7. APPLIED CONTROL
7-1. Setup of Selecting Function in Indoor Unit
(Be Sure to Execute Setup by a Wired Remote Controller)
<Procedure>
Execute the setup operation while the unit stops.
1
Push
SET
,
CL
, and
TEST
buttons simultaneously for 4 seconds or more.
The firstly displayed unit No. indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
2
Every pushing
UNIT LOUVER
(left side button) button, the indoor unit numbers in the group control
3
Specify the CODE No. (DN) using the setup temperature
and
buttons.
4
Select the setup data using the timer time
and
buttons.
(When selecting the DN code to “33”, change the temperature indication of the unit from “°C”
to “°F” on the remote controller.)
5
Push
SET
button. (OK if display goes on.)
• To change the selected indoor unit, return to procedure
2
.
• To change the CODE No. to be set up, return to procedure
3
.
6
Pushing
TEST
button returns the status to normal stop status.
1
6
5
2
4
3
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
are successively displayed. In this time, the fan of the selected indoor unit only is turned on.
- 36 -