31
6
F
2
S
0
8
5
0
(a) Direct link
(b) Electrical link via multiplexer
(c) Optical link via multiplexer
Figure 2.2.13.2 Link to Communication Circuit
Direct link
When connected to single-mode (SM) 10/125
µ
m type of dedicated optical fiber communication
circuits and using Duplex LC type connector for 30km class, the optical transmitter is an LD
with output power of more
than –13dBm and the optical receiver is a PIN diode with a sensitivity
of less than –30dBm. For 80km class, the optical transmitter is an LD with output power of more
than –5dBm and the optical receiver is a PIN diode with a sensitivity of less than –34dBm.
When connected to graded-index (GI) multi-mode 50/125
µ
m type or 62.5/125
µ
m type of
dedicated optical fiber telecommunication circuit and using an ST type connector, the optical
transmitter is an LED with output power of more
than –19dBm or –16dBm and the optical
receiver is a PIN diode with a sensitivity of less than –24dBm.
For details, refer to Appendix K.
Link via multiplexer
The GRL100 can be linked to a multiplexed communication circuit with an electrical or optical
interface. The electrical interface supports CCITT G703-1.2.1, G703-1.2.2 and 1.2.3,
X.21(RS530) or RS422. Twisted pair cable with shield (
<
60m) is used for connecting the relay
and multiplexer.
In the optical interface, optical fibers of graded-index multi-mode 50/125
µ
m or 62.5/125
µ
m
type are used and an optical to electrical converter is provided at the end of the multiplexer. The
electrical interface between the converter and the multiplexer supports CCITT G703-1.2.1,
G703-1.2.2 and 1.2.3, X.21(RS530) or RS422.
A D-sub connector (DB-25) or an ST connector is used for electrical linking and optical linking,
respectively.
O/E: Optical/Electrical converter
MUX: Multiplexer
Optical interface
GRL100
Twisted pair cable
with shield
<
60m
MUX
Optical
fibers
O/E
GRL100
Multiplexed circuit
Twisted pair cable with shield
<
60m
MUX
Electrical interface
GRL100
Optical fiber circuit
Optical interface
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...