6. Default setting
Default setting (1A rating / 5A rating)
1CB-ARC
1CB-ARC
2CB-ARC
User
2TERM
3TERM
2TERM
3TERM
2TERM
3TERM
Setting
5A rating
1A rating
214
216
224
226
211
221
311
321
323
1
Active group
1 - 8
-
Active setting group
1
1
2
Line name
Specified by user
-
Line name
Specified by user
Specified by user
3
VT
1 -
20000
-
VT ratio
2000
2000
4
VTs1
1 -
20000
-
VT ratio
2000
2000
5
VTs2
1 -
20000
-
VT ratio
--
--
2000
6
VTr1
1 -
20000
-
VT ratio for remote terminal
2000
2000
7
VTr2
1 -
20000
-
VT ratio for remote terminal
--
2000
--
2000
--
2000
8
CT
1 -
20000
-
CT ratio
400
400
9
CTr1
1 -
20000
-
CT ratio for remote terminal
400
400
10
CTr2
1 -
20000
-
CT ratio for remote terminal
--
400
--
400
--
400
11
X1
0.00 - 199.99
0.0 - 999.9
Ω
Fault location
2.00 / 10.0
2.00 / 10.0
12
X0
0.00 - 199.99
0.0 - 999.9
Ω
ditto
6.80 / 34.0
6.80 / 34.0
13
X0m
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
14
R1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.20 / 1.0
0.20 / 1.0
15
R0
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.70 / 3.5
0.70 / 3.5
16
R0m
0.00 - 199.99
0.0 - 999.9
Ω
ditto
0.20 / 1.0
0.20 / 1.0
17
Z0B-L
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
18
Z0B-R
0.00 - 199.99
0.0 - 999.9
Ω
ditto
2.00 / 10.0
2.00 / 10.0
19
Kab
80 - 120
%
ditto
100
100
20
Kbc
80 - 120
%
ditto
100
100
21
Kca
80 - 120
%
ditto
100
100
22
Ka
80 - 120
%
ditto
100
100
23
Kb
80 - 120
%
ditto
100
100
24
Kc
80 - 120
%
ditto
100
100
25
Line
0.0 - 399.9
km
ditto
50
50
26
2X1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
--
2.00 / 10.0
--
2.00 / 10.0
--
2.00 / 10.0
27
2R1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
--
0.20 / 1.0
--
0.20 / 1.0
--
0.20 / 1.0
28
2Line
0.0 - 399.9
km
ditto
--
50
--
50
--
50
29
3X1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
--
2.00 / 10.0
--
2.00 / 10.0
--
2.00 / 10.0
30
3R1
0.00 - 199.99
0.0 - 999.9
Ω
ditto
--
0.20 / 1.0
--
0.20 / 1.0
--
0.20 / 1.0
31
3Line
0.0 - 399.9
km
ditto
--
50
--
50
--
50
32
Protection scheme
3ZONE - Z1-EXT - PUP - POP - UOP
- BOP - POP+DEF - UOP+DEF -
BOP+DEF - PUP+DEF
-
Protection scheme selection
POP
POP
33
CO.LINK
Int - Ext
-
Communication link (External or Integral)
Int
Int
34
SP.SYN.
Master - Slave
-
SP synchronization setting
Master
Master
35
TERM
2TERM - 3TERM - Dual
-
Terminal selection
--
3TERM
--
3TERM
--
3TERM
36
CH.USE
Both - CH1USE - CH2USE
-
For chain topology
--
Both
--
Both
--
Both
37
RYIDSV
Off - On
-
Relay address supervision
On
On
38
CH.CON
Normal - Exchange
-
Channel exchanger
--
Normal
--
Normal
--
Normal
39
T.SFT1
Off - On
-
CH#1 bit shifter for multiplexer link
Off
Off
40
T.SFT2
Off - On
-
CH#2 bit shifter for multiplexer link
--
Off
--
Off
--
Off
41
B.SYN1
Off - On
-
CH#1 bit sync. for multiplexer
On
On
42
B.SYN2
Off - On
-
CH#2 bit sync. for multiplexer
--
On
--
On
--
On
43
RYID
0 - 63
-
Relay address for local terminal
0
0
44
RYID1
0 - 63
-
Relay address for remote terminal 1
0
0
45
RYID2
0 - 63
-
Relay address for remote terminal 2
--
0
--
0
--
0
46
TDSV
100 - 16000
us
Transmission delay time supervision
6000
6000
47
TCDT1
-10000 - 10000
us
Transmission delay time adjust (CH1)
0
0
48
TCDT2
-10000 - 10000
us
Transmission delay time adjust (CH2)
--
0
--
0
--
0
49
ZS-C
Mho - Quad
-
ZS relay characteristic
Mho
Mho
50
ZG-C
Mho - Quad
-
ZG relay characteristic
Mho
Mho
51
BLZONE
COM - IND
-
Blinder setting mode
COM
COM
52
Z1CNT
1 - 2 - 3 - 4 - 5
-
Z1 trip mode
1
1
53
PSB-Z1
Off - On
-
PSB for Z1 element
On
On
54
PSB-Z1X
Off - On
-
PSB for Z1X element
On
On
55
PSB-Z2
Off - On
-
PSB for Z2 element
On
On
56
PSB-Z3
Off - On
-
PSB for Z3 element
Off
Off
57
PSB-CR
Off - On
-
PSB for carrier trip
On
On
58
PSB-ZF
Off - On
-
PSB for ZF element
Off
Off
59
PSB-ZR1
Off - On
-
PSB for ZR1 element
Off
Off
60
PSB-ZR2
Off - On
-
PSB for ZR2 element
Off
Off
61
PSB-TP
Off - On
-
Trip for under PSB
On
On
62
UVPWIEN
Off - On
-
Counter measures for overrech of leading
phase at positive phase weak infeed
Off
Off
63
SCFCNT
BLK - Trip
-
Carrier trip operation under severe CF
BLK
BLK
64
STUB
Off - On
-
Stub protection
Off
Off
65
SOTF-DL
CB - UV - Both
-
SOTF condition judged
CB
CB
66
SOTF-OC
Off - On
-
SOTF OC trip
On
On
67
SOTF-Z1
Off - On
-
SOTF Zone1 trip
Off
Off
68
SOTF-Z2
Off - On
-
SOTF Zone2 trip
Off
Off
69
SOTF-Z3
Off - On
-
SOTF Zone3 trip
Off
Off
70
SOTF-F
Off - On
-
SOTF Zone-F trip
Off
Off
№
Name
Range
Units
Contents
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...