6 F 2 T 0 1 7 2
No.
SIGNAL Name
Contents
181
LCD IND.
LCD indication (Virtual LED) command
182
LCD IND1.
LCD indication1 (Virtual LED) command
183
LCD IND2.
LCD indication2 (Virtual LED) command
184
SEF1 PICKUP
SEF1 pick-up
185
SEF2 PICKUP
SEF2 pick-up
186
TESTING
Testing LED lit output
187
CBF OP-A
CBF start or external trip input signal (A phase)
188
CBF OP-B
CBF start or external trip input signal (B phase)
189
CBF OP-C
CBF start or external trip input signal (C phase)
190
GEN_PICKUP
General start / pick-up
191
Not in use
192
Not in use
193
PROT_COM_ON
IEC103 protection command
194
IECTST
IEC103 communication test
195
IECBLK
IEC013 communication block
196
NORM_LED_ON
IN_SERVICE LED ON
197
TRIP_LED_ON
TRIP LED ON
198
Not in use
199
Not in use
200
Not in use
201
BI1 COMMAND1
Binary Input signal of BI1 after BI1SNS
202
BI2 COMMAND1
Binary Input signal of BI2 after BI2SNS
203
BI3 COMMAND1
Binary Input signal of BI3 after BI3SNS
204
BI4 COMMAND1
Binary Input signal of BI4 after BI4SNS
205
BI5 COMMAND1
Binary Input signal of BI5 after BI5SNS
206
BI6 COMMAND1
Binary Input signal of BI6 after BI6SNS
207
Not in use
208
Not in use
209
Not in use
210
ARC_BLK_OR
Auto-Reclosing block
211
ARC_READY_T
Auto-Reclosing ready condition
212
ARC_IN-PROG
Auto-Reclosing in-progress conditon
213
ARC_SHOT
Auto-Reclosing shot
214
ARC_SHOT1
Auto-Reclosing shot of number1
215
ARC_SHOT2
Auto-Reclosing shot of number2
216
ARC_SHOT3
Auto-Reclosing shot of number3
217
ARC_SHOT4
Auto-Reclosing shot of number4
218
ARC_SHOT5
Auto-Reclosing shot of number5
219
ARC_FT
Auto-Reclosing failed (Final trip)
220
ARC_SUCCESS
Auto-Reclosing succeed
221
ARC_COM_ON
IEC103 communication command
222
ARC_COM_RECV
Auto-recloser inactivate command received
223
Not in use
224
Not in use
225
ETH1_LINKUP
Ether port 1 LINK-UP
226
ETH2_LINKUP
Ether port 2 LINK-UP
189
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...