ACE-tronics G9 ASD Installation and Operation Manual
195
Command Mode/Frequency Mode Change Lockout
Program
Utilities
Prohibition
This function is not used with the ACE-tronics G9 ASD.
Settings:
Unlocked
Locked
Direct Access Number — F736
Parameter Type — Selection List
Factory Default — Locked
Changeable During Run — Yes
Lockout All Keys
Program
Utilities
Prohibition
This function is not used with the ACE-tronics G9 ASD.
Settings:
Unlocked
Locked
Direct Access Number — F737
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Yes
Trace Selection
Program
Utilities
Trace
In conjunction with parameter
F741
–
F745
, this parameter is used to monitor
and store 4 ASD output waveform data points. The data may be read and stored
as a function of a trip (At Trip) or it may be initiated by the activation of a
discrete terminal activation (At Trigger).
Set a discrete input terminal to Trace Back Trigger Signal and activate the
terminal to initiate the At Trigger read/store function.
Table 12 on pg. 245
lists the items that may be selected for the data read/store
function along with the associated communication number for each selection.
The duration of the read/store cycle for the selected items is set at parameter
F741
.
To acquire and store the data a communications device and a PC are required.
The ACE-tronics G9 ASD supports the following communications protocols:
RS485 (MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol, CC-Link,
ProfiBus, and DeviceNet (Refer to the manual of each protocol type for
additional information).
Trace data may be viewed graphically via Program
Utilities
View Trace
Data.
Settings:
None (Disabled)
At Trip
At Trigger
Direct Access Number — F740
Parameter Type — Selection List
Factory Default — At Trip
Changeable During Run — Yes
F736
F740