6 F 2 T 0 1 7 2
PIXIT for Reporting model
ID
Description
Value / Clarification
Rp1
The supported trigger conditions are
(compare PICS)
integrity
Y
data change
Y
quality change
Y
data update
N
general interrogation Y
Rp2
The supported optional fields are
sequence-number
Y
report-time-stamp
Y
reason-for-inclusion Y
data-set-name
Y
data-reference
Y
buffer-overflow
Y
entryID
Y
conf-rev
Y
segmentation
Y
Rp3
Can the server send segmented
reports
Y
Rp4
Mechanism on second internal data
change notification of the same analogue
data value within buffer period
(Compare IEC 61850-7-2 $14.2.2.9)
Send report immediately
Rp5
Multi client URCB approach
(compare IEC 61850-7-2 $14.2.1)
Each URCB is visible to all clients
Rp6
What is the format of EntryID
It is made up of the circular buffer counter
at the time the event was entered.
Rp7
What is the buffer size for each BRCB
or how many reports can be buffered
For example, LLN0$ST$Health can be
stored 40 events.
Rp8
Pre-configured RCB attributes that
cannot be changed online when RptEna
= FALSE
(see also the ICD report settings)
N.A.
Rp9
May the reported data set contain:
- structured data objects?
- data attributes?
Y
Y
Rp10
What is the scan cycle for binary
events?
Is this fixed, configurable
GRE110: More than 1500 milliseconds
Fixed
Rp11
Does the device support to pre-assign a
RCB to a specific client in the SCL
N
335
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...