOLIZONTAL LOUVER 1 1 244 43107260 SUPPORT GRILLE HORIZONTAL 2 2 245 43122086 GRILLE A SSY VERTICAL 3 3 246 43179129 CAP DRAIN 1 1 247 43107254 HINGE GRILLE INLET 6 6 248 43107255 HOOK GRILLE INLET 3 3 249 43108016 MARK TOSHIBA 1 1 250 43170234 HOSE DRAIN 1 1 251 43102647 COVER SIDE RIGHT 1 1 252 43102648 COVER SIDE LEFT 1 1 258 43191665 ...

Page 193: ...TG 1 1 1 1 404 43160582 TERMINAL 4P 1 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 1 406 4316V437 P C BOARD ASSY MCC 1402 1 1 1 1 Location No Part No Description MMC AP0364H E TR AP0484H E TR 401 43050425 SENSOR ASSY SERVICE TC 2 2 402 43050426 SENSOR SERVICE TA 1 1 403 43150320 SENSOR ASSY SERVICE TG 1 1 404 43160582 TERMINAL 4P 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 406 4316V437 P C BOARD ...

Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...

Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...

Page 196: ...LARE 1 2 IN 1 1 231 43149352 NUT FLARE 5 8 IN 1 1 232 43149353 SOCKET 1 1 233 43149354 SOCKET 1 1 235 43139093 CONNECTION ROD 5 5 5 5 236 3759V024 GRILLE ASSY 1 1 1 1 237 43109207 GRILLE OUTLET VERTICAL 5 5 5 5 238 43100373 CABINET LOWER 1 1 1 1 239 4314Q084 DISTRIBUTOR ASSY 1 1 240 4314Q085 DISTRIBUTOR ASSY 1 1 242 43107215 HOLDER SENSOR 1 1 1 1 243 43047609 BONNET 1 1 244 43147195 BONNET 1 2 IN ...

Page 197: ...FLARE 1 2 IN 1 1 231 43149352 NUT FLARE 5 8 IN 1 1 232 43149353 SOCKET 1 1 233 43149354 SOCKET 1 1 235 43139093 CONNECTION ROD 5 5 5 5 236 3759V024 GRILLE ASSY 1 1 1 1 237 43109207 GRILLE OUTLET VERTICAL 5 5 5 5 238 43100373 CABINET LOWER 1 1 1 1 239 4314Q084 DISTRIBUTOR ASSY 1 1 240 4314Q085 DISTRIBUTOR ASSY 1 1 242 43107215 HOLDER SENSOR 1 1 1 1 243 43047609 BONNET 1 1 244 43147195 BONNET 1 2 IN...

Page 198: ...197 MMF AP0364H AP0484H AP0564H ...

Page 199: ...198 MMF AP0364H AP0484H AP0564H ...

Page 200: ...OCKET 1 1 1 231 43149352 NUT FLARE 5 8 IN 1 1 1 233 43149354 SOCKET 1 1 1 235 43139093 CONNECTION ROD 5 5 5 236 3759V024 GRILLE ASSY 1 1 1 237 43109207 GRILLE OUTLET VERTICAL 5 5 5 238 43100373 CABINET LOWER 1 1 1 241 4314Q086 DISTRIBUTOR ASSY 1 1 1 242 43107215 HOLDER SENSOR 1 1 1 243 43047609 BONNET 1 1 1 245 43194029 BONNET 1 1 1 247 43139154 BAND MOTOR LEFT 2 2 2 248 43139155 BAND MOTOR RIGHT ...

Page 201: ...SOCKET 1 1 1 231 43149352 NUT FLARE 5 8 IN 1 1 1 233 43149354 SOCKET 1 1 1 235 43139093 CONNECTION ROD 5 5 5 236 3759V024 GRILLE ASSY 1 1 1 237 43109207 GRILLE OUTLET VERTICAL 5 5 5 238 43100373 CABINET LOWER 1 1 1 241 4314Q086 DISTRIBUTOR ASSY 1 1 1 242 43107215 HOLDER SENSOR 1 1 1 243 43047609 BONNET 1 1 1 245 43194029 BONNET 1 1 1 247 43139154 BAND MOTOR LEFT 2 2 2 248 43139155 BAND MOTOR RIGHT...

