158
ACE-tronics G9 ASD Installation and Operation Manual
Load Sharing Gain Input
Program
Torque
Torque Control
This parameter Enables/Disables the Load Sharing Gain input function.
This feature is enabled by selecting a Load Sharing Gain input signal source.
Settings:
Disabled
V/I
RR
RX
Panel Keypad
RS485 2-Wire
RS485 4-Wire
Communication Option Board
RX2 Option (AI1)
Direct Access Number — F424
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Forward Speed Limit Input
Program
Torque
Torque Speed Limiting
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the input selected here.
If Setting is selected, the value set at
F426
is used as the Forward Speed Limit
input.
Settings:
Disabled
V/I
RR
RX
F426
Setting
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Forward Speed Limit Level
Program
Torque
Torque Control
This parameter provides a value to be used as the Forward Speed Limit setting
if
F426
Setting is selected at
F425
.
Direct Access Number — F426
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper Limit (
F012
)
Units — Hz
F424
F426