GRD150
4
FUNCTIONS
Protection
- 4-stage non-directional and directional overcurrent
and earth-fault protection and sensitive earth fault
protection (option)
1
st
and 2
nd
stage: Instantaneous, IDMTL or DTL
3
rd
and 4
th
stage: Instantaneous or DTL
- 2-stage non-directional and directional negative
phase sequence overcurrent protection
1
st
stage: Instantaneous, IDMTL or DTL
2
nd
stage: Instantaneous or DTL
- 2-stage overvoltage and undervoltage protection
1
st
stage: Instantaneous, IDMTL or DTL
2
nd
stage: Instantaneous or DTL
- 6-stage underfrequency or overfrequency protection
- Thermal overload protection
- Cold load protection function or Inrush current (2
nd
harmonic) detector provided for energising the
system
- Undercurrent protection
- Broken conductor detection
- Circuit breaker failure protection
- Autoreclose function: 5-shots, 3-phase autoreclose
(option)
Control
Two-stepped operation (select-control) is used for the
control procedure of circuit breakers, disconnectors,
earthing disconnector switches and transformers to
ensure highly reliable operation.
- Control of circuit breakers, disconnectors and
earthing disconnector switches
- Interlock check
- Synchronism check for circuit breaker closing
(option)
- MIMIC configuration picture displayed on LCD
- Double command blocking
- Switchgear operation counter
- Control blocking
Password protection is provided to operate above
functions.
Monitoring and Metering
- Status monitoring of switchgear devices and failure
monitoring of power apparatus, control equipment,
protection relays and ancillary equipment
- Metering: current, voltage, frequency, active power,
reactive power and max. demand values
An energy calculation (Watt-hour, var-hour) is also
available.
- Limit value checking of metering
- Opening and closing time monitoring
These data are available on the HMI and at a local or
remote PC.
Recording
- Event records: The most recent 480 time-tagged
events with 1ms resolution are stored.
- Alarm records: The most recent 32 time-tagged
alarms with 1ms resolution are stored.
- Fault records: The most recent 8 time-tagged faults
with 1ms resolution are stored.
- Disturbance records: GRD150 can record 9 analog
and 32 binary signals, initiated by relay tripping. Pre-
trigger and post-trigger recording times can be set,
and the maximum number of records which can be
stored is dependent on the recording times chosen.
These records are available on the HMI and at a local
or remote PC.