– 64 –
Check crushed or broken pipe.
Defect
→
Correct and Replace
Correct defective position.
Replace defective part.
Open valve fully.
Repair defectives position.
Recharge refrigerant.
Check outdoor P.C. board.
Defect
→
Replace
Correct connector.
Case thermostat error
→
Replace
Cut jumper line according
to the explanation sheet packaged
with the service P.C. board.
Is valve fully opened?
Is PMV normal?
Is there no gas leak?
Is it not refrigerant shortage?
Are CN609 connection
and case thermostat normal?
Is cooling/heating operation
available when short-circuiting
case thermostat?
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
CODE
No.
[H04]
[L10]
Outdoor
LED display
<Display 1> <Display 2>
z
z
z
z
{
z
z
{
z
{
{
<Display 1> <Display 2>
z
z
{
{
z
z
{
z
{
{
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Case thermostat operation]
[Unset model type]:
Only when service P.C. board is used
<Display 1> <Display 2>
z
{
z
{
z
{
{
{
<Display 1> <Display 2>
{
{
{
z
z
{
z
{
{
[Communication error between MCU]
[Heat sink temp. sensor (TH) error]
→
Refer to
[F13]
column.
∗
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is.
Communication error between MCU, Heat sing temp. sensor (TH) error, EEPROM error,
Unset model type, Heat sink overheat error, Gas leak detection, 4-way valve inverse error
[L29]
Check outdoor P.C. board.
Defect
→
Replace
Summary of Contents for CARRIER RAV-SP180AT2-UL
Page 12: ... 12 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 Outdoor Unit RAV SP180AT2 UL ...
Page 13: ... 13 RAV SP240AT2 UL ...
Page 14: ... 14 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...
Page 107: ... 107 12 EXPLODED VIEWS AND PARTS LIST 12 1 Outdoor Unit 12 1 1 RAV SP180AT2 UL ...
Page 110: ... 110 12 1 2 RAV SP240AT2 UL ...
Page 113: ... 113 12 1 3 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...