43
11.2.7
11.2.7
11.2.7
11.2.7 GROUP:PROTECTION FUNCTION PARAMETERS
GROUP:PROTECTION FUNCTION PARAMETERS
GROUP:PROTECTION FUNCTION PARAMETERS
GROUP:PROTECTION FUNCTION PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
11F
DYNAMIC BRAKING
SELECTION
0 / 1
0003
0000: no dynamic braking
(0)
0001: with dynamic braking, no DBR
overload trip
(1)
0003: with dynamic braking and
DBR overload trip
(2)
120 2
BRAKING RESISTOR
VALUE
0 / 1
FFFF
000A
∼
2710 (1.0
∼
1000)
0.1
121
BRAKING RESISTOR
POWER RATING
0 / 1
FFFF
0001
∼
EA60 (0.01
∼
600.00)
0.01
122
OVERVOLTAGE STALL
PROTECTION
0 / 1
0004
0000: ON
(0)
0004: OFF
(1)
123
DC INJECTION START
FREQUENCY
0 / 1
FFFF
0000
∼
2EE0 (0.00
∼
120.00)
0.01
124 Other
than 0
DC INJECTION
CURRENT
MAGNITUDE
0 / 1
00FF
0000
∼
0064 (0
∼
100)
1
125
DC INJECTION
TIME
0 / 1
00FF
0000
∼
0064 (0.0
∼
10.0)
0.1
126
FWD/REV DC INJECTION
PRIORITY CTRL
0 / 1
0040
0000: OFF
(0)
0040: ON
(1)
127
MOTOR SHAFT
STATIONARY CTRL
0 / 1
0080
0000: OFF
(0)
0080: ON
(1)
128
EMERGENCY OFF MODE
SELECTION
0 / 1
0030
0000: Coast stop
(0)
0010: Decelerated stop
(1)
0020: DC injection stop
(2)
129 2
EMERGENCY OFF DC
INJECTION TIME
0 / 1
00FF
0000
∼
0064 (0.0
∼
10.0)
0.1
12A
NUMBER OF RETRY
ATTEMPTS
0 / 1
00FF
0000
∼
000A (0
∼
10)
1
12B Other
than 0
TIME BETWEEN
RETRY ATTEMPTS
0 / 1
00FF
0000
∼
0064 (0.0
∼
10.0)
0.1
12C
REGENERATION POWER
RIDE-THROUGH
0 / 1
0008
0000: OFF
(0)
0008: ON
(1)
12D 1
REGENERATION
RIDE-THROUGH TIME
0 / 1
00FF
0000
∼
00FA (0.0
∼
25.0)
0.1
12E
AUTO-RESTART (MOTOR
SPEED SEARCH)
0 / 1
0018
0000: OFF
(0)
0008: On power failure
(1)
0010: On ST make/break
(2)
0018: Both (1) and (2)
(3)
12F
ELECTRONIC THERMAL
PROTECT LVL #1
0 / 1
00FF
000A
∼
0064 (10
∼
100)
1
130
OVERLOAD REDUCTION
START FREQ
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
131
MOTOR 150% OVERLOAD
TIME LIMIT
0 / 1
00FF
0001
∼
00F0 (10
∼
2400)
10
132
OVERLOAD SELECTION
0 / 1
0030
0000: with motor overload trip,
without soft-stall
(0)
0010: with motor overload trip and
soft-stall (1)
0020: without soft-stall or motor
overload trip
(2)
0030: with soft-stall, without motor
overload trip
(3)
133
STALL PROTECTION
ENABLE
0 / 1
0040
0000: ON
(0)
0040: OFF
(1)
134 0
STALL PROTECTION
CURRENT LEVEL
0 / 1
00FF
000A
∼
00D7 (10
∼
215)
1