2.4.14 Voltage Transformer Failure Supervision
When a fault occurs in the secondary circuit of the voltage transformer (VT), the voltage
dependent measuring elements may operate incorrectly. GRZ100 incorporates a VT failure
supervision function (VTFS) as a measure against such incorrect operation. When the VTFS
detects a VT failure, it blocks the following voltage dependent protections instantaneously. In 10
seconds, it displays the VT failure and outputs an alarm.
•
Zone 1-3, F, R1, R2 and ND distance protection
•
Zone 1 extension protection
•
Directional earth fault protection
•
Command
protection
Resetting of the blocks above and resetting of the display and alarm are automatically performed
when it is confirmed that all three phases are healthy.
A binary input signal to indicate a miniature circuit breaker trip in the VT circuits is also available
for the VTFS.
Scheme logic
Figure 2.4.14.1 shows the scheme logic for the VTFS. VT failures are detected under any one of
the following conditions and then a trip block signal VTF is output.
VTF1: The phase-to-phase undervoltage element UVFS or phase-to-earth undervoltage
element UVFG operates (UVFS = 1 or UVFG =1) when the three phases of the
circuit breaker are closed (CB-AND = 1) and the phase current change detection
element OCD does not operate (OCD = 0).
VTF2: The residual overcurrent element EFL does not operate (EFL = 0), the residual
overvoltage element OVG operates (OVG = 1) and the phase current change
detection element OCD does not operate (OCD = 0).
In order to prevent detection of false VT failures due to unequal pole closing of the circuit breaker,
the VTFS is blocked for 200 ms after line energisation.
The trip block signal VTF is reset 100 milliseconds after the VT failure condition has reset. When
the VTF continues for 10s or more, an alarm signal VTF-ALARM is output.
Further, the VT failure is detected when the binary input signal (PLC signal) EXT_VTF is
received.
This function can be enabled or disabled by the scheme switch [VTF1EN] or [VTF2EN] and has a
programmable reset characteristic. When set to “ON”, the latched operation for VTF1 is reset by
reset of UVFS/UVFG element, and that for VTF2 is reset by reset of OVG element. Set to
“OPT-ON” to reset the latched operation also when OCD or EFL operates.
The VTFS can be disabled by the PLC signal VTF_BLOCK.
www
. ElectricalPartManuals
. com
Summary of Contents for GRZ100-211B
Page 323: ... 322 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 343: ... 342 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 383: ... 382 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 395: ... 394 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 411: ... 410 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 423: ... 422 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 443: ... 442 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 451: ... 450 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 459: ... 458 6 F 2 S 0 8 3 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Page 463: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...