65
◆
Target outdoor unit (SMMS-i – Series 4)
*1 The TF/TSA/TOA sensors are equipped only with some types of indoor units. The data does not appear for other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
✽
, 5
✽
... U1 outdoor unit (Header unit)
2
✽
, 6
✽
... U2 outdoor unit (follower unit 1)
3
✽
, 7
✽
... U3 outdoor unit (follower unit 2)
4
✽
, 8
✽
... U4 outdoor unit (follower unit 3)
*5 Only CODE No. 5
✽
of U1 outdoor unit (Header unit) is displayed.
CODE No.
Data
Format
Unit
Remote controller display example
Indoor unit
data *2
00
Room temperature (in control)
×1
°C
[0024]=24 °C
01
Room temperature (Remote controller)
×1
°C
02
Air Temperature (TA)
×1
°C
03
Coil Temperature (TCJ)
×1
°C
04
Coil Temperature (TC2)
×1
°C
05
Coil Temperature (TC1)
×1
°C
06
Discharge temperature (TF) *1
×1
°C
08
PMV
×1/10
pls
[0150]=1500 pls
F9
Air Suction Temperature of direct expansion
coil (TSA) *1
×1
°C
[0024]=24 °C
FA
Outdoor Air Temperature (TOA) *1
×1
°C
System
data
0A
Number of connected indoor units
×1
–
[0048]=48
0B
Total horse power of connected indoor units
×10
HP
[0415]=41.5HP
0C
Number of connected outdoor units
×1
–
[0004]=4
0D
Total horse power of outdoor units
×10
HP
[0420]=42HP
CODE No.
Data
Format
Unit
Remote controller display example
U1 U2 U3 U4
Individual
data 1 of
outdoor unit
*3
10 20 30
40
Detection pressure of high-pressure sensor
(Pd)
×100
MPa
[0123]=1.23 MPa
11 21 31
41
Detection pressure of low-pressure sensor
(Ps)
×100
MPa
12 22 32
42
Discharge temperature of compressor 1
(Td1)
×1
°C
[0024]=24 °C
13 23 33
43
Discharge temperature of compressor 2
(Td2)
×1
°C
14 24 34
–
Discharge temperature of compressor 3
(Td3)
×1
°C
15 25 35
45 Suction Temperature (TS)
×1
°C
16 26 36
46 Coil Temperature 1 (TE1)
×1
°C
17 27 37
–
Coil Temperature 2 (TE2)
×1
°C
18 28 38
48 Liquid Temperature (TL)
×1
°C
19 29 39
49 Outdoor Temperature (TO)
×1
°C
1A 2A 3A 4A PMV1 + 2
×1
pls
[0050]=500 pls
1B 2B 3B
–
PMV4
×1
pls
1C 2C 3C 4C Current of compressor 1 (I1)
×10
A
[0135]=13.5 A
1D 2D 3D 4D Current of compressor 2 (I2)
×10
A
1E 2E 3E
–
Current of compressor 3 (I3)
×10
A
1F 2F 3F 4F Outdoor fan current (IFan)
×10
A
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...