94
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
AI-NET central
control
remote
controller
Check
code
Sub-code
P22
P22
SMMS (Series 1)
08: Out of step
0A: IDC
activation
0E: Sync error
0F: Control error
06: Maximum
rotation
exceeded
04: Rotation
difference error
0D: Lock
0C: Fan lock
IPDU
Outdoor fan
IPDU error
All stop
(Sub code: 08)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
• Check the fan motor.
• Check the connector
connection for fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 0A)
FAN IPDU overcurrent
protection circuit
Overcurrent was detected
when the fan started running
or during operation.
• Check the fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 0E)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
• Check the fan motor.
• Check the connector
connection for fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 0F)
FAN IPDU position detection
circuit
Position detection is not
performed properly.
• Check the fan motor.
• Check the connector
connection for fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 06)
External factors such as
blast
Position detection is not
performed properly.
(Restarted in 6 seconds)
• Check the fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 04)
External factors such as
blast
The difference between
targeted rotation and actual
rotation is 25% or more.
(Restarted in 6 seconds)
• Check the fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 0D)
FAN IPDU position detection
circuit
Position detection is not
performed properly. (No
wind)
• Check the fan motor.
• Check the connector
connection for fan motor.
• Check the error of IPDU
board for fan.
All stop
(Sub code: 0C)
External factors such as
blast
Position detection is not
performed properly. (Wind
blows) (Restarted in 6
seconds)
• Check the fan motor.
• Check the error of IPDU
board for fan.
Summary of Contents for A03-009
Page 149: ...148 ...
Page 153: ...152 9 2 1 Way cassette type SH AP015 AP018 AP024 ...
Page 161: ...160 9 4 Slim duct type MMD AP0074SPH AP0094SPH AP0124SPH AP0154SPH AP0184SPH ...
Page 165: ...164 9 5 Concealed duct standard type MMD AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 166: ...165 ...
Page 169: ...168 MMD AP0244BH AP0274BH AP0304BH AP0364BH AP0484BH ...
Page 170: ...169 ...
Page 173: ...172 MMD AP0564BH ...
Page 174: ...173 ...
Page 177: ...176 E Parts ...
Page 179: ...178 9 6 Concealed duct high static pressure type MMD AP0184H AP0244H AP0274H AP0364H AP0484H ...
Page 183: ...182 MMD AP0724H AP0964H ...
Page 184: ...183 ...
Page 187: ...186 9 7 Ceiling type MMC AP0154H AP0184H AP0244H AP0274H ...
Page 190: ...189 MMC AP0364H AP0484H ...
Page 194: ...193 9 8 Floor standing type MMF AP0154H AP0184H AP0244H AP0274H ...
Page 195: ...194 MMF AP0154H AP0184H AP0244H AP0274H ...
Page 198: ...197 MMF AP0364H AP0484H AP0564H ...
Page 199: ...198 MMF AP0364H AP0484H AP0564H ...
Page 203: ...202 9 9 Floor standing concealed type MML AP0074BH AP0094BH AP0124BH AP0154BH AP0184BH ...
Page 206: ...205 MML AP0244BH ...
Page 209: ...208 9 10 Floor standing cabinet type MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 210: ...209 MML AP0074H AP0094H AP0124H AP0154H AP0184H ...
Page 213: ...212 MML AP0244H ...
Page 214: ...213 MML AP0244H ...