ZIC
0.00 - 5.00 A
0.01 A
0.0 0
Charging current setting
( 0.00 - 1.00 A
0.01 A
0.00 A) (*)
Vn
100 - 120
1 V
110 V
Rated line voltage
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
Setting of phase selection element
Phase selection is required only for faults on the protected line. Therefore, impedance reach
setting UVCZ is set to 120% of the positive-sequence impedance of the protected line. Impedance
angle setting UVC
θ
is set the same as the protected line angle.
Undervoltage setting UVCV is set higher than the estimated maximum fault voltage at the fault
point for a single-phase earth fault.