– 40 –
3-2) Heating fan control
c
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.
(Control from minimum W1 to maximum (according to the following table))
d
For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in
the following table is fixed and then the fan is controlled by temperature of TE sensor.
Object: RAV-SP300AT2-UL
Object: RAV-SP360AT2-UL, RAV-SP420AT2-UL
–2 taps / 20 sec. (Up to W1)
Stop timer count
+1 tap / 20 sec
(Up to the maximum tap of each zone)
–2 taps / 20 sec. (Up to W1)
–1 tap / 20 sec. (Up to W1)
Revolution frequency hold
TE
˚F (˚C)
75.2 (24)
69.8 (21)
64.4 (18)
59.0 (15)
e
When TE
≥
75.2°F (24°C) continues for
5 minutes, the compressor stops.
It is the same status as the normal
THERMO-OFF without error display.
The compressor restarts after approx.
2 minutes 30 seconds and this intermit-
tent operation is not abnormal.
f
In case that the status in item
e
generates frequently, stain on filter of
the suction part of the indoor unit is
considered. Clean the filter and then
restart the operation.
Object: RAV-SP240AT2-UL
Temp. range
50°F (10°C)
≤
TO
41°F (5°C)
≤
TO < 50°F (10°C)
26.6°F (–3°C)
≤
TO < 41°F (5°C)
14°F (–10°C)
≤
TO < 26.6°F (–3°C)
TO < 14°F (–10°C)
TO error
20 Hz or lower
20Hz to 45Hz
45Hz or higher
Max.
Max.
Max.
W7
W8
W9
W9
WA
WB
WB
WB
WC
WC
WC
WC
WD
WD
WD
WD
WD
WD
Temp. range
50°F (10°C)
≤
TO
41°F (5°C)
≤
TO < 50°F (10°C)
26.6°F (–3°C)
≤
TO < 41°F (5°C)
14°F (–10°C)
≤
TO < 26.6°F (–3°C)
TO < 14°F (–10°C)
TO error
20 Hz or lower
20Hz to 45Hz
45Hz or higher
Max.
Max.
Max.
W7
W8
W9
W9
WA
WA
WA
WA
WB
WB
WB
WB
WD
WD
WD
WD
WD
WD
Temp. range
50°F (10°C)
≤
TO
41°F (5°C)
≤
TO < 50°F (10°C)
26.6°F (–3°C)
≤
TO < 41°F (5°C)
14°F (–10°C)
≤
TO < 26.6°F (–3°C)
TO < 14°F (–10°C)
TO error
20 Hz or lower
20Hz to 45Hz
45Hz or higher
Max.
Max.
Max.
W7
W8
W9
W9
WB
WD
WD
WD
WE
WE
WE
WE
WF
WF
WF
WF
WF
WF
Summary of Contents for CARRIER RAV-SP180AT2-UL
Page 12: ... 12 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 Outdoor Unit RAV SP180AT2 UL ...
Page 13: ... 13 RAV SP240AT2 UL ...
Page 14: ... 14 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...
Page 107: ... 107 12 EXPLODED VIEWS AND PARTS LIST 12 1 Outdoor Unit 12 1 1 RAV SP180AT2 UL ...
Page 110: ... 110 12 1 2 RAV SP240AT2 UL ...
Page 113: ... 113 12 1 3 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...