6 F 2 T 0 1 7 2
ID
Description
Value / Clarification
Go17
What is the behavior when a
subscribed GOOSE message is “test”
GOOSE subscribe quality information will
become QUESTIONABLE | TEST (=1100 0000
0001 0).
Payload data is not received.
Go18
What is the behavior when a
subscribed GOOSE message is
“ndsCom”
GOOSE subscribe quality information will
become QUESTIONABLE | INACCURATE
(=1100 0000 0100 0).
Payload data is not received.
Go19
Acceptable data type
Boolean
BitSring
Integer
Unsigned Integer
But each data size shall be less than 32 bits.
Other types (TimeStamp, OctetString, etc) will
be ignored by IED.
When GOOSE subscribe quality information is
GOOD, the IED receives the payload data.
Go20
Dataset structure of a subscribed
GOOSE
This is not checked. Two GOOSEs, which have
same header (e.g.GoID) and different dataset
structure, are treated as the same GOOSEs.
And if received GOOSEs have same header, the
fixed position of the GOOSE dataset is read. E.g.
the 1st element of the dataset is set to read, it
keeps reading the 1st element even if the dataset
structure is different.
Note:
Subscribed payload data structure is checked to
determine if IED accepts/discards the data;
however the TAL timeout is reset even when such
data is discarded.
Go21
What is the behavior when the
device starts up?
The device starts sending GOOSE from
stNum=1 and sqNum=1.
Go22
Is it supported to set the “ndsCom”
as TRUE?
N
TAL = Time Allowed to Live
338
Summary of Contents for GRE110
Page 183: ...6 F 2 T 0 1 7 2 Appendix B Signal List 184 ...
Page 191: ...6 F 2 T 0 1 7 2 Appendix C Event Record Items 192 ...
Page 196: ...6 F 2 T 0 1 7 2 Appendix D Binary Output Default Setting List 197 ...
Page 199: ...6 F 2 T 0 1 7 2 Appendix E Relay Menu Tree 200 ...
Page 210: ...6 F 2 T 0 1 7 2 Appendix F Case Outline 211 ...
Page 211: ...6 F 2 T 0 1 7 2 Case Outline for model 400 401 420 421 820 and 821 212 ...
Page 212: ...6 F 2 T 0 1 7 2 Case Outline for model 402 and 422 213 ...
Page 213: ...6 F 2 T 0 1 7 2 Appendix G Typical External Connection 214 ...
Page 245: ...6 F 2 T 0 1 7 2 Appendix J Return Repair Form 246 ...
Page 249: ...6 F 2 T 0 1 7 2 Customer Name Company Name Address Telephone No Facsimile No Signature 250 ...
Page 250: ...6 F 2 T 0 1 7 2 Appendix K Technical Data 251 ...
Page 256: ...6 F 2 T 0 1 7 2 Appendix L Symbols Used in Scheme Logic 257 ...
Page 259: ...6 F 2 T 0 1 7 2 Appendix M Modbus Interoperability 260 ...
Page 289: ...6 F 2 T 0 1 7 2 Appendix N IEC60870 5 103 Interoperability 290 ...
Page 296: ...6 F 2 T 0 1 7 2 Appendix O PLC Default setting 297 ...
Page 298: ...6 F 2 T 0 1 7 2 Appendix P Inverse Time Characteristics 299 ...
Page 304: ...6 F 2 T 0 1 7 2 Appendix Q IEC61850 Interoperability 305 ...