6 F 2 T 0 1 7 2
Test
Standards
Details
Electromagnetic Environment
High Frequency
Disturbance / Damped
Oscillatory Wave
IEC 60255-22-1 Class 3,
IEC 61000-4-12
IEEE C37.90.1
1MHz 2.5kV to 3kV (peak) applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
Electrostatic
Discharge
IEC 60255-22-2 Class 3,
IEC 61000-4-2
6kV contact discharge, 8kV air discharge.
Radiated RF
Electromagnetic
Disturbance
IEC 60255-22-3 Class 3,
IEC 61000-4-3
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
900 and 1890MHz.
Fast Transient
Disturbance
IEC 60255-22-4 Class A,
IEC 61000-4-4,
IEEE C37.90.1
4kV, 2.5kHz, 5/50ns applied to all inputs.
Surge Immunity
IEC 60255-22-5,
IEC 61000-4-5
1.2/50
µ
s surge in common/differential modes:
HV, Power Supply Unit and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF
Electromagnetic
Disturbance
IEC 60255-22-6 Class 3,
IEC 61000-4-6
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
Power Frequency
Disturbance
IEC 60255-22-7 Class A,
IEC 61000-4-16
300V 50Hz for 10s applied to ports in common mode.
150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted and
Radiated Emissions
IEC 60255-25,
EN 55022 Class A,
IEC 61000-6-4
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 10m):
30 to 230MHz: <40dB
230 to 1000MHz: <47dB
European Commission Directives
89/336/EEC
Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to generic
EMC standards EN 61000-6-2 and EN 61000-6-4.
73/23/EEC
Compliance with the European Commission Low Voltage
Directive is demonstrated according to product safety standard
EN 60255-27.
256
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...