Page 202: ...06 43160582 TERMINAL 4P 1 1 1 1 407 4316V444 P C BOARD ASSY MCC 1403 1 1 1 1 408 4316V345 P C BOARD ASSY MCC 1520 1 1 1 1 Location No Part No Description MMF AP0364H E TR AP0484H E TR AP0564H E TR 401 43050425 SENSOR ASSY SERVICE 2 2 2 402 43050426 SENSOR SERVICE 1 1 1 403 43150320 SENSOR ASSY SERVICE 1 1 1 404 43158204 TRANSFORMER 1 1 1 405 43160575 TERMINAL BLOCK 2P 20A 1 1 1 406 43160582 TERMIN...

Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...

Page 204: ... 3 8 IN 1 1 1 223 43049776 SOCKET 1 1 1 224 43149351 SOCKET 1 1 1 1 1 225 43047688 NUT FLARE 1 2 IN 1 1 227 43149353 SOCKET 1 1 229 43122046 PLATE WIND 2 2 2 230 43170197 HOSE ASSY 1 1 1 1 1 231 43107215 HOLDER SENSOR 1 1 1 1 1 232 43047609 BONNET 1 1 1 233 43147195 BONNET 1 2 IN 1 1 235 43049697 BONNET 1 1 1 1 1 236 43139154 BAND MOTOR LEFT 2 2 2 2 2 237 43139155 BAND MOTOR RIGHT 2 2 2 2 2 238 43...

Page 205: ...RE 3 8 IN 1 1 1 223 43049776 SOCKET 1 1 1 224 43149351 SOCKET 1 1 1 1 1 225 43047688 NUT FLARE 1 2 IN 1 1 227 43149353 SOCKET 1 1 229 43122046 PLATE WIND 2 2 2 230 43170197 HOSE ASSY 1 1 1 1 1 231 43107215 HOLDER SENSOR 1 1 1 1 1 232 43047609 BONNET 1 1 1 233 43147195 BONNET 1 2 IN 1 1 235 43049697 BONNET 1 1 1 1 1 236 43139154 BAND MOTOR LEFT 2 2 2 2 2 237 43139155 BAND MOTOR RIGHT 2 2 2 2 2 238 ...

Page 206: ...205 MML AP0244BH ...

Page 207: ... SX A11JE2 1 248 43166006 REMOTE CONTROLLER WH H1JE2 1 249 431S8205 OWNER S MANUAL MMY MAP0804HT8 E 1 Location No Part No Description MML AP0244BH TR 201 43723020 CASE FAN LEFT 2 202 43126119 CASE FAN RIGHT 2 204 43155171 CAPACITOR 1 206 4312C008 MOTOR FAN 1 208 43146707 MOTOR PMV 1 210 43146726 BODY PMV 1 211 43120232 FAN MULTI BLADE 2 213 43180295 FILTER 1 214 43170206 CATCH DRAIN 1 217 4314J431...

Page 208: ...60575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 406 43160582 TERMINAL 4P 1 1 1 1 1 407 4316V444 P C BOARD ASSY MCC 1403 1 1 1 1 1 408 4316V345 P C BOARD ASSY MCC 1520 1 1 1 1 1 Location No Part No Description MML AP0244BH E TR 401 43050425 SENSOR ASSY SERVICE TC 2 402 43050426 SENSOR SERVICE TA 1 403 43150320 SENSOR ASSY SERVICE TG 1 404 43158204 TRANSFORMER 1 405 43160575 TERMINAL BLOCK 2P 20A 1 406 431605...

Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...

Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...

