DeviceNet Module Installation and Operation Manual
41
Table 59. Control Supervisor Object Common Services.
Control Supervisor Object Specific Services.
The Control Supervisor Object provides no object specific services.
5
Net Control
BOOL
Get/Set
Requests Run/Stop control to be local or
from network
0 = Local Control
1 = Network Control
Note that the status of Run/Stop control is
reflected in attribute 15, CtrlFromNet
-
6
State
USINT
Get
0 = Vendor Specific
1 = Startup
2 = Not_Ready
3 = Ready
4 = Enabled
5 = Stopping
6 = Fault_Stop
7 = Faulted
-
7
Running 1
BOOL
Get
1 = (Enabled and Run1)
OR (Stopping and Running1)
OR (Fault_Stop and Running1)
0 = Other state
-
8
Running 2
BOOL
Get
1 = (Enabled and Run2)
OR (Stopping and Running2)
OR (Fault_Stop and Running2)
0 = Other state
-
9
Ready
BOOL
Get
1 = Ready
OR Enabled
OR Stopping
0 = Other state
-
10
Faulted
BOOL
Get
1 = Fault Occurred (latched)
0 = No Faults present
-
11
Warning
BOOL
Get
1 = Warning (not latched)
0 = No Warnings present
-
12
Fault Reset
BOOL
Get/Set
0
→
1 = Fault Reset
0 = No action
-
15
Control From Net
USINT
Get
Status of Run/Stop control source.
0 = Control is local
1 = Control is from network
-
Service
Code
Service Name
Supported
Class
Supported
Instance
Description of Service
0x05
Reset
N/A
Yes
Used to reset all resettable connection objects
0x0E
Get_Attribute_Single
N/A
Yes
Returns the contents of the specified attribute
0x10
Set_Attribute_Single
N/A
Yes
Modifies the value of the specified attribute
Attribute
ID
Name
Data
Type
Access
Rules
Description
Default
Value
Summary of Contents for DEV002Z
Page 1: ...Installation and Operation Manual ASD OPTIONAL DEVICENET MODULE ...
Page 2: ......