Minimum Operating Current of Distance Protection
Current
0.08A (1A relay), 0.4A (5A relay)
Residual Current Compensation
Residual current compensation for reactance element
of Z1G, Z2G, ZRG
Earth return compensation
Mutual coupling compensation (ZRG excluded)
Adjustable as follows:
0 to 1000% in 1% steps
0 to 1000% in 1% steps
Command Protection
Coordination time for BOP scheme
0 to 50ms in 1ms steps
Operating and Resetting Time of Distance Measuring Element
Typical operating time
Resetting time
20ms
Less than 30ms (for tripping output)
Less than 40ms (for signal output)
Power Swing Blocking
Detection zone (PSBZS, PSBZG)
Detection time
2.5 to 75.0
Ω
in 0.1
Ω
steps (1A relay)
0.50 to 15.00 in 0.01
Ω
steps (5A relay)
20 to 60ms in 1ms steps
Phase Selection Element
Undervoltage
Impedance
Characteristic angle
Residual current compensation
10 to 60V in 1V steps
0.0 to 250.0
Ω
in 0.1
Ω
steps (1A relay)
0.0 to 50.0
Ω
in 0.1
Ω
steps (5A relay)
45
°
to 90
°
in 1
°
steps
Automatically set according to residual current
compensation setting of reactance element
Weak Infeed and Echo Protection
Phase-to-phase undervoltage element
Phase-to-earth undervoltage element
50 to 100V in 1V steps
10 to 60V in 1V steps
Directional Earth Fault Protection
Characteristic angle
Polarising voltage (3V0)
Zero-sequence current (3I0)
Time for backup trip
0 to 90
°
in 1
°
steps (3I0 lags for
−
3V0)
1.7 to 21.0V in 0.1V steps
0.10 to 1.00A in 0.01A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
Directional Earth Fault Command Protection
Time for delayed trip
Coordination time
0.00 to 0.30s in 0.01s steps
0 to 50ms in 1ms steps
Inverse Time Overcurrent Protection
OCI (for phase fault protection)
OCI time multiplier
OCI characteristic
Reset time delay
0.10 to 5.00A in 0.01A steps (1A relay)
0.5 to 25.0A in 0.1A steps (5A relay)
0.05 to 1.00 in 0.01 steps
Standard / Very / Extremely / Long-time inverse
0.0 to 10.0s in 0.1s steps
EFI (for earth fault protection)
EFI time multiplier
EFI characteristic
Reset time delay
0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.05 to 1.00 in 0.01 steps
Standard / Very / Extremely / Long-time inverse
0.0 to 10.0s in 0.1s steps
Definite Time Overcurrent Protection
OC (for phase fault protection)
OC time delay
0.1 to 20.0A in 0.1A steps (1A relay)
0.5 to 100.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
EF (for earth fault protection)
EF time delay
0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...