6 F 2 T 0 1 7 2
Protcol Implementation eXtra Information for Testing (PIXIT) for IEC61850 interface in GRE series IED
・
Introduction
This document specifies the protocol implementation extra information for testing (PIXIT) of the
IEC 61850 interface in GRE series IED with communication firmware MVM850-01 series version
upper than A (MVM850-01-A).
Together with the PICS and the MICS the PIXIT forms the basis for a conformance test according to
IEC 61850-10.
・
Contents of this document
Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC
61850-10.
PIXIT for Association model
ID
Description
Value / Clarification
As1
Maximum number of clients that can
set-up an association simultaneously
6
As2
TCP_KEEPALIVE value
7200 seconds at the default setting.
Setting range is from 1s to 43200s.
As3
Lost connection detection time
After the KEEPALIVE is no response,
retrying 9 times every “X” seconds until
declaring that the association has been lost.
“X” is one tenth of TCP_KEEPALIVE value.
Ex. The lost connection detection time is 18s
(9 times x 2 s), when TCP_KEEPALIVE
value is 20 s.
As4
Is authentication supported
N
As5
What association parameters are
necessary for successful association
Transport selector
N
Session selector
N
Presentation selector N
AP Title
N
AE Qualifier
N
As6
If association parameters are
necessary for association, describe the
correct values e.g.
N.A.
As7
What is the maximum and minimum
MMS PDU size
Max MMS PDU size 8172
Min MMS PDU size
Not limited. It
depends on a request.
As8
What is the maximum startup time
after a power supply interrupt
180 seconds
Check the start-up signal
(No.227)
332
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...