408
6
F
2
S
0
8
5
0
ENVIRONMENTAL PERFORMANCE CLAIMS
Test Standards
Details
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating range: -10
°
C to +55
°
C.
Storage / Transit: -25
°
C to +70
°
C.
Humidity IEC60068-2-78
56 days at 40
°
C and 93% relative humidity.
Enclosure Protection
IEC60529
IP51 (Rear: IP20)
Mechanical Environment
Vibration IEC60255-21-1
Response - Class 1
Endurance - Class 1
Shock and Bump
IEC60255-21-2
Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC60255-21-3
Class
1
Electrical Environment
Dielectric Withstand
IEC60255-5
2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage Impulse
IEC60255-5
Three positive and three negative impulses of 5kV(peak),
1.2/50
µ
s, 0.5J between all terminals and between all terminals
and earth.
Electromagnetic Environment
High Frequency
Disturbance /
Damped Oscillatory
Wave
IEC60255-22-1 Class 3,
IEC61000-4-12 /
EN61000-4-12
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
Electrostatic
Discharge
IEC60255-22-2 Class 3,
IEC61000-4-2 /
EN61000-4-2
6kV contact discharge, 8kV air discharge.
Radiated RF
Electromagnetic
Disturbance
IEC60255-22-3 Class 3,
IEC61000-4-3 /
EN61000-4-3
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
900 and 1890MHz.
Fast Transient
Disturbance
IEC60255-22-4,
IEC61000-4-4 /
EN61000-4-4
4kV, 2.5kHz, 5/50ns applied to all inputs.
Surge Immunity
IEC60255-22-5,
IEC61000-4-5 /
EN61000-4-5
1.2/50
µ
s surge in common/differential modes:
HV ports: 2kV/1kV (peak)
PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF
Electromagnetic
Disturbance
IEC60255-22-6 Class 3,
IEC61000-4-6 /
EN61000-4-6
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
Power Frequency
Disturbance
IEC60255-22-7,
IEC61000-4-16 /
EN61000-4-16
300V 50Hz for 10s applied to ports in common mode.
150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted and
Radiated Emissions
IEC60255-25,
EN55022 Class A,
IEC61000-6-4 /
EN61000-6-4
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 30m):
30 to 230MHz: <30dB
230 to 1000MHz: <37dB
89/336/EEC
Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to EN
61000-6-2 and EN 61000-6-4.
73/23/EEC
Compliance with the European Commission Low Voltage
Directive is demonstrated according to EN 50178 and EN
60255-5.
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...