91
MG-CTT: Magnet contactor
Check code
Location
of
detection
Description
System
status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
AI-NET central
control
remote
controller
Check
code
Sub-code
P05
P05
SMMS (Series 1)
01: Open phase
detected
02: Phase
sequence error
I/F
Open phase detected,
Phase sequence error
All stop
• Phase sequence
error was detected
when the power is
turned on.
• Open phase error
was detected
when the power is
turned on.
• Check the phase sequence of
outdoor power wiring.
• Check the outdoor PC board
(I/F) error.
SMMS-i
(Series 4)
00:
AF
I/F
Detection of open
phase / phase
sequence
All stop
• Open phase is
detected when
power is turned
on.
• Inverter DC
voltage is too high
(overvoltage) or
too low
(undervoltage).
• Check for defect in outdoor
P.C. board (I/F).
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
Inverter DC voltage
(Vdc) error
(compressor)
MG-CTT error
P07
P07
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
1C
IPDU
I/F
Heat sink overheating
error
All stop
Temperature sensor
built into IGBT (TH)
is overheated.
• Check power supply voltage.
• Check outdoor fan system
error.
• Check heat sink cooling duct
for clogging.
• Check IGBT and heat sink for
thermal performance for faulty
installation.
(e.g. mounting screws and
thermal conductivity)
• Check for defect in A3-IPDU.
(faulty IGBT built-in
temperature sensor (TH))
P10
P10
Detected indoor
address
0b
Indoor
unit
Indoor overflow error
All stop
• Float switch
operates.
• Float switch circuit
is open-circuited
or disconnected at
connector.
• Check float switch connector.
• Check operation of drain
pump.
• Check drain pump circuit.
• Check drain pipe for clogging.
• Check for defect in indoor
P.C. board.
P12
–
–
11
Indoor
unit
Indoor fan motor error
Stop of
corresponding
unit
• Motor speed
measurements
continuously
deviate from target
value.
• Overcurrent
protection is
activated.
• Check connection of fan
connector and wiring.
• Check for defect in fan motor.
• Check for defect in indoor
P.C. board.
• Check impact of outside air
treatment (OA).
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...