GRZ100
17
Disturbance Record Initiation
Overcurrent element
Undervoltage element
Pre-fault time
Post-fault time
0.1 to 50.0A in 0.1A steps (1A relay)
0.5 to 250.0A in 0.1A steps (5A relay)
0 to 132V in 1V steps (for phase fault)
0 to 76V in 1V steps (for earth fault)
0.3s fixed
0.1 to 3.0s in 0.1s steps
Communication Port
Front communication port (local PC)
Connection
Cable type
Cable length
Connector
Point to point
Multi-core (straight)
15m (max.)
RS232C 9-pin D-subminiature connector female
Rear communication port (remote PC)
RS485 I/F:
Transmission data rate for RSM system
Connection
Connector
Cable and length
Isolation
64kbps
Multidrop mode (max. 32 relays)
Screw terminals
Twisted pair cable, max. 1200m
2kVac for 1min.
Fibre optic I/F:
ST connector, graded-index multi-mode 50/125
µ
m or
62.5/125
µ
m type optical fibres
Ethernet LAN I/F:
10BASE-T, RJ-45 connector
IRIG-B Port
Connection
Cable type
BNC connector
50 ohm coaxial cable
Binary Inputs
Operating voltage
Typical 74Vdc(min.70Vdc) for 110V/125Vdc rating
Typical 138Vdc(min.125Vdc) for 220V/250Vdc rating
Typical 31Vdc(min.28Vdc) for 48V/54V/60Vdc rating
Typical 15Vdc(min.14Vdc) for 24Vdc rating
Contact Ratings
Trip contacts
Make and carry
Break
Auxiliary contacts
Make and carry
Break
Durability
Make and carry
Break
5A continuously,
30A, 290Vdc for 0.5s (L/R=10ms)
0.15A, 290Vdc (L/R=40ms)
4A continuously,
10A, 220Vdc for 0.5s (L/R
≧
5ms)
0.1A, 220Vdc (L/R=40ms)
10,000 operations minimum
100,000 operations minimum
Mechanical design
Weight
Case colour
Installation
10kg (Type-A), 13kg (Type-B)
Munsell No. 10YR8/0.5
Flush mounting or rack mounting