Page 211: ...SSY 1 1 228 4314Q074 DISTRIBUTOR ASSY 1 229 43047685 NUT FLARE 1 4 IN 1 1 1 1 1 230 43149355 NUT FLARE 3 8 IN 1 1 1 231 43049776 SOCKET 1 1 1 232 43149351 SOCKET 1 1 1 1 1 233 43047688 NUT FLARE 1 2 IN 1 1 235 43149353 SOCKET 1 1 237 43100374 CABINET UPPER WHITE 1 1 1 1 1 238 43100228 OUTLET WHITE 1 1 1 1 1 239 43109395 GRILLE WHITE 3 3 3 3 3 240 43109240 GRILLE 1 1 1 1 1 241 43170201 HOSE DRAIN 1...

Page 212: ... ASSY 1 1 228 4314Q074 DISTRIBUTOR ASSY 1 229 43047685 NUT FLARE 1 4 IN 1 1 1 1 1 230 43149355 NUT FLARE 3 8 IN 1 1 1 231 43049776 SOCKET 1 1 1 232 43149351 SOCKET 1 1 1 1 1 233 43047688 NUT FLARE 1 2 IN 1 1 235 43149353 SOCKET 1 1 237 43100374 CABINET UPPER WHITE 1 1 1 1 1 238 43100228 OUTLET WHITE 1 1 1 1 1 239 43109395 GRILLE WHITE 3 3 3 3 3 240 43109240 GRILLE 1 1 1 1 1 241 43170201 HOSE DRAIN...

Page 213: ...212 MML AP0244H ...

Page 214: ...213 MML AP0244H ...

Page 215: ...8 IN 1 231 43049776 SOCKET 1 234 43149352 NUT FLARE 5 8 IN 1 236 43149354 SOCKET 1 237 43100374 CABINET UPPER WHITE 1 238 43100228 OUTLET WHITE 1 239 43109395 GRILLE WHITE 3 240 43109240 GRILLE 1 241 43170201 HOSE DRAIN 1 242 43107215 HOLDER SENSOR 1 243 43047609 BONNET 1 245 43194029 BONNET 1 247 43196087 BUSHING GRILLE 6 248 43139154 BAND MOTOR LEFT 2 249 43139155 BAND MOTOR RIGHT 2 250 43122104...

Page 216: ...8 IN 1 231 43049776 SOCKET 1 234 43149352 NUT FLARE 5 8 IN 1 236 43149354 SOCKET 1 237 43100374 CABINET UPPER WHITE 1 238 43100228 OUTLET WHITE 1 239 43109395 GRILLE WHITE 3 240 43109240 GRILLE 1 241 43170201 HOSE DRAIN 1 242 43107215 HOLDER SENSOR 1 243 43047609 BONNET 1 245 43194029 BONNET 1 247 43196087 BUSHING GRILLE 6 248 43139154 BAND MOTOR LEFT 2 249 43139155 BAND MOTOR RIGHT 2 250 43122104...

Page 217: ...575 TERMINAL BLOCK 2P 20A 1 1 1 1 1 406 43160582 TERMINAL 4P 1 1 1 1 1 407 4316V469 P C BOARD ASSY MCC 1403 1 1 1 1 1 408 4316V345 P C BOARD ASSY MCC 1520 1 1 1 1 1 Location No Part No Description MML AP0244H E TR 401 43050425 SENSOR ASSY SERVICE 2 402 43050426 SENSOR SERVICE 1 403 43150320 SENSOR ASSY SERVICE 1 404 43158204 TRANSFORMER 1 405 43160575 TERMINAL BLOCK 2P 20A 1 406 43160582 TERMINAL ...

Page 218: ...sed in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 T...

Page 219: ...INATOKU TOKYO 108 0075 JAPAN Copyright 1999 to 2012 TOSHIBA CARRIER CORPORATION ALL Rights Reserved 2nd publication in Mar 2012 File No A10 033 1 REVISED EDITION 1 1st publication in Apr 2011 File No A10 033 Specifications subject to change without notice ...

Reviews: