Test run
CAUTION
• Turn on the power and turn on the case heater of
the compressor.
To save the compressor when it is activated, leave
the power on for more than 12 hours.
■
Methods of test run
◆
A test run is executed by using a
remote control
Operate the system normally to check the running
condition using the wired remote control. Follow the
instructions in the supplied owner’s manual when
operating the unit.
If a wireless remote control is used for operations,
follow the instructions in the installation manual
supplied with the indoor unit.
To execute a test run forcibly under the condition that
the thermostat automatically turns the unit off due to
the indoor temperature, follow the procedure below.
The forcible test run will automatically stop after 60
minutes to prevent continuous forcible running and
return to normal running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
1
Push and hold the
TEST
button for more than
4 seconds. TEST appears on the LCD and
the unit enters the TEST mode.
TEST
2
Push
the
ON / OFF
button.
3
Push
the
MODE
button to switch the running
mode to COOL or HEAT.
NOTE
• Do not run the unit in any mode other than COOL or
HEAT.
• The temperature setting cannot be changed during
the test run.
• Check codes are detected as usual.
TEST
4
Push
the
ON / OFF
button to stop running
after
fi
nishing the trial run.
The indication on the LCD display returns
to the status of procedure 1.
5
Push
the
TEST
button to exit the test mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.)
<In case of connecting one group operation of
indoor units and two indoor units>
Single port type FS unit
Piping
Control wiring between
indoor unit and FS unit
(Within 49 ft (15 m))
Remote
control
Indoor unit
Indoor unit
Multi port type FS unit
Remote
control
[ 0E ] :
1
1
0
0
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
[ 0E ] :
1
1
0
0
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
Group control
Piping
Group control
<In case of connecting four indoor units>
Single port type FS unit
Piping
Control wiring between
indoor unit and FS unit
(Within 49 ft (15 m))
Remote control
Indoor unit
Indoor unit
Multi port type FS unit
Remote control
[ 0E ] :
0
0
0
0
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
[ 0E ] :
0
0
0
0
[ FE ] :
1
1
1
1
[ FD ] :
0
0
0
0
Piping
<Incorrect connection examples>
Incorrect
Incorrect
Incorrect
Incorrect
Piping
Control wiring
between indoor
unit and FS unit
(Within 49 ft (15 m))
Remote control
Indoor unit
Indoor
unit
Multi port type FS unit
Multi port type FS unit
Multi port type FS unit
Multi port type FS unit
Remote control
Remote control
Remote control
Group control
Piping
Group control
Single port type FS unit
Single port type
FS unit
Single port type FS unit
Piping
Piping
Indoor
unit
Group control
Group control
Indoor
unit