– 48 –
⎫
⎪
⎬
⎪
⎭
Lamp indication
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Simultaneous flash
Operation Timer
Ready
Simultaneous flash
Check code
F01
F02
F10
F04
F06
F07
F08
F12
F13
F15
F29
F31
H01
H02
H03
H04
H06
L03
L07
L08
L09
L10
L20
L29
L30
L31
Cause of trouble occurrence
Heat exchanger sensor (TCJ) error
Heat exchanger sensor (TC) error
Indoor unit sensor error
Heat exchanger sensor (TA) error
Discharge temp. sensor (TD) error
Temp. sensor (TE) error
Temp. sensor (TL) error
Temp. sensor (TO) error
Sensor error of outdoor unit
Temp. sensor (TS) error
Temp. sensor (TH) error
Temp. Sensor miswiring (TE, TS)
Indoor EEPROM error
Outdoor EEPROM error
Compressor break down
Compressor lock
Outdoor compressor system error
Current detection circuit error
Case thermostat worked.
Outdoor unit low pressure system error
Duplicated header indoor units
There is indoor unit of group connection
→
AUTO address
in individual indoor unit.
∗
If group construction and
Unsetting of group address
address are not normal
Missed setting
when power supply turned on,
(Unset indoor capacity)
automatically goes to address
setup mode.
Unset model type (Service board)
Duplicated indoor central addresses
Outdoor unit and other error
Others
Outside interlock error
Negative phase error
⎫
⎪
⎪
⎪
⎪
⎪
⎪
⎬
⎪
⎪
⎪
⎪
⎪
⎪
⎭
⎫
⎪
⎪
⎬
⎪
⎪
⎭
⎫
⎪
⎪
⎪
⎪
⎬
⎪
⎪
⎪
⎪
⎭
⎫
⎪
⎪
⎬
⎪
⎪
⎭
Revised : Feb. 2010
Summary of Contents for CARRIER RAV-SP180AT2-UL
Page 12: ... 12 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 Outdoor Unit RAV SP180AT2 UL ...
Page 13: ... 13 RAV SP240AT2 UL ...
Page 14: ... 14 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...
Page 107: ... 107 12 EXPLODED VIEWS AND PARTS LIST 12 1 Outdoor Unit 12 1 1 RAV SP180AT2 UL ...
Page 110: ... 110 12 1 2 RAV SP240AT2 UL ...
Page 113: ... 113 12 1 3 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...