72
Flow chart of setting central control address (digest)
(In case of central remote controller TCB-SC642TLE)
Automatic
setting?
Completion of indoor unit
addresses
Set from wired
remote controller?
Manual setting
Yes
Yes
Method
Yes
No
(No duplication)
Yes
(Duplication is
discovered.)
VRF* system?
Duplication?
*Super MMS
Super HRM
Automatic setting
Setting from central remote controller
Digital Inverter
Super Digital Inverter
1 by 1 model
No
No
No
Central remote controller
(TCB-SC642TLE)
End
Checking from central remote controller
for duplication of central control address
(1) Press the and buttons at the
same time for more than 4 sec.
(2) Select CODE No. C3 using setup
temp. buttons.
(3) Press the button.
(4) indication flashes and central
control address duplicated error check
starts.
(5) The check is completed when CODE
No. C3 flashes and goes off.
(6) If any duplication is discovered, the
GROUP No. will flash.
The central control address is cleared
by selecting the data where GROUP
No. is flashing and by pressing the
button.
Set the correct central control address.
Checking duplication of central control address.
(1) Press button three times.
If any duplication is discovered, error code "L20" is displayed.
Wired remote controller : Displayed promptly.
Central remote controller : Max. 4 min. later.
Method
Method
Manual setting from wired remote
controller (RBC-AMT21E)
(1) Press the and buttons at the
same time for more than 4 sec.
(Don't press button.)
(2) Set CODE No. to 03 using setup
temp. buttons.
(3) Set the central control address
using timer buttons.
(4) Press the button to register
the address.
( indications changes from
flashing to ON state.)
(5) Press the button.
(6) indications changes from
ON state to flashing.
(approx. 1 minute.)
(7) End
Manual setting from central
remote controller (TCB-SC642TLE)
(1) Press the and buttons at
the same time for more than 4 sec.
(2) Set CODE No. to C1 using
setup temp. buttons.
(3) Press the button.
(4) Select the zone and group No.
with and
(Group) buttons.
(5) Set the Unit No. (Indoor and line
address) with and buttons.
(6) Press the button.
(7) Register the other Unit No. in
the same way following the
steps (4) to (6).
(8) Press the button.
(9) flashes for a few minutes,
then OFF.
(10)End
Automatic setting from central
remote controller (TCB-SC642TLE)
(1) Press the and buttons at
the same time for more than 4 sec.
(2) Select CODE No. C2 by
pressing setup temp.
buttons.
(3) Press the button.
("C2" changes from flashing to
ON state and automatic setting
will start.)
(4) Finishing automatic setting,
changes from flashing to
OFF.
(5) Press the button.
(6) flashes for a few minutes,
then OFF.
Setting from wired
remote controller
SET
SET
SET
UNIT
SET
SET
CL
(For detailed setting procedure, refer to installation manual attached
central control devices.)
Summary of Contents for BMS-TP0640ACE
Page 1: ...FILE NO A04 016 TCS NET AIR CONDITIONING CONTROL SYSTEM TOUCHSCREENCONTROLLER TENTATIVE ...
Page 16: ...16 ...
Page 17: ...17 2 SYSTEM CONFIGURATION 2 1 Touch screen controller system configuration ...
Page 22: ...22 ...
Page 54: ...54 ...
Page 96: ...96 ...
Page 103: ...103 ...
Page 104: ......