190
6
F
2
S
0
7
8
9
Standard (Except Y-TYPE)
Default Setting of Relay Series
(50Hz / 60Hz)
Name
Range
Units
Contents
2-Winding
3-Winding
1
2
3
4
5
6
7
8
50Hz
60Hz
101B
102B
201B
202B
231
22,278
BISW7
Norm - Inv
-
ditto
Norm
232
22,279
BISW8
Norm - Inv
-
ditto
Norm
233
22,280
BISW9
Norm - Inv
-
ditto
Norm
234
22,281
BISW10
Norm - Inv
-
ditto
Norm
235
22,282
BISW11
Norm - Inv
-
ditto
Norm
236
22,283
BISW12
Norm - Inv
-
ditto
Norm
237
22,284
BISW13
Norm - Inv
-
ditto
Norm
238
22,285
BISW14
Norm - Inv
-
ditto
Norm
239
22,286
BISW15
Norm - Inv
-
ditto
Norm
240
22,287
BISW16
Norm - Inv
-
ditto
Norm
241
22,400
LED1
0 - 3071
-
Configrable
LEDs
0
242
22,401
LED2
0 - 3071
-
ditto
0
243
22,402
LED3
0 - 3071
-
ditto
0
244
22,403
LED4
0 - 3071
-
ditto
0
245
21,632
Plant name
Specified by user
-
Plant name
Specified by user
246
21,648
Description
ditto
-
Memorandum for
user
Specified by user
247
21,888
Address-HDLC
1 - 32
-
Relay ID No. for
RSM
1
248
21,889
Address-IEC
1 - 254
-
Relay ID No. for
IEC103
2
249
21,890
Address-MOD
1 - 247
-
Relay ID No. for
MODBUS
1
250
21,924
PRTCL1
RS485 Port Comm.
Protocol
HDLC
251
21,920
232C
-
Comm. speed for
RSM
9.6
252
21,921
IECBR
-
19.2
253
21,922
IECBLK
-
Normal
254
21,923
MODBR
-
Comm speed for
Modbus
19.2
255
21,810
Record-
Fault
Phase mode
Operating - Fault
-
Phase indication of
Fault recording
Operating
256
21,760
Mech.trip1
None - Operate - Reset - Both
-
Event record trigger
Both
257
21,761
Mech.trip2
None - Operate - Reset - Both
-
ditto
Both
258
21,762
Mech.trip3
None - Operate - Reset - Both
-
ditto
Both
259
21,763
Mech.trip4
None - Operate - Reset - Both
-
ditto
Both
260
21,764
Trip
None - Operate - Reset - Both
-
ditto
Both
261
21,765
Ind.Reset
None - Operate - Reset - Both
-
ditto
Both
262
21,766
Relay fail
None - Operate - Reset - Both
-
ditto
Both
263
21,767
CT1 err
None - Operate - Reset - Both
-
ditto
Both
264
21,768
CT2 err
None - Operate - Reset - Both
-
ditto
Both
265
21,769
CT3 err
None - Operate - Reset - Both
-
ditto
--
Both
266
21,771
Event1
None - Operate - Reset - Both
-
ditto
Both
267
21,772
Event2
None - Operate - Reset - Both
-
ditto
Both
268
21,773
Event3
None - Operate - Reset - Both
-
ditto
Both
269
21,774
Sys. Set change
None - Operate
-
ditto
Operate
270
21,775
Rly. Set change
None - Operate
-
ditto
Operate
271
21,776
Grp. Set change
None - Operate
-
ditto
Operate
272
21,816
Time
0.1 - 3.0
s
Disturbance record
1.0
273
21,824
1OCPS
0.10 - 20.00
pu
OC element for
disturbance
1.00
274
21,825
2OCPS
0.10 - 20.00
pu
recorder initiation
1.00
275
21,826
3OCPS
0.10 - 20.00
pu
--
1.00
276
21,828
1OCPG
0.05 - 20.00
pu
1.00
277
21,829
2OCPG
0.05 - 20.00
pu
1.00
278
21,830
3OCPG
0.05 - 20.00
pu
--
1.00
279
21,786
TRIP1
Off - On
-
Disturbance trigger
On
280
21,787
TRIP2
Off - On
-
ditto
On
№
Modbus address
comm
Active Group
Normal - Block
9.6 - 19.2
Record-
Event
record
Record-
Disturbanc
e
User Setting
LED
Descriptio
n
Communic
ation
HDLC - IEC103 - MODBUS
9.6 - 19.2 - 38.4 - 57.6
9.6 - 19.2
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......