GRZ100
12
TECHNICAL DATA
Ratings
AC current I
n
:
1A or 5A
AC voltage V
n
:
100V, 110V, 115V, 120V
Frequency:
50Hz or 60Hz
DC power supply:
110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc)
48Vdc/54Vdc/60Vdc (Operative range: 38.4 - 72Vdc)
24Vdc/30Vdc (Operative range: 19.2 – 36Vdc)
AC ripple on DC supply IEC60255-11
maximum 12%
DC supply interruption IEC60255-11
Permissive duration of DC supply voltage
interruption to maintain normal operation:
Restart time:
less than 50ms at 110V
less than 10s
Binary input circuit DC voltage
110Vdc/125Vdc
220Vdc/250Vdc
48Vdc/54Vdc/60Vdc
24Vdc/30Vdc
Overload Ratings
AC current input
AC voltage input
4 times rated continuous
100 times rated for 1s
2 times rated continuous
2.5 times rated for 1s
Burden
AC current input
0.2VA per phase (at rated 5A)
0.4 VA at zero-sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3 VA at zero-sequence circuit (at rated 1A)
AC voltage input
0.1VA (at rated voltage)
DC power supply:
less than15W (quiescent)
less than 25W (operation)
Binary input circuit:
≤
0.5W/input at 110Vdc
CT Ratio Setting
CT ratio
1 to 20000 in 1 steps
Full Scale of Current for Measurement
Current
65 times rated current
Phase Fault Distance Measuring Element
Z1S, Z2S and Z1XS
Z1S
θ
1
Z1S
θ
2
ZFS, ZR1S and ZR2S
Z3S and Z4S
Characteristic angle
Z1S and Z4S offset
ZNDS
Blinder (BFRS1, BFRS2, BFRS3, BRRS, BNDS)
BRLS: Linked with BRRS
Characteristic angle: (BFRS1, BFRS2, BFRS3, BRRS, BNDS)
Characteristic angle (BFLS)
0.10 to 250.00
Ω
in 0.01
Ω
steps (1A relay)
0.01 to 50.00
Ω
in 0.01
Ω
steps (5A relay)
0
°
to 45
°
in 1
°
steps
45
°
to 90
°
in 1
°
steps
0.1 to 250.0
Ω
in 0.1
Ω
steps (1A relay)
0.01 to 50.00 in 0.01
Ω
steps (5A relay)
0.1 to 250.0
Ω
in 0.1
Ω
steps (1A relay)
0.01 to 50.00 in 0.01
Ω
steps (5A relay)
45
°
to 90
°
in 1
°
steps
7.5
Ω
fixed (1A relay)
1.5
Ω
fixed (5A relay)
0.1 to 250.0
Ω
in 0.1
Ω
steps (1A relay)
0.01 to 50.00 in 0.01
Ω
steps (5A relay)
0.5 to 100.0
Ω
in 0.1
Ω
steps (1A relay)
0.10 to 20.00
Ω
in 0.01
Ω
steps (5A relay)
75
°
fixed
90
°
to 135
°