50
6
F
2
S
0
8
5
0
Element Range
Step
Default
Remarks
Z2G
0.01 - 50.00
Ω
0.01
Ω
4.00
Ω
Z2 reach
(0.10 - 250.00
Ω
0.01
Ω
20.00
Ω
)
BFR2G
0.10 - 20.00
Ω
0.01
Ω
5.10
Ω
Forward right blinder reach for Z2
(0.5 - 100.0
Ω
0.1
Ω
25.5
Ω
)
Z3G
0.01 - 100.00
Ω
0.01
Ω
8.00
Ω
Z3 reach
(0.1 – 500.0
Ω
0.1
Ω
40.0
Ω
)
Z3G
θ
(*2)
45 - 90°
1°
85°
Characteristic angle of mho element
ZBG
θ
(*3)
0° - 45°
1°
30°
Angle of directional element
BFRG
0.10 - 20.00
Ω
0.01
Ω
5.10
Ω
Forward right blinder reach for Z3
(0.5 - 100.0
Ω
0.1
Ω
25.5
Ω
)
BFLG
θ
90° - 135°
1°
120°
Forward left blinder angle
ZRG
0.01 - 100.00
Ω
0.01
Ω
4.00
Ω
ZR reach
(0.1 – 500.0
Ω
0.1
Ω
20.0
Ω
)
Z4G
0.01 - 100.00
Ω
0.01
Ω
8.00
Ω
Z4 reach
(0.1 – 500.0
Ω
0.1
Ω
40.0
Ω
)
BRRG
0.10 - 20.00
Ω
0.01
Ω
5.10
Ω
Reverse right blinder reach
(0.5 - 100.0
Ω
0.1
Ω
25.5
Ω
)
Krs
0 - 1000 %
1%
340%
Residual current compensation = R0/R1
Kxs
0 - 1000 %
1%
340%
Residual current compensation = X0/X1
Krm
0 - 1000 %
1%
300%
Mutual coupling compensation = ROM/R1
Kxm
0 - 1000 %
1%
300%
Mutual coupling compensation = XOM/X1
KrsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = R0/R1
KxsR
0 - 1000 %
1%
100%
Residual current compensation for ZR = X0/X1
TZ1G
0.00 - 10.00 s
0.01 s
0.00 s
Zone 1 timer
TZ2G
0.00 - 10.00 s
0.01 s
0.30 s
Zone 2 timer
TZ3G
0.00 - 10.00 s
0.01 s
0.40 s
Zone 3 timer
TZRG
0.00 - 10.00 s
0.01 s
0.60 s
Zone R timer
UVC
Phase selection element
UVCV
10 - 60 V
1 V
48 V
Voltage setting
UVCZ
0.0 - 50.0
Ω
0.1
Ω
2.0
Ω
Reach setting
(0 - 250
Ω
1
Ω
10
Ω
)
UVC
θ
45° - 90°
1°
85°
Characteristic angle
EFL
0.5 – 5.0 A
0.1 A
1.0 A
Earth fault detection
(0.10 – 1.00 A
0.01 A
0.20 A)
UVPWI
30 V fixed
UV for positive weak infeed
Scheme switch
DISCR
OFF/ON
OFF
Distance carrier protection enable
Z1CNT
1/2/3/4/5/6
2
Zone 1 trip mode selection
BLZONE
COM/IND
COM
Blinder setting mode
PSB - Z1
OFF/ON
ON
Z1 power swing blocking
PSB - Z2
OFF/ON
ON
Z2 power swing blocking
PSB - Z3
OFF/ON
OFF
Z3 power swing blocking
PSB - ZR
OFF/ON
OFF
ZR power swing blocking
Z2TP
OFF/ON
ON
Z2 trip enable
Z3TP
OFF/ON
ON
Z3 trip enable
ZRTP
OFF/ON
OFF
ZR trip enable
UVPWIEN
OFF/ON
OFF
Countermeasures for overreaching of a
leading-phase distance element at positive
phase weak infeed condition
www
. ElectricalPartManuals
. com
Summary of Contents for GRL100-701B
Page 329: ... 328 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 339: ... 338 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 351: ... 350 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 381: ... 380 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 413: ... 412 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 417: ... 416 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 453: ... 452 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 457: ... 456 6 F 2 S 0 8 5 0 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 473: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...