Accuracy
Current differential protection: pick-up
±
5% (
±
7% at I
<
0.3
×
In)
Distance measuring element
Static accuracy
Static angle accuracy
Transient overreach
±
5% under SIR
<
30,
±
10% under 30
<
SIR
<
50
±
5
°
+
5%
Inverse time overcurrent characteristics
±
5% or 30ms(1.5 to 30 times setting)
Definite time overcurrent protection: pick-up
±
5%
Overcurrent element for BF: pick-up
±
5%
Autoreclose function
Number of shots
1 to 4 shots
Timer settings
Dead time for single-phase autoreclose
Dead time for three-phase autoreclose
Multi-shot dead line time
Multi-shot reset time
Reclaim time
Pulse width of reclosing signal output
Autoreclose reset time
Reset time for developing fault
0.01 to 10.00s in 0.01s steps
0.01 to 100.00s in 0.01s steps
5.0 to 300.0s in 0.1s steps
5.0 to 300.0s in 0.1s steps
5 to 300s in 1s steps
0.1 to 10.0s in 0.1s steps
0.01 to 100.00s in 0.01s steps
0.01 to 10.00s in 0.01s steps
One-and-a-half breaker system
Follower breaker autoreclose delay time
0.1 to 10.0s in 0.1s steps
Voltage and synchronism check element
Synchronism check angle
UV element
OV element
Busbar or line dead check
Busbar or line live check
Synchronism check time
Voltage check time
5
°
to 75
°
in 1
°
steps
60 to 150V in 1V steps
10 to 100V in 1V steps
10 to 100V in 1V steps
10 to 100V in 1V steps
0.01 to 10.00s in 0.01s steps
0.01 to 1.00s in 0.01s steps
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase)
Undervoltage element (phase-to-earth)
Current change detection element
Residual voltage element
Residual current element
50 to 100V in 1V steps
10 to 60V in 1V steps
0.1A fixed (1A relay)
0.5A fixed (5A relay)
20V fixed
Common use with earth fault detection element
Fault Locator
Line resistance and reactance settings
0.0 to 999.9
Ω
in 0.1
Ω
steps (1A relay)
0.00 to 199.99
Ω
in 0.01
Ω
steps (5A relay)
Line length
0.0 to 399.9km in 0.1km steps
Accuracy
Two terminal
Three terminal
±
1km (up to 100km) or
±
1% (up to 399.9km at DIFI=0.5In
setting and Id=2In
±
2km (up to 100km) or
±
2% (up to 399.9km at DIFI=0.25In
setting and Id=2In
Minimum measuring cycles
2 cycles
Disturbance Record Initiation
Overcurrent element
0.1 to 50.0A in 0.1A steps (1A relay)
0.5 to 250.0A in 0.1A steps (5A relay)
Undervoltage element
0 to 132V in 1V steps (for phase fault)
0 to 76V in 1V steps (for earth fault)
Pre-fault time
0.3s (fixed)
Post-fault time
0.1 to 3.0 in 0.1s steps
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...