6.5.1.9 Frequency element FRQ
The frequency element is checked on the following items
Operating frequency
Undervoltage block
Operating frequency test
The testing circuit is shown in Figure 6.5.13.
Variable
frequency
source
TB 1 -27
V
-28
GRT100
Monitoring
jack
A
0V
TB 4 - A16
- A17
E
DC
power
supply
DC
voltmeter
V
f
Figure 6.5.13 Testing Frequency Element (Model 100s, 200s)
The output signal numbers of the FRQ elements are as follows:
Element
Signal number
Remarks
81-1
89
Underfrequency tripping
91
Overfrequency tripping
81-2
90
Underfrequency alarm
92
Overfrequency alarm
Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit"
screen.
Enter a signal number to observe the FRQ output at monitoring jack A and press the
ENTER
key.
Apply rated voltage and change the magnitude of the frequency applied and measure the
value at which the element operates. Check that the measured value is within
0.03Hz of
the setting.
Undervoltage block test
Apply rated voltage and change the magnitude of frequency to operate the element.
Keep the frequency that the element is operating, and change the magnitude of the voltage
applied from the rated voltage to less than UV setting voltage. And then, check that the
element resets.
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......