035-000051-001
Page 37 of 60
MMD IOM 1.2 11-10-2020
SPECIAL INSTRUCTIONS—CONTROLS
■
Function code (DN code) setting
DN
Code
Items
Description
At shipment
01
Filter display de-
lay timer
0000 : None 0001 : 150H
0002 : 2500H 0003 : 5000H
0004 : 10000H
0000 : None
02
Dirty state of filter
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0000 : Standard
03
Central control
address
0001 : No.1 unit to 0064 : No.64 unit,
0099 : Unfixed
0099 : Unfixed
04
Specific indoor
unit priority
0000 : No priority 0001 : Priority
0000 : No priority
05
Constant fan
0001 : L tap during heating thermo-off
0012 : Fan tap by remote control set during heating
thermo-off
0001 : L tap
06
Heating temp.
shift
0000 : No shift 0001 : +1 (+1.8 )
0002 : +2 (+3.6 ) to 0010 : +10 (+18 )
(Up to +6 recommended)
0002 : +2
(+3.6 )
0d
Existence of
[AUTO] mode
0000 : Provided
0001 : not provided (Automatic selection from connect-
ed outdoor unit
0001 : Not provid-
ed
0E
FS unit connec-
tion set of multi-
ple indoor units
0000 : Standard (1 FS unit : 1 indoor unit)
0001 : Multiple unis connected ( 1 FS unit : Multiple
indoor units)
0000 : Standard
0F
Cooling only
0000 : heat pump
0001 : Cooling only (no display of [AUTO] [HEAT])
0000 : Heat pump
10
Model code
0029 : Vertical air handling unit
0029
12
Line (System)
address
0001: No.1 unit to 0030: No.30 unit
0099 : Unfixed
13
Indoor address
0001 : No.1 unit to 0064 : No.64 unit
0099 : Unfixed
14
Group address
0000 : Individual
0001 : Header unit of group
0002 : Follower unit of group
0099 : Unfixed
28
Automatic restart
of power failure
0000 : None
0001 : Restart
0001 : Restart
2E
HA terminal
(CN61) select
0000 : Usual 0001: Leaving-ON prevention control
0002 : Fire alarm input
0000 : Usual
(HA termi-
nal)
31
Ventilation fan
control
0000 : Unavailable
0001 : Available
0000 : Unavailable
32
Remote control
sensor
0000 : Body TA sensor
0001 : Remote control sensor
0000 : Body TA
sensor
33
Temperature unit
select
0000 : ̊C, 0001 : ̊F
0001 : ̊F
60
Timer setting
(wired remote
controller)
0000 : Available (Can be performed)
0001 : Unavailable (Cannot be performed)
0000 : Available
77
Dual set point
0000 : Unavailable 0002 : Available
0000 : Unavailable
FD
Priority operation
mode
(Flow selector
unit)
0000 : Heating 0001 : Cooling
0000 : Heating
92
Alarm clearance
condition
0000 : Operation stop
0001 : Release signal received
0000 : Operation
stop
9B
Setting of
“prevention of
cold air dis-
charge” control
0000 : Prevention control of cold air discharge “enable”
0001 : Prevention control of cold air discharge without
“Fan off” zone
0002 : Work in remote control setting fan speed.
(prevention control of cold air discharge
“disable”)
0000 : Enable
Summary of Contents for Carrier MMD-AP0180VHG2UL
Page 2: ...035 000051 001 Page 2 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 4: ...035 000051 001 Page 4 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 6: ...035 000051 001 Page 6 of 60 MMD IOM 1 2 11 10 2020 PRODUCT NOMENCLATURE ...
Page 27: ...035 000051 001 Page 27 of 60 MMD IOM 1 2 11 10 2020 AIRFLOW PERFORMANCE ...
Page 31: ...035 000051 001 Page 31 of 60 MMD IOM 1 2 11 10 2020 SPECIAL FACTORY OPTIONS ...
Page 42: ...035 000051 001 Page 42 of 60 MMD IOM 1 2 11 10 2020 SPECIAL INSTRUCTIONS CONTROLS ...
Page 43: ...035 000051 001 Page 43 of 60 MMD IOM 1 2 11 10 2020 SPECIAL INSTRUCTIONS CONTROLS ...
Page 46: ...035 000051 001 Page 46 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 47: ...035 000051 001 Page 47 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 48: ...035 000051 001 Page 48 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 49: ...035 000051 001 Page 49 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 50: ...035 000051 001 Page 50 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 51: ...035 000051 001 Page 51 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 52: ...035 000051 001 Page 52 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 53: ...035 000051 001 Page 53 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 54: ...035 000051 001 Page 54 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS ...
Page 55: ...035 000051 001 Page 55 of 60 MMD IOM 1 2 11 10 2020 REPLACEMENT PARTS 19 ...
Page 56: ...035 000051 001 Page 56 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...035 000051 001 Page 58 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 59: ...035 000051 001 Page 59 of 60 MMD IOM 1 2 11 10 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...