117
6
F
2
S
0
8
5
0
is assigned by the PLC as a default setting.)
If [ARC-M] is set to "SPAR" or "Disable", autoreclose is not activated.
In "SPAR & TPAR" or "TPAR", if the operating conditions of the voltage and synchronism
check elements assigned by the PLC as default are not satisfied during three-phase reclosing, the
TRR is then picked up and reclosing is reset. In "MPAR2" or "MPAR3", if the operating
condition of interlinking is not satisfied, autoreclosing is not activated and three-phase final
tripping is performed in case of setting [MA-NOLK] to “FT”. In case of setting [MA-NOLK] to
"S" or "S+T", it is shifted to other reclose modes and three-phase final tripping is not performed.
Autoreclose for an evolving fault
Figure 2.15.2.2 shows the sequence diagram of autoreclose for an evolving fault when "SPAR &
TPAR" is selected. If single-phase tripping (1
φ
trip) is performed, the evolving fault detection
timer TEVLV is started at the same as the TSPR is started. If no evolving faults occur,
single-phase reclosing is performed when the TSPR is picked up.
Figure 2.15.2.2 Autoreclose for Evolving Fault
As shown in the figure, if an evoving fault occurs before the TEVLV is picked up, three-phase
tripping (3
φ
trip) is performed. If this occurs, the TSPR and TEVLV are reset, and the TTPR1 is
now started.
After the TTPR1 is picked up, three-phase reclosing is performed based on the status of the
voltage and synchronism check elements output signal SYN-OP. If an evolving fault occurs after
the TEVLV has picked up, autoreclose is reset and reclosing is not performed.
In "MPAR2" or "MPAR3", an evolving fault only resets and restarts the dead time counter TSPR
provided the network conditions defined for linked circuits are satisfied, though not shown in
Figure 2.15.2.1.
Voltage and synchronism check
There are four voltage modes as shown below when all three phases of the circuit breaker are
open. The voltage and synchronism check is applicable to voltage modes 1 to 3 and controls the
energizing process of the lines and busbars in the three-phase autoreclose mode.
Evolving fault
First fault
Fault
Trip
3
φ
reclosing
1
φ
reclosing
1
φ
trip
3
φ
trip
TSPR
TEVLV
TSPR
TTPR1
TEVLV
TTPR1
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...