10
MMU-AP___2H2UL
E15-3C1
6.
Electrical current characteristics
MCA: Minimum Circuit Amps FLA: Full Load Amps
MOCP: Maximum Overcurrent Protection (Amps)
Type
Model
Nominal Voltage
(V-Ph-Hz)
Voltage Range
(V)
Power
consumption
FLA
MCA MOCP
Min
Max
kW
A
A
A
4-Way
Cassette
type
MMU-AP0072H2UL
208/230-1-60
187
253
0.021
0.6
0.8
15
MMU-AP0092H2UL
208/230-1-60
187
253
0.021
0.6
0.8
15
MMU-AP0122H2UL
208/230-1-60
187
253
0.023
0.6
0.8
15
MMU-AP0152H2UL
208/230-1-60
187
253
0.026
0.6
0.8
15
MMU-AP0182H2UL
208/230-1-60
187
253
0.026
0.6
0.8
15
MMU-AP0212H2UL
208/230-1-60
187
253
0.036
0.8
1.0
15
MMU-AP0242H2UL
208/230-1-60
187
253
0.036
0.8
1.0
15
MMU-AP0302H2UL
208/230-1-60
187
253
0.043
0.8
1.0
15
MMU-AP0362H2UL
208/230-1-60
187
253
0.088
1.0
1.3
15
MMU-AP0422H2UL
208/230-1-60
187
253
0.112
1.0
1.3
15
MMU-AP0072H2UL-1
208/230-1-60
187
253
0.023
0.6
0.8
15
+00E15-3C1_01EN.book Page 10 Thursday, March 24, 2016 11:25 AM