TECHNICAL DATA
Ratings
AC current
1A or 5A
AC voltage
100V, 110V, 115V, 120V
Frequency
50Hz or 60Hz
DC power supply
AC ripple on DC supply IEC 60255-11
DC supply interruption IEC 60255-11
Permissive duration of DC supply voltage
interruption to maintain normal operation
Restart time
110Vdc/125Vdc (Operative range: 88 to 150Vdc)
220Vdc/250Vdc (Operative range: 176 to 300Vdc)
48Vdc/54Vdc/60Vdc (Operative range: 38.4 to 72Vdc)
24Vdc/30Vdc (Operative range: 19.2 to 36Vdc)
maximum 12%
maximum 50ms at 110Vdc
less than 10s
Overload rating
AC current input
4 times rated continuous
100 times rated for 1s
AC voltage input
2 times rated continuous
2.5 times rated for 1s
Burden
AC current circuit
0.3VA per phase (at rated 5A)
0.4VA at zero sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3VA at zero sequence circuit (at rated 1A)
AC voltage circuit
0.1VA (at rated voltage)
DC power supply
less than 15W (quiescent)
less than 25W(operation)
Binary input circuit
0.5W/input at 110Vdc
Current differential protection
Minimum operate current (ik)
0.10 to 1.00pu in 0.01pu steps
Slope 1 (p1)
10 to 100% in 1% steps
Slope 2 (p2)
10 to 200% in 1% steps
kp
1.00 to 20.00pu in 0.01pu steps
Vector group compensation (Winding 1 to 3) (d1
– d3) 0 to 11 (0 to 330deg in 30deg steps)
CT ratio correction (Winding 1 to 3) (kct1
– kct3)
0.05 to 50.00 in 0.01 steps
Inrush setting (2nd harmonic ratio) (k2f)
10 to 50% in 1% steps
Overexcitation setting (5th harmonic ratio) (k5f)
10 to 100% in 1% steps
Operating time
typical 35ms
High-set differential overcurrent protection
Overcurrent (kh)
2.00 to 20.00pu in 0.01pu steps
Operating time
typical 20ms
Restricted earth fault element
Minimum operating current
0.05 to 0.50pu in 0.01pu steps
Slope 1 (p1)
10 %
Slope 2 (p2)
50 to 100% in 1% steps
kp
0.50 to 2.00pu in 0.01pu steps
CT ratio correction (kct)
1.00 to 50.00 in 0.01 steps
Operating time
typical 35ms
Summary of Contents for GRT100 Series
Page 142: ... 141 6 F 2 S 0 7 8 9 Appendix A Block Diagram ...
Page 144: ... 143 6 F 2 S 0 7 8 9 Appendix B Signal List ...
Page 159: ... 158 6 F 2 S 0 7 8 9 ...
Page 160: ... 159 6 F 2 S 0 7 8 9 Appendix C Variable Timer List ...
Page 162: ... 161 6 F 2 S 0 7 8 9 Appendix D Binary Output Default Setting List ...
Page 165: ... 164 6 F 2 S 0 7 8 9 ...
Page 166: ... 165 6 F 2 S 0 7 8 9 Appendix E Details of Relay Menu and LCD and Button Operation ...
Page 174: ... 173 6 F 2 S 0 7 8 9 Appendix F Case Outline Flush Mount Type Rack Mount Type ...
Page 179: ... 178 6 F 2 S 0 7 8 9 ...
Page 180: ... 179 6 F 2 S 0 7 8 9 Appendix G External Connections ...
Page 185: ... 184 6 F 2 S 0 7 8 9 ...
Page 200: ... 199 6 F 2 S 0 7 8 9 ...
Page 201: ... 200 6 F 2 S 0 7 8 9 Appendix J Return Repair Form ...
Page 205: ... 204 6 F 2 S 0 7 8 9 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Page 206: ... 205 6 F 2 S 0 7 8 9 ...
Page 207: ... 206 6 F 2 S 0 7 8 9 Appendix K Technical Data ...
Page 220: ... 219 6 F 2 S 0 7 8 9 ...
Page 221: ... 220 6 F 2 S 0 7 8 9 Appendix M Symbols Used in Scheme Logic ...
Page 224: ... 223 6 F 2 S 0 7 8 9 ...
Page 225: ... 224 6 F 2 S 0 7 8 9 Appendix N Implementation of Thermal Model to IEC60255 8 ...
Page 228: ... 227 6 F 2 S 0 7 8 9 ...
Page 229: ... 228 6 F 2 S 0 7 8 9 Appendix O IEC60870 5 103 Interoperability and Troubleshooting ...
Page 241: ... 240 6 F 2 S 0 7 8 9 Appendix P Modbus Interoperability ...
Page 255: ... 254 6 F 2 S 0 7 8 9 ...
Page 256: ... 255 6 F 2 S 0 7 8 9 Appendix Q Inverse Time Characteristics ...
Page 259: ... 258 6 F 2 S 0 7 8 9 ...
Page 260: ... 259 6 F 2 S 0 7 8 9 Appendix R Failed Module Tracing and Replacement ...
Page 266: ... 265 6 F 2 S 0 7 8 9 Appendix S Ordering ...
Page 269: ... 268 6 F 2 S 0 7 8 9 3 1 Oct 2 2017 Republished under spin off company ...
Page 270: ......