DeviceNet Module Installation and Operation Manual
FE36 — Analog Input Value V/I
Read the V/I terminal input.
The value range is 0x0000 – 0x2710 (0 – 100.00%).
FE37 — RX Input
Read the RX terminal.
The value range is 0xD8F0 – 0x2710 (-100.00 – +100.00%).
FE60 to FE63 — My Function Monitor (1 – 4)
Refer to the My Function Instruction Manual (Document No. 58692).
FE14 — Cumulative Run Time
The cumulative power-on run time in hours, counted in Hex.
For example, when the cumulative run time reads, 0x12, the decimal equivalent run time is 18 hours.
0x12 (Hex) = 18 (Decimal).
FE40 — Analog Output (FM)
Read the output value of the FM terminal.
The value range is 0 – 65535 (0xFFFF).
FE41 — Analog Output (AM)
Read the output value of the AM terminal.
The value range is 0 – 65535 (0xFFFF).
FC91 — Alarm Code
Bit
Function
0
1
Note
0
Over Current Alarm
Normal
Active alarm
“
C
” blinking
1
ASD Overload Alarm
Normal
Active alarm
“
L
” blinking
2
Motor Overload Alarm
Normal
Active alarm
“
L
” blinking
3
Over Heat Alarm
Normal
Active alarm
“
H
” blinking
4
Over Voltage Alarm
Normal
Active alarm
“
P
” blinking
5
Under Voltage of Main Power
Normal
Active alarm
-
6
(Reserved)
-
-
-
7
Under Current Alarm
Normal
Active alarm
-
8
Over Torque Alarm
Normal
Active alarm
-
9
Dynamic Braking Resistor Overload Alarm
Normal
Active alarm
-
10
Cumulative Run-Time Alarm
Normal
Active alarm
-
11
(Reserved)
-
-
-
12
(Reserved) -
-
-
13
(Reserved)
-
-
-