12
DeviceNet Module Installation and Operation Manual
Example: F830 = 2 (Instance 100/150)
Table 4. Output Instance 100 Format.
1 – Drive Reference Speed command value.
Frequency is specified in Hex notation with a resolution of of 0.01 Hz per unit.
Example: Set the frequency to 60 Hz. With the incremental frequency of 0.01 Hz per unit, the
corresponding entry is calculated as:
60 Hz ÷ 0.01 Hz/unit = 6000 units, or 0x1770 (Hex).
Table 5. Output Instance 150 Format.
Table 6. Data Composition of Output Instance 100.
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0
DC Braking
Acc/Dec
#1/#2
PI Control
Motor #1/#2
Preset Speed
4
Preset Speed
3
Preset Speed
2
Preset Speed
1
1
Command
Link
Frequency
Link
Reset Trip
Emergency
Off
Coast to Stop
(ST)
Run/Stop
Forward/
Reverse
Jog
2
Drive Reference Speed Hz (Low byte)
1
3
Drive Reference Speed Hz (High byte)
1
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0
DC Braking
Acc/Dec
#1/#2
PI Control
Motor #1/#2
(Reserved)
Alarm
(FC91)
Fault
Fault FL
1
(Reserved)
Ready
without
ST/Run
Ready
with
ST/Run
Emergency
Off
Coast to Stop
(ST)
Run/Stop
Forward/
Reverse
Jog
2
Drive Speed Hz (Low byte)
3
Drive Speed Hz (High byte)
Byte
Bit
Specifications
0
1
Supplement
0
0
Preset Speed #1 1
Preset Speed: 0000 = Off
Preset Speed 0001 to 1111 = #1– #15
The combination of 4 bits is used to
select a Preset Speed from: speed
operation Off, and Preset Speeds #1 to
#15.
0
1
Preset Speed #2 1
0
2
Preset Speed #3 1
0
3
Preset Speed #4 1
0
4
Motor #1/#2
(THR2 Selection)
Motor #1
(THR1)
Motor #2
(THR2)
Used to select a motor electronic-
thermal protection level
0: Protection Level #1 (F600)
1: Protection Level #2 (F173)
0
5
PI Control
Normal Operation
PI Control Off
-
0
6
Acceleration/
Deceleration #1/#2
Selection
Acceleration/
Deceleration #1
(AD1)
Acceleration/
Deceleration #2
(AD2)
Used to select Acceleration/
Deceleration time
0: F009, F010
1: F500, F501