6 F 2 T 0 1 7 2
INF
Description
Contents
GI
Type
ID
COT
FUN
IECI1 User specified 1
Signal specified by IECE1: ON (*1)
IECG1
(yes/no)
2
1, 7
160
IECI2 User specified 2
Signal specified by IECE2: ON (*1)
IECG2
(yes/no)
2
1, 7
160
IECI3 User specified 3
Signal specified by IECE3: ON (*1)
IECG3
(yes/no)
2
1, 7
160
IECI4 User specified 4
Signal specified by IECE4: ON (*1)
IECG4
(yes/no)
2
1, 7
160
IECI5 User specified 5
Signal specified by IECE5: ON (*1)
IECG5
(yes/no)
2
1, 7
160
IECI6 User specified 6
Signal specified by IECE6: ON (*1)
IECG6
(yes/no)
2
1, 7
160
IECI7 User specified 7
Signal specified by IECE7: ON (*1)
IECG7
(yes/no)
2
1, 7
160
IECI8 User specified 8
Signal specified by IECE8: ON (*1)
IECG8
(yes/no)
2
1, 7
160
Measurands(*3)
144
Measurand I
<meaurand I>
--
3.1
2, 7
160
145
Measurand I,V
Ib measurand <meaurand I>
--
3.2
2, 7
160
146
Measurand I,V,P,Q
Ib measurand <meaurand I>
--
3.3
2, 7
160
147
Measurand IN,VEN
Ie, Io measurand <meaurand I>
--
3.4
2, 7
160
148
Measurand IL1,2,3, VL1,2,3,
P,Q,f
Ia, Ib, Ic measurand <meaurand II>
--
9
2, 7
160
Generic Function
240
Read Headings
Not supported
241
Read attributes of all entries of
a group
Not supported
243
Read directory of entry
Not supported
244
Real attribute of entry
Not supported
245
End of GGI
Not supported
249
Write entry w ith confirm
Not supported
250
Write entry w ith execute
Not supported
251
Write entry aborted
Not supported
Note (
∗
3): depends upon the relay model as follows:
Type ID=3.1
Type ID=3.2
Type ID=3.3
Type ID=3.4
Model
(INF=144)
(INF=145)
(INF=146)
(INF=147)
IL2
IL2
VL1-VL2
IL2
VL1-VL2 3-phase P 3-phase Q
IN
VEN
Model 400
Ib
Ib
-
Ib
-
-
-
Ie
-
Model 420
Ib
Ib
-
Ib
-
-
-
Ie
-
Type ID=9
Model
(INF=148)
IL1
IL2
IL3
VL1
VL2
VL3
3-phase P 3-phase Q
f
Model 400
Ia
Ib
Ic
-
-
-
-
-
-
Model 420
Ia
Ib
Ic
-
-
-
-
-
-
Above values are normalized by IECNF
∗
.
294
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...