DeviceNet Module Installation and Operation Manual
13
1 – Preset Speed operation can be performed at up to 15 different frequencies (Preset Speed operation
frequencies #1 to #15) specified by combining Preset Speed bit 1 thru Preset Speed bit 4. To per-
form Preset Speed operation, the Command Link bit and the Run/Stop bit must be set to 1.
Example: To run the motor in the reverse direction at Preset Speed operation frequency #7
10000110 00000111 = 0x8607 (Hex).
If one of the bits for Preset Speed #1 through Preset Speed #4 is set to 1, priority is given to Preset
Speed operation even though the Frequency Link bit is set to 1.
2 – Jog operation overrides Preset Speed operation when the Jog frequency is higher.
Received Jog
commands are ignored when the Jog frequency is lower than the Preset Speed Frequency.
Table 7. Data Composition of Output Instance 150.
0
7
DC Braking
Off
Forced DC
Braking
If “1” is specified, some units may dis-
play “db”
1
0
Jog Run 2
Off
Jog Run
If “1” is specified operation is performed
at the frequency specified with F260 (Jog
Run Frequency)
1
1
Forward Run/
Reverse Run
Forward Run
Reverse Run
-
1
2
Run/Stop
Stop
Run
-
1
3
Coast to Stop
Ready for
Operation
Coast to Stop
-
1
4
Emergency Off
Off
Emergency Off
If “1” is specified
error
tripping can
occur
1
5
Reset
Off
Reset
Enabled only in the event of tripping
1
6
Frequency Link
Off
Priority
Enabled: Overrides the setting of F004
1
7
Command Link
Off
Priority
Enabled: Overrides the setting of F003
Byte
Bit
Specifications
0
1
Supplement
0
0
Fault FL
No Output
Output
-
0
1
Fault
No Trip
Tripped
Both the F301 status and the trip reten-
tion status are both regarded as a
tripped status
0
2
Alarm
No Alarm
Alarm Issued
-
0
3
(Reserved)
-
-
-
0
4
Motor #1/#2
(THR1/2 selection)
Motor #1
(THR1)
Motor #2
(THR2)
Indicates the motor electronic-
thermal protection level selected
0: Protection level #1 (F600)
1: Protection level #2 (F173)
0
5
PI Control
PI Control
Permission
PI Control
Prohibition
-
0
6
Acceleration/Deceleration
#1/#2 Selection
Acceleration/
Deceleration
#1 (AD1)
Acceleration/
Deceleration
#2 (AD2)
Indicates the acceleration/
deceleration time selected
0: F009 (Accel ), F010 (Decel )
1: F500, F501
0
7
DC Braking
Off
Forced DC
Braking
-
1
0
Jog run
Off
Jog Run
-
1
1
Forward Run/Reverse Run Forward Run
Reverse Run
-
Byte
Bit
Specifications
0
1
Supplement
Summary of Contents for DEV002Z