Check that the A-phase differential current Ida on the "Metering" screen coincides with the Id
mentioned above with an error within
±
7%.
End-to-end test setup
When the percentage restraint characteristic is checked, an end-to-end setup using two relays is
required.
<Testing at laboratory>
If the relays can be collected and tested at a laboratory, the end-to-end test is possible by directly
connecting their communication ports. Figure 6.5.1.3 (a) shows the testing circuit of the
laboratory end-to-end test.
In case of two-terminal applications, the signal terminals CH1-TX1 and -RX1 of one relay are
directly connected to CH1-RX1 and -TX1 of another relay.
Note:
When the relays have an electrical telecommunications interface in accordance with
CCITT-G703-1.2.1 or an optical interface (Short wavelength light, GI, 2km class), the scheme
switch [D. test] must be set to “1” (= On) to test them under the direct connection of the
communication circuits.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...