4.2.7.1 Setting the switches
The automatic monitor function (A.M.F.) can be disabled by setting the switch [A.M.F] to
"OFF".
Disabling the A.M.F. prevents tripping from being blocked even in the event of a failure in the
items being monitored by this function. It also prevents failures from being displayed on the
"ALARM" LED and LCD described in Section 4.2.1. No events related to A.M.F. are recorded,
either.
Disabling A.M.F. is useful for blocking the output of unnecessary alarms during testing.
Note:
Set the switch [A.M.F] to "Off" before applying the test inputs, when the A.M.F is disabled.
The switch [Reset] is used to test the THR and V/F elements. When the switch [Reset] is set to
"1", the time counting of inverse time characteristic can be forcibly reset.
While the switch [A.M.F] is set to "0" or [Reset] is set to "1", the red "TESTING" LED is lit for
alarm purposes.
Caution:
Be sure to restore these switches after the tests are completed.
Disabling automatic monitoring
Press 5 (= Test) on the top "MENU" screen to display the "Test" screen.
/ 1
T e s t
1 = S w i t c h
2 =
3 =
B i n a r y
o u t p u t
4 =
T i m e r
L o g i c
c i r c u i t
Press 1 (= Switch) to display the "Switch" screen.
/ 2 S w i t c h
1 / 3
A . M . F .
0 = O f f
1 = O n
0
1
R e s e t
0 = O f f
1 = O n
I E C T S T
0 = O f f
1 = O n
1
Enter 0 for A.M.F to disable the A.M.F. and press the
ENTER
key.
Enter 1(=On) for IECTST to transmit ‘test mode’ to the control system by IEC60870-5-103
communication when testing the local relay, and press the
ENTER
key.
Press the
END
key to return to the "Test" screen.
Resetting the time counting of THR and V/F elements
Enter 1 for Reset to reset the time counting forcibly and press the
ENTER
key.
Press the
END
key to return to the "Test" screen.
4.2.7.2 Binary Output Relay
It is possible to forcibly operate all binary output relays for checking connections with the
external devices. Forced operation can be performed on one or more binary outputs at a time for
each module.
Press 2 (= Binary output) on the "Test" screen to display the "Binary output" screen.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......