6F9G0154
(2) Mechanical service life
The normally energized type has the mechanical service life of 0.25 million operations ,
and the latch type 0.25 million operations. (The mechanical service life of the vacuum
interrupter is 100,000 operations.)
For the components listed below , replacement or detailed inspection and cleaning are
recommended after the indicated number of operations.
Table 9 Recommended replacement parts
Parts name
No. of operation for replacement
Vacuum interrupter
100,000 operations or 15 years
Auxiliary switch
100,000 operations or 10 years
Movable conductor
100,000 operations or 15 years
Latch mechanism
250,000 operations or 10 years
Closing/trip coil
250,000 operations
Movable core
Detailed inspection and cleaning
every 100,000 operations.
Stationary core
Detailed inspection and cleaning
every 100,000 operations.