50
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
211
TOSLINE-S20 COMM
ERROR MODE
1
0002
0000: Data cleared
(0)
0002: Data retained
(1)
1
212
TOSLINE-S20 COMM
OPTION RESET
1
0004
0000: No effect
(0)
0004: Reset
(1)
1
213
RS485/12-BIT BINARY
BIAS,GAIN
0 / 1
0020
0000: OFF
(0)
0020: ON
(1)
214 1
RS485/12-BIT
BINARY POINT #1
0 / 1
00FF
0000
∼
0064 (0
∼
100)
1
215
RS485/12-BIT
BINARY PT. #1
FREQ
0 / 1
FFFF
0000
∼
Fmax (0
∼
Fmax)
0.01
216
RS485/12-BIT
BINARY POINT #2
0 / 1
00FF
0000
∼
0064 (0
∼
100)
1
217
RS485/12-BIT
BINARY PT. #2
FREQ
0 / 1
FFFF
0000
∼
Fmax (0
∼
Fmax)
0.01
11.2.11
11.2.11
11.2.11
11.2.11 GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
GROUP:AM/FM TERMINAL ADJUSTMENT PARAMS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
218
FM TERMINAL FUNCTION
SELECTION
0 / 1
FFFF
1194: Pre-comp ref. frequency
(0)
6686: Post-comp output freq.
(1)
1500: Frequency setting
(2)
2576: Output current
(3)
2689: DC voltage
(4)
5668: Output voltage
(5)
3684: Torque current
(6)
2688: Excitation current
(7)
7506: PID feedback value
(8)
0584: Motor overload ratio
(9)
0586: Inverter overload ratio
(10)
0588: DBR overload ratio
(11)
835C: Input power
(12)
835E: Output power
(13)
A000: Fixed output
(14)
2304: Peak output current
(15)
8302: Peak input voltage
(16)
219
FREQUENCY METER
ADJUSTMENT
0 / 1
FFFF
0000
∼
FFFF
1
21A
AM TERMINAL FUNCTION
SELECTION
0 / 1
FFFF
Same as
FM TERMINAL FUNCTION
SELECTION
21B
CURRENT METER
ADJUSTMENT
0 / 1
FFFF
0000
∼
FFFF
1
Summary of Contents for G3 TOSVERT-130
Page 60: ...59 13 13 13 13 Notes Notes Notes Notes ...
Page 61: ...60 ...