– 69 –
Check code
Display of receiving unit
Typical fault site
Description of error
Outdoor 7-segment display Indicator light block
Sub-code
Flash
Timer Ready
Operation
⎯
⎯
⎯
⎯
⎯
⎯
E01
E02
E02
Main
remote
controller
No master remote controller,
faulty remote controller
communication (reception)
Faulty remote controller
communication (transmission)
Signals cannot be received from indoor unit; master remote
controller has not been set (including two remote controller
control).
Signals cannot be transmitted to indoor unit.
Duplicated master remote
controller
Both remote controllers have been set as master remote
controller in two remote controller control (alarm and
shutdown for header unit and continued operation for
follower unit)
(Error detected by main remote controller)
Check code
Display of receiving unit
Typical fault site
Description of error
Outdoor 7-segment display Indicator light block
Sub-code
Flash
Timer Ready
Operation
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
C05
⎯
⎯
C06
C12
P30
(Error detected by central control device)
TCC-LINK
central
control
No indication
(when main remote
controller also in
use)
Faulty central control
communication (transmission)
Faulty central control
communication (reception)
Multiple network adapters
Central control device is unable to transmit signal due to
duplication of central control device (AI-NET).
Central control device is unable to receive signal.
Multiple network adapters are connected to remote
controller communication line (AI-NET).
Blanket alarm for general-
purpose device control
interface
Device connected to general-purpose device control
interface for TCC-LINK / AI-NET is faulty.
As per alarm unit (see
above)
Group control follower unit
error
Group follower unit is faulty (unit No. and above detail
[
∗∗∗
] displayed on main remote controller)
Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller / central control device do not necessarily have a direct impact on air
conditioner operation.
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...