Check that the operating time is within 1-1.5 cycle.
•
Set the scheme switch [SOTF-OC] to "Off" and [SOTF-Z
∗
] to "On" and repeat the above.
Breaker failure tripping
Set the scheme switch [BF1] to "T" or "TOC" and BF2 to "On".
•
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
•
Enter a signal number 199 for the TermA line to observe the retrip signal at monitoring jack A
and 200 for the TermB line to observe the adjacent circuit breaker trip signal at monitoring
jack B and press the ENTER key.
•
Apply a zone 1 fault and maintain it. Check that the retrip signal is generated after the time
setting of TBF1 and the adjacent circuit breaker trip signal is generated after the time setting of
the TBF2.
Out-of-step tripping
Set the scheme switch [OST] to "On".
To simulate out-of-step, the impedance seen by the OST element must be moved slowly from the
first quadrant to the second quadrant or vice versa.
The following shows the case of the former.
•
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
•
Enter signal number 203 for the TermA line to observe the out-of-step tripping signal at
monitoring jack A and press the ENTER key.
•
Apply a three-phase rated voltage and current.
•
Gradually lower the voltage to zero, keeping the voltage and current sources in-phase. Then
gradually raise the voltage from zero to the rated value, while keeping the phase angle of
voltage and current in anti-phase.
During this process, keep the current at the rated value.
•
Check that out-of-step tripping takes places at monitoring jack A.
•
Check that out-of-step tripping does not take place if the voltage was lowered or raised steeply
or was gradually raised while retaining the phase angle of voltage and current in-phase, not
anti-phase.
Voltage transformer failure supervision
A voltage transformer (VT) failure is detected when an undervoltage element or residual
overvoltage element operates but a current change detection element or residual overcurrent
element does not operate accordingly.
VT failure detection is checked as follows:
•
Set the circuit breaker closed condition by applying a "1" signal to binary inputs
(CB_CONT-A, -B and -C).
•
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
•
Enter signal number 172 for the TermA line to observe the VT failure alarm signal, and 173
for the TermB line to observe the VT failure detection signal at monitoring jack A and B. Press
the ENTER key.
•
Apply a three-phase rated voltage. Then, remove single-, two- or three-phase voltage. Check
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...