DeviceNet Module Installation and Operation Manual
31
FA23 — Command Word 2 from Internal Option PCB
FA07 — Frequency Reference from Internal Option PCB
The Frequency reference is stored as a Hex number in unit increments of 0.01 Hz/unit.
For example, when Frequency reference is set to 80 Hz, it is converted as follows:
80 (Hz)/0.01 (Hz/unit) = 8000 (units) or 0x1F40 (Hex).
9
Forward/Reverse
Forward
Reverse
-
10
Run/Stop
Stop
Run
-
11
Coast (ST)
Coast
-
12
Emergency Off
Off
Emergency Off
Recommend this bit always be Enabled
13
Reset Trip
Off
Reset
-
14
Frequency Link
Off
Priority
When Enabled, this overrides the
parameter F004
15
Command Link
Off
Priority
When Enabled, this overrides the
parameter F003
Bit
Function
0
1
Note
0
Speed/Torque
Speed Control
Torque Control
-
1
Clear kWh
Off
Clear
Clear the value of FE76, FE77
2
(Reserved)
-
-
-
3
Brake Close (BC)
Normal
Forced Close
-
4
Pre-Magnetic
Normal
On
-
5
Brake Open (B)
Brake Close
Brake Open
-
6
Brake Answer (BA)
Brake Close
Brake Open
-
7
Fast Stop
Normal
On
-
8
Accel 1/Accel 2
00: Acc./Dec. 1
01: Acc./Dec. 2
10: Acc./Dec. 3
11: Acc./Dec. 4
Combination of 2 bits:
AD1: F009, F010
AD2: F500, F501
AD3: F510, F511
AD3: F514, F515
9
Accel 3/Accel 4
10
THR 1/2
00: V/f 1
01: V/f 2
10: V/f 3
11: V/f 4
Combination of 2 bits
11
THR 3/4
12
Torque Limit 1/2
00: Torque limit 1
01: Torque limit 2
10: Torque limit 3
11: Torque limit 4
Combination of 2 bits
13
Torque Limit 3/4
14
Speed Gain 1/2
Gain 1
Gain 2
Gain 1: F460, F461
Gain 2: F462, F463
15
(Reserved) - -
-
Bit
Function
0
1
Note