DeviceNet Module Installation and Operation Manual
Instance 100/150
Toshiba Specific data. (4 bytes, parameter F830 = 2)
Table 33. Output Instance 100 Layout.
1 – Bit 14 and 15 of the instance 100 byte 0 are defined as follows.
Bit 14 (Frequency link) — When set to 1, bytes two and three are enabled. When set to 0, Drive
Reference Speed is set to ASD parameter F004
.
Bit 15 (Command link) — When set to 0, the other command does not work except bits 12 and 13,
Run/Stop is according to setup of the ASD parameter F003.
2 – Drive Reference Frequency is specified in Hex notation in increments of 0.01 Hz per unit.
Example: Set the frequency to 60 Hz. With the incremental frequency resolution of 0.01 Hz per
unit, the corresponding entry is calculated as: 60 Hz ÷ 0.01 Hz/unit = 6000 units = 0x1770.
Table 34. Input Instance 150 Layout.
Examples of Instance 100/150
Table 35. Instance 100/150 – Stop.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
DC Braking
Accel 1/
Accel 2
PI Off
THR2
Preset
Speed4
Preset
Speed3
Preset
Speed2
Preset
Speed1
1
Command
Link
1
Frequency
Link
1
Reset
trip
Emergency
Off
Coast
(ST)
Run/Stop
Forward/
Reverse
Jog
2
Drive Reference Speed Hz (Low byte)
2
3
Drive Reference Speed Hz (High byte)
2
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
DC Braking
Accel 1/
Accel 2
PI Off
THR2
(VF2+tH2)
-
ALARM
(FC91)
Emg. FL
-
1
-
Ready
without
ST/Run
Ready with
ST/Run
Emergency
Off
Coast
(ST)
Run/Stop
Forward/
Reverse
Jog
2
Drive Speed Hz (Low byte)
3
Drive Speed Hz (High byte)
Instance
Byte
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Hex
Output
Instance 100
1, 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0x0000
3, 2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Input
Instance 150
1, 0
0
1
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0x4800
3, 2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0x0000
Summary of Contents for DEV002Z
Page 1: ...Installation and Operation Manual ASD OPTIONAL DEVICENET MODULE ...
Page 2: ......
Page 55: ......