33
11.2
11.2
11.2
11.2 Read/Write Registers
Read/Write Registers
Read/Write Registers
Read/Write Registers
11.2.1
11.2.1
11.2.1
11.2.1 GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
GROUP:FUNDAMENTAL PARAMETERS #1
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
26
MAXIMUM OUTPUT
FREQUENCY
(
∗∗∗∗
)
0 / 1
FFFF
0BB8
∼
9C40 (30.00
∼
400.00)
0.01
27
BASE FREQUENCY #1
0 / 1
FFFF
09C4
∼
9C40 (25.00
∼
400.00)
0.01
28
BASE FREQUENCY
VOLTAGE SELECT
(
∗∗∗∗
)
0 / 1
0030
0000: Input voltage level
(0)
0020: Automatic setting
(1)
0030: Stationary setting
(2)
29
MAXIMUM OUTPUT
VOLTAGE #1
0 / 1
FFFF
0000
∼
0258 (0
∼
600)
1
2A
REVERSE OPERATION
DISABLE SELECT
0 / 1
0020
0000: Reverse allowed
(0)
0020: Reverse not allowed
(1)
2B
UPPER LIMIT FREQUENCY
0 / 1
FFFF
0000 ~ Fmax
0.01
2C
LOWER LIMIT FREQUENCY
0 / 1
FFFF
0000
∼
UL, Fmax
0.01
2D
VOLTS PER HERTZ
PATTERN
(
∗∗∗∗
)
0 / 1
000F
0000: Constant torque
(1)
0001: Variable torque
(2)
0002: Auto. torque boost
(3)
0006: #3 w/ auto. energy savings (4)
000A: Vector control
(5)
000E: #5 w/ auto. energy savings (6)
2E 1,
2
VOLTAGE BOOST #1
0 / 1
FFFF
0000
∼
012C (0.0
∼
30.0)
0.1
2F
ACCELERATION TIME #1
0 / 1
FFFF
0001
∼
EA60 (0.01~ 600.00)
0001
∼
EA60 (0.1~ 6000.0)
0.01
0.1
30
DECELERATION TIME #1
0 / 1
FFFF
0001
∼
EA60 (0.01~ 600.00)
0001
∼
EA60 (0.1~ 6000.0)
0.01
0.1
31
ACC/DEC PATTERN #1
SELECTION
0 / 1
0030
0000: Linear
(0)
0010: Self-adjusting
(1)
0020: S-Pattern #1
(2)
0030: S-Pattern #2
(3)
32
ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1
00FF
0003 ~ 00FD (0
∼
50)
(Note 1)
1
33
ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1
00FF
0003 ~ 00FD (0
∼
50)
(Note 1)
1
Note 1:
Register data = (desired setting x 5 + 3), converted to hexadecimal